37
2.11 Auxiliary Pool Water Heating
A properly sized Desert Aire dehumidifier equipped with the pool water heating option can maintain the pool
water temperature under normal conditions. However, like any refrigerated dehumidifier, the Desert Aire unit
may require days to heat a recently-filled pool by itself. For this reason, you should install an auxiliary pool
heater.
Desert Aire dehumidifiers ordered with the water heating option are provided with a set of dry contacts for
controlling an auxiliary pool water heater. The dehumidifier will be the primary source of water heating. If it
cannot keep up with the demand for pool heat, the Desert Aire controller will then energize the auxiliary water
heater.
Note: Do not use the aqua stat mounted on the auxiliary heater for temperature control. This can lead to
excessive water temperature fluctuation. It may also permanently prevent the dehumidifier from heating
pool water if the set point of the heater aqua stat is higher than the water heating set point of the dehumidifier.
2.12 Smoke Alarm Interlock
Desert Aire SA series dehumidifiers are equipped with a set of terminal blocks for interlocking with the smoke
alarm (alarm provided and installed by others). The smoke alarm contacts must be rated for at least 15 amps
at 24 VAC. The contacts must break when smoke is present. This will shut off the blower(s) and compressors.
See the dehumidifier wiring diagram for connection details.
Desert Aire - SA Manual
Содержание SA Series
Страница 2: ...2 ...
Страница 6: ...6 Desert Aire SA Manual ...
Страница 38: ...38 Desert Aire SA Manual ...
Страница 72: ...72 Desert Aire SA Manual ...
Страница 73: ...73 Desert Aire SA Manual ...
Страница 74: ...74 Desert Aire SA Manual ...
Страница 75: ...75 Desert Aire SA Manual ...
Страница 76: ...76 Desert Aire SA Manual ...
Страница 77: ...77 Desert Aire SA Manual ...