25
Ground Wire
L1
L2
L3
Main Power
Supply from
Disconnect Box
Main Power
Block in Unit
Factory Supplied
Wiring
Ground
Lug
Figure 17 - A Typical Desert Aire Three-Phase Power Block
Some equipment may contain a variable speed drive for the supply fan. The fan will run the correct
direction regardless of the input power. In these cases, the compressor must be “bumped” to determine
if it is pumping correctly. Use the controller display to view the analog inputs and briefly energize one of
the compressor contactors. The discharge pressure should increase and the suction pressure should
decrease when phasing is correct. Do not run the compressors in reverse rotation for an extended
period of time as damage will result.
To assist in compliance with NEC and local codes, a second lug connected to the service panel in
equipment with pool water condensers is provided. This lug is intended to be connected to the pool
equipotential bonding grid in the field when required by code. This also removes the possibility of
differences in potential between metals in the pool water and the water condenser that may accelerate
corrosion. The bonding lug should be connected to the equipotential grid with 8 AWG or larger solid
copper conductor.
2.8 Controls and Sensors
The standard Desert Aire SA series dehumidifiers are controlled by a microprocessor controller. This
controller monitors conditions such as room humidity and temperatures and controls the dehumidifier
accordingly. A separate controls manual has been provided. Refer to this separate manual for controller
and sensor specifications, operation, and options.
2.8.1 Air Temperature/Humidity Sensors
Duct Mount Temperature/Humidity Sensor
Install the duct-mount sensor in the return air duct upstream of any outdoor air intakes.
• Do not mount the sensor in a section of duct where false readings may occur due to
dead air regions, solar heat gain, or thermal losses in winter.
• Do not mount the sensor where water is likely to drip on it. Liquid moisture will ruin the
humidity sensing element in the sensor.
Desert Aire - SA Manual
Содержание SA Series
Страница 2: ...2 ...
Страница 6: ...6 Desert Aire SA Manual ...
Страница 38: ...38 Desert Aire SA Manual ...
Страница 72: ...72 Desert Aire SA Manual ...
Страница 73: ...73 Desert Aire SA Manual ...
Страница 74: ...74 Desert Aire SA Manual ...
Страница 75: ...75 Desert Aire SA Manual ...
Страница 76: ...76 Desert Aire SA Manual ...
Страница 77: ...77 Desert Aire SA Manual ...