
Document:
DS-M8--OPM-1.0M
Page 14 of 19
© DESAY INTELLIGENT CO. LTD.
T
+752 2617 333
WWW.DESAYOPTO.COM
3.2 Electrical
The power distribution system used must provide adequate protection against excess line current and
leakage currents to earth.
Electrical Characteristics for ONE M8
For large installations, a three-phase supply is recommended and the power from each phase should
be distributed evenly to the single-phase appliance coupler on each panel. The screen may be
conveniently split into sections (e.g. rows or columns), each powered from a single phase.
3.2.1 Circuit Protection
Each section of the screen should be protected by a Circuit Breaker to protect against high fault
currents, and a Residual Current Device (RCD) to detect earth leakage currents.
3.2.2 Earth Leakage Considerations
To reliably operate a LED video screen, the leakage value figure per panel must be known, or if the
leakage value is close to the breaker trip value, the breaker may trip at a very inopportune time.
Ensure that the total leakage current value per earth leakage breaker is at least 10% (preferably 20%)
below the value earth leakage breaker trip point to ensure that nuisance tripping does not occur. Earth
leakage current is normally a constant value, but can increase in wet or humid weather, so this margin
is suggested.
Each panel of the system has earth leakage current contributions from two switched-mode power
supplies and one RFI filter. The total earth leakage current per panel can be up to 3mA at 240V. If a
24mA RCD is used, then the maximum number of panels per section should be safely limited to 8.
3.2.3 Inrush-current and over-current considerations
Video screen panels draw a very high in-rush or surge current at the moment of switch-on. This
current can be twenty times the maximum operating current of the panel, but occurs only for a very
short time
–
typically less than half an AC power cycle
–
less than 10 ms.
On each M8 panel the in-rush current is 180A at 230V. However, maximum current in the steady-state
for a panel is considerably less: 2 A at 240 volts. This high in-rush current needs to be considered when
selecting a suitable circuit breaker to feed the panels. In choosing the circuit breaker, both the
maximum operating current and the in-rush (surge) current need to be considered.