INSTALLATION

Continued

CHECKING GAS CONNECTIONS

 WARNING: Test all gas piping 

and  connections,  internal  and 

external to unit, for leaks after 

installing or servicing. Correct 

all leaks at once.

  WARNING:  Never  use  an 

open flame to check for a leak. 

Apply  a  commercial  leak  de-

tection  solution  to  all  joints. 

Bubbles  forming  show  a  leak. 

Correct all leaks at once.

  CAUTION:  For  propane/LP 

units, make sure external regula-

tor  has  been  installed  between 

propane/LP  supply  and  heater. 

See guidelines under 

Connecting 

to Gas Supply

, page 13.

PRESSURE TESTING GAS SUPPLY 
PIPING SYSTEM 
Test Pressures In Excess Of 1/2 PSIG 
(3.5 kPa)

1.  Disconnect appliance with its appliance main 

gas valve (control valve) and equipment shutoff 

valve from gas supply piping. Pressures in ex-

cess of 1/2 psig will damage heater regulator.

2.  Cap off open end of gas pipe where equipment 

shutoff valve was connected.

3.  Pressurize supply piping system by either 

opening propane/LP supply tank valve for 

propane/LP gas or opening main gas valve 

located on or near gas meter for natural gas 

or using compressed air.

4.  Check all joints of gas supply piping system. 

Apply a commercial leak detection solution 

to all joints. Bubbles forming show a leak. 

5.  Correct all leaks at once.

6.  Reconnect heater and equipment shutoff valve 

to gas supply. Check reconnected fittings for 

leaks. 

*  Purchase  the  optional  CSA  design-certified 

equipment shutoff valve from your dealer. See 

Accessories

, page 41.

** Minimum inlet pressure for purpose of input 

adjustment. 

Figure 15 - Gas Connection (Remote-

Ready Models Only)

Gas Control Valve

 Tee  Pipe  Cap
 Joint  Nipple

3" Minimum

Sediment Trap

PROPANE/LP

 From 

External Regulator
(11" W.C.** to 
14" W.C. Pressure)

NATURAL

 

From Gas 

Meter (5" W.C.** 
to 10.5" W.C. 
Pressure)

CSA Design-Certified 
Equipment Shutoff Valve 
With 1/8" NPT Tap*

Approved 
Flexible Gas 
Hose (if allowed 
by local codes)

Figure 14 - Gas Connection

  Cap  Pipe  Tee
     Nipple Joint

3" Min.

Sediment Trap

Gas 
Regulator

CSA Design-Certified 
Equipment Shutoff Valve 
With 1/8" NPT Tap*

Approved Flexible Gas 
Hose (if allowed by 
local codes)

Natural 

From Gas 

Meter (5" W.C.** 

to 10.5" W.C. 

Pressure)

Propane/LP

From External 

Regulator

(11" W.C.** 

to 14" W.C. 

Pressure

Содержание VRL24NR

Страница 1: ...hbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a quali fied installer service agency o...

Страница 2: ...as supplier WARNING This is an unvented gas fired heat er It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air...

Страница 3: ...anual for reference It is your guide to safe and proper operation of this fireplace WARNING Any change to this heater or its controls can be dangerous WARNING Do not use a blower insert heat exchanger...

Страница 4: ...with pro pane LP models do not use propane LP fuel tank of less than 100 lb capacity 20 Provide adequate clearances around air openings Keep the appliance area clear and free from combustible ma teri...

Страница 5: ...y MA 02269 Note Where listed vented decorative logs are required thermostat models are not permitted Product Identification Base Assembly Piezo Ignitor Front and Rear Burner Control Knob Selector Swit...

Страница 6: ...ARNING This heater shall not be installed in a confined space or unusually tight con struction unless provisions are provided for adequate combus tionandventilationair Readthe following instructions t...

Страница 7: ...ireplace plus any adjoining rooms with doorless pas sageways or ventilation grills between the rooms 1 Determine the volume of the space length x width x height Length x Width x Height __________cu ft...

Страница 8: ...ovide adequate combustion and ventilation air byoneofthemethodsdescribed in the National Fuel Gas Code ANSIZ223 1 NFPA54Section5 3 or applicable local codes VENTILATION AIR Ventilation Air From Inside...

Страница 9: ...may cause pilot outage or sooting Use a heat resistant sealant Do not seal chimney flue damper INSTALLATION Continued WARNING Never install the heater in a bedroom or bathroom unless installed as a v...

Страница 10: ...tc must be at least 1 2 inch thick With sheet metal you must have noncombustiblematerialbehindit Noncombustible material must extend at least 8 inches up for all models If noncombustible material is l...

Страница 11: ...l clearances you must also meet required clearances between fireplace opening and mantel shelf If you do not meet the clearances listed below you will need a hood Determining Minimum Mantel Clearance...

Страница 12: ...hese tem peratures meet the requirement ofthenationalproductstandard Follow all minimum clearances shown in this manual NOTICE Ifyourinstallationdoes not meet the minimum clear ances shown you must do...

Страница 13: ...r vented operation If reasons number 1 or 2 above apply to you you must permanently open chimney flue damper You must install the damper clamp accessory to order see Accessories page 41 This will insu...

Страница 14: ...refully remove logs without moving heater base 7 Mark screw locations through one hole on each side of the mounting bracket see Figure 12 If installing in a brick bottom fireplace mark screw locations...

Страница 15: ...t shutoff valve union and plugged 1 8 NPT tap Locate NPT tap within reach for test gauge hook up NPT tap must be upstream from heater see Figure 14 or 15 page 16 depending on your model IMPORTANT Inst...

Страница 16: ...e LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air 4 Check all joints of gas supply piping system Apply a commercial leak detection solution to all...

Страница 17: ...LP supply tank valve 3 Make sure control knob of heater is in the OFF position 4 Check all joints from equipment shutoff valve to thermostat gas valve Thermostat Controlled Models or control valve Rem...

Страница 18: ...screws are in place and straight Models CSG3924NT CSG3924PT CSG3924NR CSG3924PR CTB3924NT CTB3924PT CTB3924NR CTB3924PR CSG3930NR and CSG3930PR 1 Place log 1 ember bed onto base over align ment screw...

Страница 19: ...dels VRL24NR VRL24PR VRL30NR VRL30PR VRL24NT VRL24PT VRL30NT and VRL30PT 1 Place log 1 ember bed onto base over log alignment screws to the left of front burner and behind middle burner Log 1 will sit...

Страница 20: ...You must operate this heater with a fireplace screen in place Make sure fireplace screen is closed before run ning heater NOTICE Duringinitialoperation of new heater burning logs will give off a pape...

Страница 21: ...ntil repairs are made light pilot with match To light pilot with match see Manual Lighting Procedure page 22 7 Keep control knob pressed in for30 seconds after lighting pilot After 30 seconds release...

Страница 22: ...with the chimney damper closed This will put all the heat into the room However there may be times you will desire the full flames of the HI heat setting but will find the heat output excessive You c...

Страница 23: ...urn control knob counter clockwise to the PILOT position Press in control knob for five 5 seconds see Figure 30 Note You may be running this heater for the first time after hooking up to gas sup ply I...

Страница 24: ...control knob to ON position Adjust flameadjustmentknobanywherebetweenHIand LO Slide the selector switch to the REMOTE position see Figure 33 Note The burner may light if hand held remote was on when...

Страница 25: ...the hand held remote to control the room temperature If the hand held remote is misplaced obstructed or for any reason cannot transmit to the receiver the receiver will shut off the fireplace after 8...

Страница 26: ...ocal computer store hardware store or home center may carry compressed air in a can You can use a vacuum cleaner in the blow position If using com pressed air in a can please follow the directions on...

Страница 27: ...htly blow air through the air inlet hole The access hole for propane LP pilot is on the front of the burner carriage as shown in Figure 42 The access hole for natural pilot is behind the pilot bracket...

Страница 28: ...en in stalled 5 Depleted gas supply propane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct OBSERVED PROBLEM When ignitor button is pressed there is no spark at ODS pilot When ig...

Страница 29: ...l or pro pane LP gas company 2 Clean burner s see Cleaning and Maintenance page 26 or replace burner orifice s 3 Contact qualified service person 1 Clean burner see Cleaning and Maintenance page 26 or...

Страница 30: ...oved from line Have gas line checked by local natural or propane LP gas company 3 Observe minimum installation clearances see page 8 4 Clean burners see Cleaning and Maintenance page 26 1 Turn heater...

Страница 31: ...propane LP only 3 Locate and correct all leaks see Checking Gas Connec tions page 16 1 Open window and or door for ventilation 2 Contact local natural or pro pane LP gas company 3 Clean ODS pilot see...

Страница 32: ...lace see Figure 45 for location If you have a factory built metal fireplace see Figure 46 for location If your fireplace has glass doors position sensing bulb directly behind door gap on right bottom...

Страница 33: ...sitioning of Thermostat Sensing Bulb Continued O D S PILOT THERMOPILE PILOT THERMOCOUPLE IGNITOR VALVE THERMOCOUPLE CONNECTION PILOT OUT TPTH TP TH PIEZO SWITCH AUTO OFF ON gnitor Cable Thermopile Wir...

Страница 34: ...11 2 2000 Z21 11 2 2000 Z21 11 2 2000 Z21 11 2 2000 For purpose of input adjustment 24 Remote Ready 30 Remote Ready Btu Variable 10 000 40 000 10 000 40 000 10 000 40 000 10 000 40 000 Type Gas Propan...

Страница 35: ...03 01 Log Ember Bed 1 3 110105 01 110106 01 110107 01 111528 01 Log Right Front 1 4 110105 02 110106 02 110107 02 111528 02 Log Left Front 1 5 110105 03 110106 03 110107 03 111528 03 Log Back 1 6 1101...

Страница 36: ...N 36 ILLUSTRATED PARTS BREAKDOWN Thermostat Controlled Models VRL24NT VRL24PT VRL30NT VRL30PT CSG3924NT CSG3924PT CTB3924NT CTB3924PT 1 16 17 2 18 12 28 24 27 27 27 27 27 27 8 8 7 9 13 5 6 19 20 4 14...

Страница 37: ...159 04 097159 04 Piezo Ignitor 1 15 098271 10 098271 10 098271 10 098271 10 098271 10 098271 10 Ignitor Cable 1 16 099056 18 099056 21 099056 18 099056 21 099056 18 099056 21 Burner Orifice Injector B...

Страница 38: ...N Remote Ready Models VRL24NR VRL24PR VRL30NR VRL30PR CSG3924NR CSG3924PR CTB3924NR CTB3924PR CSG3930NR CSG3930PR 1 16 2 18 11 22 Items 12 22 Natural Gas Models Only 12 20 28 24 32 32 32 32 32 32 7 27...

Страница 39: ...056 21 099056 21 099056 18 099056 21 Burner Orifice Injector Back 1 17 101004 02 101004 02 101004 18 101004 18 101004 02 101004 18 Burner Orifice Injector Front 1 18 101004 11 101004 11 101004 13 1010...

Страница 40: ...of this product If they can t supply original replacement part s call DESA Heating Products at 1 866 672 6040 for referral information When calling DESA Heating Products have ready model number of you...

Страница 41: ...y also email your request to productsupport desaint com RECEIVER AND HAND HELD THERMOSTAT REMOTE CONTROL KIT HRC200 For all Remote Ready Models Allows the gas log heater to be operated in a manually o...

Страница 42: ...__ ______________________________________________________ ______________________________________________________ ______________________________________________________ ________________________________...

Страница 43: ...__ ______________________________________________________ ______________________________________________________ ______________________________________________________ ________________________________...

Страница 44: ...2701 Industrial Drive P O Box 90004 Bowling Green KY 42102 9004 www desatech com 110021 01 Rev N 04 06 NOT A UPC 110021 01...

Отзывы: