background image

                                                                                                        - 4 -                                           

For more information, visit www.desatech.com

 

FAN/BLOWER KIT ASSEMBLY 

Fan or blower kit is optional (for circulating models only) with 
this fireplace.  Use of blowers or fans other than manufactured 
by DESA voids the warranty.  Fan is operated by pressing the 
rocker switch (see figure 5a) in the lower right hand corner of 
the fireplace face.  Blower is operated by turning the control 
knob (not shown). 
Fan/blower kit electrical connections are made through the 
electrical cover plate on the side of the fireplace as shown in 
figure 5a.   
  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

WIRING INSTRUCTIONS 

i. Remove 

electrical 

cover plate (with electrical 

bushing) from the fireplace by removing the two 
sheet metal screws as shown in figure 5a. 

ii. 

Slide power source wiring through the electrical 
bushing opening and electrical cover plate and make 
all the necessary connections. 

iii. 

Slide all wiring connections in the electrical housing 
as shown in figure 5b. 

iv. 

Secure the electrical cover plate with screws 
previously removed.  

NOTE: Electrical housing and cover plate have sharp edges, 
wear protective gloves. 
 
 
 
 
 
 
 
 
 
 
 
 
 

CHIMNEY PIPE 

The DESA chimney system consists of 12, 18, 24, 36 and 48 
inch, snap-lock double-wall pipe segments, planned for 
maximum adaptability to individual site requirements.  Actual 
lengths gained after fitting overlaps must be taken into 
consideration (lineal gain) and are given in the lineal gain 
chart (see figure 6). 
  

ASSEMBLY AND INSTALLATION OF THE DOUBLE 

WALL CHIMNEY SYSTEM 

Each double wall chimney section is consist of a galvanized 
outer pipe, a stainless steel inner flue pipe and a wire spacer.   
The pipe sections must be assembled independently as the 
chimney is installed.  When connecting chimney directly to 
the fireplace, the inner flue pipe section must be installed first 
with the lanced side up.  The outer pipe section can then be 
installed over the flue pipe section with the hemmed end up.   
Press down on each pipe section until the lances securely 
engage the hem on the fireplace starter.  The wire will assure 
the proper spacing between the inner and outer pipe sections. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

For Canada, use chimney parts designated “HT” 

 
 
 
 
Continue to assemble chimney sections as outlined above, 
making sure that both the inner and outer pipe sections are 
locked together.  When installing double wall “snap lock” 
chimney together, it is important to assure the joint between 
the chimney sections is locked.  Check by pulling chimney 
upward after locking.  The chimney will not come apart if 
properly locked.  It is not necessary to add screws to keep the 
chimney together (exception – see page 5 figure 9). 

INSTRUCTIONS WHEN ELBOW OFFSET (30E-8DM) 

OF CHIMNEY IS NEEDED 

1.  To achieve desired offset, you may install combinations of               
12”, 18”, 24”, 36” and 48” length of double wall pipe (SEE 
SINGLE OFFSET CHARTAND FIGURE 7). 
2.    Chimney  weight  above  offset  rests  on  return  elbow.              
Straps must be securely nailed to rafters or joists (see figure 8, 
details a & b). 
3.    Maximum length of pipe between supports (return elbow 
or 12S-8DM) is 6’ of angle run.  Maximum of two (2) 6’ angle 
run sections per chimney system (see figure 7). 
 

WARNING

: The opening in the collar around the

chimney at the top of the fireplace must not be obstructed.
Never use blown insulation to fill the chimney enclosure.

 

Figure 6                        LINEAL GAIN 

 

Figure 5b       ELECTRICAL HOUSING 

 

Figure 5a    FAN SWITCH-ELECTRICAL BUSHING

Содержание (V)C36LH

Страница 1: ...nted gas log approved to ANS Z21 60 Z21 84 or RGA 2 72 standards or for use with a vent free gas log heater approved to ANS Z21 11 2 standard A DESA hood must be installed when using a vent free gas l...

Страница 2: ...DE AIR KIT INSTALLATION PG 3 7 FAN BLOWER KIT ASSEMBLY PG 4 8 CHIMNEY PIPE AND OFFSET INSTALLATION PG 4 5 9 FIRESTOP SPACERS PG 5 10 FLASHING AND TERMINATION PG 6 7 11 FINISHING YOUR FIREPLACE PG 7 12...

Страница 3: ...l to Opening of unit 12 minimum Top Spacers 0 minimum Mantel Clearances see page 8 Mantels Chimney Outer Pipe Surfaces 1 minimum MINIMUM MAXIMUM CHIMNEY HEIGHT The minimum height of the chimney measur...

Страница 4: ...the fireplace HEARTH EXTENSION A hearth extension projecting a minimum of 16 in front of and a minimum of 8 beyond each side of the fireplace opening is required to protect combustible floor construct...

Страница 5: ...nd a wire spacer The pipe sections must be assembled independently as the chimney is installed When connecting chimney directly to the fireplace the inner flue pipe section must be installed first wit...

Страница 6: ...pipe passes through a framed opening into an attic space the firestop must be placed into an attic floor as shown in figure 11 PENETRATING THE ROOF OFFSET RISE A B 48 36 24 18 12 4 3 8 16 3 8 9 3 4 2...

Страница 7: ...ASHING INSTALLATION V6F 8DM or V12F 8DM Determine the flashing to be used with the roof opening chart Slide flashing over pipe until base is flat against roof Replace as many shingles as needed to cov...

Страница 8: ...prevent smoke spillage from one termination to another We suggest that terminations be separated at least 24 inches center to center and stacked at vertical height difference of 18 inches see figure 1...

Страница 9: ...owed to assure that both the fireplace and the glass door retain their beauty and function properly Both the flue damper and the glass doors must be fully opened before starting the fire This will pro...

Страница 10: ...for fitting connection see figure 22 NOTE Secure incoming gas line to wood framing to provide rigidity for threaded end STEP 4 Repack insulation around gas line and into sleeve opening Seal any gaps b...

Страница 11: ...ure 23 Pulling the handle out will free the outside air door to open Pushing the handle in will lock the door close FOR FURTHER OPERATING GUIDELINES INSTRUCTIONS AND WARRANTY INFORMATION PLEASE REFER...

Страница 12: ...502 BAG POLY 1 17a 106651 01 PANEL CLOSURE SMOOTH 1 51 16901 STRAPPING 7 16 10 5 18 106687 01 COLLAR DAMPER CAN 1 52 20023 COLLAR STARTER 1 19 106691 01 ROD SCREEN 2 53 20027 RETAINER REFRACTORY 2 20...

Страница 13: ...11a For more information visit www desatech com ILLUSTRATED PARTS...

Страница 14: ...12 For more information visit www desatech com REPLACEMENT PARTS ACCESSORY PARTS VC36H VC36LH C36H C36LH VC36 I VC36L I CWC36C C36 I C36L I...

Отзывы: