www.desatech.com
123551-01D
12
INSTALLATION
Continued
INSTALLING HEATER BASE
ASSEMBLY
CAUTION: Do not remove the
data plates attached to the heater
base assembly. The data plates
contain important warranty and
safety information.
WARNING: If installing in a
sunken fireplace, special care
is needed. You must raise the
fireplace floor to allow access
to heater control panel. This
will insure adequate air flow
and guard against sooting and
controls being damaged. Raise
fireplace floor with noncombus-
tible material. Make sure material
is secure.
CAUTION: Do not pick up
heater base assembly by the
burner. This could damage
heater. Only handle base as-
sembly by grates.
Hearth
5"
Min.
Combustible
Material
14"
Min.
Combustible
Material
Noncombustible Material
Figure 8 - Minimum Fireplace Clearances
If Installed at Floor Level
Figure 9 - Minimum Fireplace Clearances
Above Combustible Flooring
MANTEL CLEARANCES
In addition to meeting noncombustible mate-
rial clearances, you must also meet required
clearances between fireplace opening and
mantel shelf. If you do not meet the clearances
listed below, you will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between man-
tel shelf and top of fireplace opening, a hood
is not required (see Figure 6, page 11).
Determining Minimum Mantel Clearance
when Using a Hood
If minimum clearances in Figure 6, page 11,
are not met, you must have a hood. When
using a hood there are still certain minimum
mantel clearances required. Follow minimum
clearances shown in Figure 7, page 11, when
using a hood.
NOTICE: Surface temperatures
of adjacent walls and mantels
become hot during operation.
Walls and mantels above the
firebox may become hot to
the touch. If installed properly,
these temperatures meet the
requirement of the national
product standard. Follow all
minimum clearances shown in
this manual.
NOTICE: If your installation does
not meet the minimum clear-
ances shown, you must do one
of the following:
• raise the mantel to an accept-
able height
• remove the mantel
FLOOR CLEARANCES
A. If installing appliance on the floor level,
you must maintain the minimum distance
of 14" to combustibles (see Figure 8).
B. If combustible materials are less than 14"
to the fireplace, you must install appliance
at least 5" above the combustible flooring
(see Figure 9).