AIR FOR COMBUSTION AND VENTILATION

PROVIDING ADEQUATE 
VENTILATION 

The following are excerpts from 

National Fuel 

Gas  Code,  ANSI  Z223.1/NFPA  54,  Air  for 
Combustion and Ventilation.

All spaces in homes fall into one of the three 

following ventilation classifications:

1.  Unusually Tight Construction

2.  Unconfined Space
3.  Confined Space

The information on pages 6 through 8 will help 

you classify your space and provide adequate 

ventilation.

Unusually Tight Construction

The air that leaks around doors and windows 
may provide enough fresh air for combustion 

and ventilation. However, in buildings of un

-

usually tight construction, you must provide 

additional fresh air.

Unusually tight construction is defined as 
construction where:
a.  walls and ceilings exposed to the out-

side  atmosphere  have  a  continuous 
water vapor retarder with a rating of one 
perm (6 x 10

-11

 kg per pa-sec-m

2

) or less 

with openings gasketed or sealed and

b.  weather stripping has been added on 

openable windows and doors and 

c.  caulking  or  sealants  are  applied  to 

areas  such  as  joints  around  window 
and door frames, between sole plates 
and floors, between wall-ceiling joints, 
between  wall  panels,  at  penetrations 
for plumbing, electrical and gas lines 
and at other openings.

If your home meets all of the three criteria 
above, you must provide additional fresh air. 

PRODUCT FEATURES

OPERATION

This  heater  is  clean  burning.  It  requires  no 

outside venting. There is no heat loss out a 
vent or up a chimney. Heat is generated by 

both realistic flames and glowing coals. This 

heater  is  designed  for  vent-free  operation 

with flue damper closed. It has been tested 

and approved to ANSI Z21.11.2 standard for 
unvented  heaters. State and local  codes in 
some areas prohibit the use of vent-free heat-
ers. This heater may also be operated as a 
vented decorative (ANSI Z21.60) product by 

opening the flue damper (only when thermo

-

stat remote control is not installed).

SAFETY DEVICE

This heater has a pilot with an Oxygen Deple-
tion Sensing (ODS) safety shutoff system. The 

ODS/pilot is a required feature for vent-free 

room  heaters.  The  ODS/pilot  shuts  off  the 
heater if there is not enough fresh air.

ELECTRONIC IGNITION SYSTEM

This heater has an electronic ignitor to light 
heater fuel supply.

 WARNING: This heater shall 

not  be  installed  in  a  room  or 

space unless the required vol-

ume  of  indoor  combustion  air 

is provided by the method de-

scribed in the 

National Fuel Gas 

Code, ANSI Z223.1/NFPA 54,

 the 

International Fuel Gas Code,

 or 

applicable local codes. Read the 

following instructions to insure 

proper  fresh  air  for  this  and 

other  fuel-burning  appliances 

in your home.

Today’s homes are built more energy efficient 
than ever. New materials, increased insulation 

and new construction methods help reduce 
heat  loss  in  homes. Home  owners  weather 
strip  and  caulk  around  windows  and  doors 
to keep the cold air out and the warm air in. 

During  heating  months,  home  owners  want 

their homes as airtight as possible.
While it is good to make your home energy 

efficient, your home needs to breathe. Fresh 

air must enter your home. All fuel-burning ap-
pliances need fresh air for proper combustion 
and ventilation.

Exhaust  fans,  fireplaces,  clothes  dryers  and 

fuel burning appliances draw air from the house 

to operate. You must provide adequate fresh 

air for these appliances. This will insure proper 
venting of vented fuel-burning appliances.

Содержание CRB3624NR

Страница 1: ...ny electrical switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fir...

Страница 2: ...at er It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ven tilation section on page 6 o...

Страница 3: ...erates chemicals known to the state of California to cause cancer or birth defects or other reproduc tive harm IMPORTANT Read this owner s manual carefully and completely beforetryingtoassemble operat...

Страница 4: ...age 19 To prevent performance problems do not use propane LP fuel tank of less than 100 lb capacity propane LP units only 20 Provide adequate clearances around air openings 1 This appliance is only fo...

Страница 5: ...o not pick up heater base assem bly by burners This could damage heater Always handle base assembly by grate 2 Remove all protective packaging applied to logs and heater for shipment 3 Check all items...

Страница 6: ...ation with flue damper closed It has been tested and approved to ANSI Z21 11 2 standard for unvented heaters State and local codes in some areas prohibit the use of vent free heat ers This heater may...

Страница 7: ...m Btu Hr the space can support Example 2560 cu ft volume of space x 20 51 200 maximum Btu Hr the space can support 3 Add the Btu Hr of all fuel burning appliances in the space Vent free fireplace ____...

Страница 8: ...lhelp circulatetheheatthroughoutthe house In the event of a power outage you can use this heater as your primary heat source Figure 2 Ventilation Air from Inside Building Or Remove Door into Adjoining...

Страница 9: ...ALLATION AND CLEARANCES For Vent Free Operation WARNING Maintain the minimum clearances If you can provide greater clearances from floor ceiling and adjoin ing wall MINIMUM FIREPLACE CLEARANCE TO COMB...

Страница 10: ...sured at 14 depth Figure 4 Minimum Clearance for Combustible to Wall Minimum 16 from Side Wall Example Carefully follow the instructions below This will ensure safe installation into a masonry UL127 l...

Страница 11: ...does not meet the minimum clear ances shown you must do one of the following operate logs only with the flue damper open raise the mantel to an accept able height remove the mantel Figure 6 Minimum Ma...

Страница 12: ...t Flue Opening 6 to 15 39 sq inches 15 to 30 29 sq inches Damper Damper Clamp Damper Damper Clamp Damper Figure 10 Attaching Damper Clamp Manufactured Fireplace Masonry Fireplace 14 Min Combustible Ma...

Страница 13: ...HRC200 or HRC100 Receiver and Hand Held Remote Control Kit see Accessories page 31 before installing gas log heater See installation instructions included with the kit 1 Apply pipe joint sealant ligh...

Страница 14: ...th Vent Pointing Down Installation Continued Purchase the optional CSAdesign certified equipment shutoff valve from your dealer See Accessories page 31 Minimum inlet pressure for purpose of input adju...

Страница 15: ...equip ment shutoff valve from gas supply piping system Pressures in excess of 1 2 psig will damage heater regulator 2 Cap off open end of gas pipe where equip ment shutoff valve was connected 3 Press...

Страница 16: ...5 11 If logs were removed from heater for in stall remote accessory replace logs see Installing Logs page 17 Installation Continued Figure 19 Disconnecting Jumper Wire From Control Valve Jumper Wire C...

Страница 17: ...l and not leaning in toward burner where the flame will touch the log 3 Position front log as shown in Figure 23 making sure the grooves in the bottom of the log fit over the grate prongs Base Assembl...

Страница 18: ...the OFF position see Figure 24 page 19 WARNING Burners will come onautomaticallywithinoneminute when the selector switch is in the ON position after the pilot is lit FOR YOUR SAFETY READ BEFORE LIGHT...

Страница 19: ...Note If pilot goes out repeat steps 4 through 8 beginning on page 18 9 Slightly push in and turn control knob coun terclockwise to the ON position 10 Wait one minute and switch selector switch to the...

Страница 20: ...de Button Locks System to Prevent Accidental Ignition Turns Burners On or Off Increases or Decreases Room Temperature in AUTO Mode Digital Display Shows Temperature and Settings MANUAL LIGHTING PROCED...

Страница 21: ...ace off This feature is not available in the MANU mode 2 The receiver continuously receives sig nals from the hand held remote to control the room temperature If the hand held remote is misplaced obst...

Страница 22: ...ater clean Inspect these areas of heater before each use Have heater inspected yearly by a qualified service person Heater may need more frequent cleaning due to excessive lint fromcarpeting pethair b...

Страница 23: ...he unit off lightly blow air through the air inlet hole You may blow through a drinking straw if compressed air is not available LOGS If you remove logs for cleaning refer to Installing Logs page 17 t...

Страница 24: ...ion 4 Air in gas lines when in stalled 5 Depleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pin...

Страница 25: ...reset Repeat ignition operation 4 Fully open equipment shut off valve 5 A Contact local natural or propane LP gas company B Clean ODS pilot see Cleaning and Maintenance page 22 or replace ODS pilot a...

Страница 26: ...ave gas line checked by local natural or propane LP gas company 3 Observe minimum installa tion clearances see pages 9 through 12 4 Clean burners see Clean ing and Maintenance page 22 or replace burne...

Страница 27: ...d 1 Gas leak See Warning statement at top of page 2 Control valve or gas control defective 1 Foreign matter between control valve and burner 2 Gas leak See Warning statement at top of page 1 Hand held...

Страница 28: ...www desatech com 120044 01D 28 Parts Models CRB3624NR and CRB3624PR LPG 5 6 21 14 22 14 23 24 2 19 20 16 1 18 17 10 11 4 3 8 8 12 14 13 7 15 9 8...

Страница 29: ...101004 02 Rear Burner Injector Propane LP 1 12 101004 08 Front Burner Injector Natural 1 101004 06 Front Burner Injector Propane LP 1 13 112708 01 Remote Burner Tube 1 14 M12461 26 Screw 5 15 099918...

Страница 30: ...acement parts This will protect your warranty coverage for parts replaced under warranty Parts Under Warranty Contact authorized dealers of this product If they can t supply original replacement part...

Страница 31: ...GWMS2 For all models Allows the gas log heater to be turned on and off with a wall switch VENT FREE LOGMATE FIREBOXES Available in 32 36 and 42 models Circulating fireboxes feature louvers and an opt...

Страница 32: ...proved by DESA Heating LLC Warranty parts must be obtained through authorized dealers of this prod uct and or DESA Heating LLC who will provide original factory replacement parts Failure to use origin...

Отзывы: