DIRECT-VENT FIREPLACE (NATURAL/PROPANE)

®

FIREPLACE
INSTALLATION

Continued

Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)

1.

Close manual shutoff valve (see Fig-
ure 37).

2.

Pressurize supply piping system by ei-
ther opening propane supply tank valve
for propane gas fireplace or opening
main gas valve located on or near gas
meter for natural gas fireplace, or using
compressed air.

3.

Check all joints from propane supply
tank or gas meter to manual shutoff
valve (see Figure 38 for propane or Fig-
ure 39 for natural). Apply commercial
leak test solution to all gas joints.
Bubbles forming show a leak. Correct
all leaks at once.

Pressure Testing Fireplace Gas
Connections

1.

Open manual shutoff valve (see Figure
37).

2.

Open propane supply tank valve for
propane fireplace or  main gas valve lo-
cated on or near gas meter for natural
gas fireplace.

3.

Make sure control knob of fireplace is
in the OFF position.

4.

Check all joints from manual shutoff
valve to thermostat gas valve (see Fig-
ure 38 for propane or Figure 39 for natu-
ral). Apply commercial leak test solu-
tion to all gas joints. Bubbles forming
show a leak. Correct all leaks at once.

5.

Light fireplace (see Operating Fire-
place
, pages 24 and 25). Check all other
internal joints for leaks.

6.

Turn off fireplace (see To Turn Off Gas
to Appliance
, page  24).

Figure 37 - Manual Shutoff Valve

ON

POSITION

OFF

POSITION

Open

Closed

Manual
Shutoff
Valve

Figure 39 - Checking Gas Joints for Natural Gas Fireplace

Figure 38 - Checking Gas Joints for Propane/LP Gas Fireplace

Propane Supply Tank

Gas Valve

Manual
Shutoff Valve

Gas Meter

Gas Valve

Manual
Shutoff Valve

INSTALLING OPTIONAL
WALL MOUNT SWITCH
GWMS2

1.

Connect one terminal of 25 ft. wire for
the wall switch to the TPTH terminal
on the valve. Connect remaining wire
terminal to the TH terminal on the
valve. Make sure that the wire termi-
nals are in the positions on the unit as
pictured in Figure 41, page 21. If wires
are not connected as shown  the switch
will not work.

2.

Route the 25 ft. wire through openings
provided on the sides of the fireplace
to a convenient location to mount your
switch.

3.

Connect one bare wire end to each of
the terminals of the GWMS2 Wall
Switch.

4.

Install the wall switch and cover in the
wall.

Содержание BDV34N

Страница 1: ...fer to this manual for correct in stallation and operational procedures Forassistance or additional information consultaqualifiedinstaller service agency or the gas supplier This appliance may be inst...

Страница 2: ...rly seated and sealed If this unit is not properly installed by a qualified service person with glass door properly seated and sealed gas leakage can occur Carbon Monoxide Poisoning Early signsofcarbo...

Страница 3: ...OR This fireplace has a piezo ignitor This sys tem requires no matches batteries or other sources to light fireplace Figure 1 Vanguard Direct Vent Fireplace BDV Series Glass Door Assembly Blower Adjus...

Страница 4: ...3 20 34 3 4 5 8 for drywall facing Must maintain a minimum 1 clearance to combustibles 34 1 2 34 3 4 20 Vertical Termination 19 Horizontal Termination CLEARANCES Minimum clearances to combustibles for...

Страница 5: ...pe cifically approved for this fireplace Minimum clearance between vent pipes and combustible materials is 1 25 mm except where stated otherwise Combustible material may be flush with the top front of...

Страница 6: ...de walk or a paved driveway located on public property 84 inches 2133mm minimum M clearance under veranda porch deck 12 inches 305mm minimum N clearance above a roof shall extend a minimum of 24 inche...

Страница 7: ...proper length of vent pipe for the type of termination you choose It is also important to note the wall thickness For Horizontal Termination Select the amount of vertical rise desired The horizon tal...

Страница 8: ...appliance adaptor with pipe seams oriented towards the wall or floor Twist lock Procedure The female ends of the pipes and fittings have four locking lugs indentations These lugs will slide straight i...

Страница 9: ...f 1 to combustibles is maintained At tach the vent cap with four wood screws supplied see Figure 13 Note Re place the wood screws with appropri ate fasteners for stucco brick concrete or other types o...

Страница 10: ...for use with corner installation UP Horizontal Venting See information in Figures 17 and 18 for Vertical V and Horizontal H maxi mums and minimums The same amounts apply for flexible venting BVK Vent...

Страница 11: ...max 8 min 8 min 20 max 20 max 8 max 20 max Venting with Two 90 Elbows Vertical V Horizontal H1 Horizontal H2 5 min 6 max 6 min 12 max 7 min 18 max 8 min 20 max 20 max 20 max Figure 19 Horizontal Termi...

Страница 12: ...as specified in the second warning state ment on page 7 Be sure all pipe and elbow connections are fully twist locked see Figure 11 page 9 3 Cut a hole in the roof using the locating hole as a center...

Страница 13: ...Cut hole 1 8 larger than support box when projected onto roofline 2 minimum below finished ceiling Cathedral ceiling support box Level 3 Lower the support box through the hole in the roof until the b...

Страница 14: ...No Horizontal Run VENTING INSTALLATION Continued Venting with Two 90 Elbows Vertical V1 Horizontal H 5 min 6 max 6 min 12 max 7 min 18 max 8 min 20 max Note Vertical V1 Vertical V2 20 max Figure 27 V...

Страница 15: ...of Flashing RTV Silicone VerticalTermination and26screws D1000 7 x 12 Galvanized Coaxial Pipe 6 pcs D1010 7 x 24 Galvanized Coaxial Pipe 6 pcs D1020 7 x 48 Galvanized Coaxial Pipe 6 pcs D1030 7 Adjust...

Страница 16: ...un system scirculatingblowerwhile using heater This will help circu late the heat throughout the house In the event of a power outage you can use this heater as your primary heat source NOTICE A quali...

Страница 17: ...the right side see Figure 33 Route power cord through both plastic bushing s and plug the power cord into a properly grounded 3 prong wall receptacle near the firebox b If your fireplace system insta...

Страница 18: ...con nector if allowed by local codes not provided AnA G A design certifiedmanualshutoff valve with 1 8 NPT tap is an acceptable alternative to test gauge connection Pur chase the A G A design certifie...

Страница 19: ...provided by installer from manual shutoff valve to fireplace Route flexible gas supply line through one of the access holes on side of fireplace 3 Attach flexible gas line from gas sup ply to control...

Страница 20: ...gure 39 for natu ral Apply commercial leak test solu tion to all gas joints Bubbles forming show a leak Correct all leaks at once 5 Light fireplace see Operating Fire place pages 24 and 25 Check all o...

Страница 21: ...witch bracket Lean bracket forward so you are able to ac cess the back of the remote receiver 3 Locate the battery clip mounted on the back of the receiver Slide a 9 volt bat tery not included through...

Страница 22: ...ebox see Figure 46 4 Slide the left retainer bracket against the left side brick panel Loosely se cure the bracket screw This secures the left side brick panel 5 Install the right brick panel using th...

Страница 23: ...lace model numbers WARNING Failure to position thepartsinaccordancewiththese diagrams or failure to use only parts specifically approved with this heater may result in property damage or personal inju...

Страница 24: ...not require ac cessing for lighting 8 Turn knob on gas control counter clockwise to PILOT 9 Push in control knob all the way and hold Immediately light the pilot by repeatedly depressing the piezo spa...

Страница 25: ...h is in the ON position In the OFF position the blower will not operate Note for DA3610T Only Your fireplace and blower will not turn on and off at the same time The fireplace may run for sev eral min...

Страница 26: ...ol before cleaning CAUTION Youmustkeepcon trol areas burners and circulat ing air passageways of fireplace clean Inspect these areas of fire place before each use Have fire place inspected yearly by a...

Страница 27: ...loose at con trol valve 6 Thermocouple damaged 7 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut hold...

Страница 28: ...t warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local pro pane gas company 3 Clean burner see Cleaning and Maintenance page 26 or replace burner orifice...

Страница 29: ...nt above 1 Improper log placement 2 Air holes at burner inlet blocked 3 Burner flame holes blocked OBSERVED PROBLEM Fireplace produces unwanted odors Fireplace shuts off in use Gas odor even when cont...

Страница 30: ...n servicing controls Wiringerrorscancause improper and dangerous opera tion Verify proper operation af ter servicing Red Variable Fan Switch Fan Switch N O Black Black Green White On 110 115 V A C Blo...

Страница 31: ...anifold Pressure 3 5 w c 10 0 w c Minimum Inlet Supply Pressure 4 5 w c 11 0 w c Dimension Inches mm HxWxD Fireplace 33 x 34 x 18 1 2 33 x 34 x 18 1 2 838 x 940 x 470mm 838 x 940 x 470mm Carton 37 x 4...

Страница 32: ...rim accessories Dimensions WxHxD 56 3 4 x48 3 4 x22 7 8 HARDWOOD HEARTH BASE G3000F Series Walnut Finished G3001U Series Unfinished G3006F Series Oak Finished with Medium Stain G3007U Series Unfinishe...

Страница 33: ...lack louvers by screwing into place DECORATIVE 2 PIECE BRASS ACCENT TRIM D7034 Not Shown Thesestripshaveamagneticbackingwhich makes installation and removal quick and easy They are designed to go at t...

Страница 34: ...L PROPANE ILLUSTRATED PARTS BREAKDOWN BDV34N A 1 2 3 4 6 7 7 8 9 10 11 Included in Hardware Pack 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 29 30 31 3 31 2 31 4 31 1 32 33 32 34 46 5 5 5 35...

Страница 35: ...Natural 1 18 104497 01 SIT Pilot Natural 1 19 104498 01 Thermocouple 1 20 104499 01 Thermopile 1 21 104500 01 Ignitor 1 22 104501 01 Ignitor Bracket 1 23 104502 01 Ignitor Screw 1 24 104503 01 Ignito...

Страница 36: ...L PROPANE ILLUSTRATED PARTS BREAKDOWN BDV34P A 1 2 3 4 6 7 7 8 9 10 11 Included in Hardware Pack 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 28 29 30 31 3 31 2 31 4 31 1 32 33 32 34 46 5 5 5 35...

Страница 37: ...Natural 1 18 104497 02 SIT Pilot Natural 1 19 104498 01 Thermocouple 1 20 104499 01 Thermopile 1 21 104500 01 Ignitor 1 22 104501 01 Ignitor Bracket 1 23 104502 01 Ignitor Screw 1 24 104503 01 Ignito...

Страница 38: ...ing a defective heater will be the responsibility of the owner TOTHEFULLEXTENTALLOWEDBYTHELAWOFTHEJURISDICTIONTHATGOVERNSTHESALEOFTHEPRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED...

Отзывы: