![Denyo DCA-60ESI2 Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/denyo/dca-60esi2/dca-60esi2_instruction-manual_2485068023.webp)
(5) Fuel priming pump button
The 60ESI2 is provided with an fuel priming pump
button. The button is used to vent the air contained in
fuel piping before the engine that has been stopped
because of fuel shortage, etc. is started.
In such a case, set the starter switch to "Run", press
down the fuel priming pump button for about 1 minute,
and then start the engine.
If the engine rotation is found unstable after it is started,
press down the button again for about 10 seconds while
the engine is running.
If the engine still rotates unstably or still fails for starting, clean up the Fuel Filter
Element located into
the
Fuel Pump, or replace it to new one.
Parts number of fuel filter element located into the fuel pump:
Model name
Parts number
manufacture
Parts number of manufacture
DCA-60ESI2
Y06020 42425
ISUZU
894437-0220
Voltage regulator and overcurrent relay
(1) Voltage regulator
This regulator is used to control the output voltage.
Turn the regulator to clockwise to increase the voltage
and counter clockwise to decrease it.
Adjust the voltage to the rated voltage with this
regulator.
(2) Overcurrent relay
This relay is used to trip the circuit breaker (for 3 phase)
when overcurrent flows into the circuit.
[Note]
Do not change the set value unnecessarily.
-
2 2
-