![Denyo DCA-30ESX Скачать руководство пользователя страница 47](http://html1.mh-extra.com/html/denyo/dca-30esx/dca-30esx_instruction-manual_2485065047.webp)
5-5
Protection device
Protection devices and emergency stop devices are provided for protection o f the
machine against trouble during operation. When the running caution lamp lights, stop
the engine immediately. Check and remove the cause o f trouble.
Table of protec ion device
action
w arning
turn OFF the
circuit breaker
stop
the engine
indicate by
warning lamp
function
oil pressure
failure
(OIL PRESS)
—
-
set point ; 130кРа
—
stop
О
set point : 98,lkPa
high jacket
w ater
temperature
(WATER TEMP)
—
-
set point :
91°C
—
stop
О
set point : l O S t
Battery charging
failure
-
“
ж©
set point : 12,5V
overcuirent o f
generator
О
-
—
When overcurrent
flows, the device acts
fuel level
failure
(FUEL LEVEL)
—
—
о
When fuel supply is necessary
because of fuel shortage, the
device acts.
high fuel filter
w a te r level
(FU EL FILTER
W ATER LEVEL)
—
—
О
When the water level in the
fuel filter would rise only for
30ESX
air filter blinding
(A IR FILTER)
—
—
о
When replace or cleaning of
air filter is necessary because
o f blinding of filter, the device
acts
earth leakage
О
—
о
When electric leakage,
the device acts
Current sensitivity : 30mA
over speed o f
engine
(OVER SPEED)
—
Stop
о
set point : 2070 m in 1
Abnormal value and unit will be indicated lighting on and off.
- 46 -