74
DENT
Instruments
PowerScout 24
All Things Modbus
Modbus
Offset
Register
Detailed Description
* System=sum of three phases
47029
7028
Negative kW L1
Individual Phase Instantaneous Negative True Powers
(kW)
47030
7029
Negative kW L2
“
47031
7030
Negative kW L3
“
47032
7031
Negative kVARh L1 LSW
Individual Phase Negative Reactive Energy LSW
(kVARh, resettable)
47033
7032
Negative kVARh L1 MSW
Individual Phase Negative Reactive Energy MSW
(kVARh, resettable)
47034
7033
Negative kVARh L2 LSW
“
47035
7034
Negative kVARh L2 MSW
“
47036
7035
Negative kVARh L3 LSW
“
47037
7036
Negative kVARh L3 MSW
“
47038
7037
Negative kVAR L1
Individual Phase Negative Instantaneous Reactive
Powers (kVAR)
47039
7038
Negative kVAR L2
“
47040
7039
Negative kVAR L3
“
47041
7040
kVAh L1 LSW
Individual Phase Apparent Energy LSW (kVAh,
resettable)
47042
7041
kVAh L1 MSW
Individual Phase Apparent Energy MSW (kVAh,
resettable)
47043
7042
kVAh L2 LSW
“
47044
7043
kVAh L2 MSW
“
47045
7044
kVAh L3 LSW
“
47046
7045
kVAh L3 MSW
“
47047
7046
kVA L1
Individual Phase Instantaneous Apparent Powers
(kVA)
47048
7047
kVA L2
“