40
DENT
Instruments
PowerScout 24
Field Installation
M
ODBUS
O
UTPUT
P
ORT
R
EGISTERS
Modbus
Register
Offset
Register Name
Detailed Description
45302
4401/5301
Port 1 output control
when used as an on/off—
open/closed switch
0 = output LOW (closed)
1 = output HIGH (open) [default]
45310
5109/5309
Digital Port 1
Configuration
Turns pulses on/off
0 = No pulses, Port may be used as an
on/off—
open/closed switch
44001 = System kWh pulses
44008 = System kVARh pulses
44011 = System kVAh pulses
45311
5110/5310
Port 1 pulse output relay
type
0 = normally open (HIGH)
1 = normally closed (LOW)
Table 13: Modbus Digital Port Pulse Output
BAC
NET
O
UTPUT
P
ORT
O
BJECTS
Refer to the following two tables to configure the PowerScout output port when using the BACnet
protocol.
Object
Identifier
Object Name
Detailed Description
NA
Port 1 output control when used as an
on/off—open/closed switch
0 = output LOW (closed) 1 = output HIGH
(open) [default]
Object 13100 present value must = 0 to use
15000
Digital Port 1 Configuration
Turns pulses on/off
0 = No pulses, Port may be used as an
on/off—
open/closed switch
44001 = System kWh pulses
44008 = System kVARh pulses
44011 = System kVAh pulses
15010
Port 1 pulse output relay type
0 = normally open (HIGH)
1 = normally closed (LOW)
Table 14: BACnet Digital Port Pulse Output