5.1.3 Foundation requirements for indoor installation
•
The foundation/bottom base may protrude a maximum of 20
mm beyond the outer edge of the unit to enable mounting of
cover plates or accessories, such as condensate traps.
•
The supporting points of the foundation must be located at
every shipping split. Besides, ensure that the maximum dis-
tance between these points does not exceed 1600 mm in the
unit length(see fig. 5-4).
•
Units with
side-by-side arrangement
must be supported in
the center (see fig. 5-5).
Fig. 5-4:
Foundation requirements with side-by-side units
operator side
Fig. 5-5:
Foundation requirements with side-by-side
cross-section
L
≤
1600
L
≤
1600