Important

The  refrigerant  available  on  the  C  series  of  Compressed  Air  Dryers  is 

Refrigerant  R134a  or  Refrigerant

R407C

. It is imperative that refrigerants are not mixed. A label is fixed to each compressor, which identifies the

refrigerant being used within the unit,  and  that  refrigerant  ONLY  should  be  used  in  the  dryer.  R134a  &  R407C
are ozone benign refrigerants and meet the requirements of the revised “Montreal Protocol”. These refrigerants
require the use of ESTER oil within the system and not MINERAL oil as used with R22 systems, and therefore
again these oils must NOT be mixed.

Introduction

The  Denco  C  series  of  Compressed  Air  Dryers  are  used  to  remove  entrained  moisture  from  compressed  air
supply  systems  and  thus  protect  the  various  components  and  are  designed  such  that  routine  maintenance  is
kept to a minimum.

Most  parts  are  field  replaceable  but  should  major  maintenance  or  repair  be  required  please  refer  to  Denco
Limited or an authorised distributor.

NOTE: This manual applies ONLY to 

the 

C series

 

of Compressed Air Dryers

. For actual model refer to serial

plate fitted to the unit. For other ranges refer to the respective manuals.

Warning

These  Dryers  are  only  designed  for  use  with  compressed  air  at  or  below  the  design  maximum  pressure  (see
Technical Data sheet(s) for maximum working pressures applicable). These Dryers must NOT be used for drying
any  other  gases  or  fluids  at  other  pressures.    Operation  of  these  Dryers  using  compressed  air  of  a  greater
temperature than that specified will cause excessively high pressures in the refrigeration system, which may be
dangerous.

The air supplied to the dryer must be free of any corrosive or combustible gases or impurities.

Warranty

The warranty will only be considered valid if the equipment supplied is installed, commissioned and maintained
in  accordance  with  the  instructions  issued  by  Denco  Limited.    Furthermore  the  Company  will  not  accept  any
liability  whatsoever  should  the  Dryer  be  installed  incorrectly  or  operated  outside  its  stated  design  duties  and
operating conditions or improper use be made of the equipment.

Содержание C120-3

Страница 1: ......

Страница 2: ...10 Description of Operation 10 Schematic Flow Diagram 11 General Arrangement Drawings 12 Technical Description of Components 17 Technical Data Tables 18 Electrical Description 20 Wiring Diagrams 22 Co...

Страница 3: ...authorised distributor NOTE This manual applies ONLY to the C series of Compressed Air Dryers For actual model refer to serial plate fitted to the unit For other ranges refer to the respective manual...

Страница 4: ...reaction to sensitive skin Refrigerants contain hydrofluorocarbons HFC s Glycol water mix is used during manufacture but drained before delivery The quantities in use are minimal but care should be t...

Страница 5: ...BEFORE and DURING this operation Proper fire precautions shall be observed and the necessary fire safety equipment on hand typical for electrical oil and foam fires The refrigerant used is refrigeran...

Страница 6: ...itions Containers may burst if overheated Precautions in Handling and Use General Precautions Atmospheric levels should be minimised and kept as low as reasonably practicable below hygiene standard Av...

Страница 7: ...contaminated clothing carefully wash affected areas of skin thoroughly with copious amounts of warm water If symptoms occur obtain medical attention Eyes Irrigate with eyewash solution or clean water...

Страница 8: ...ertures in the dryer as lifting points Position of Unit The dryer should be placed on a firm level load bearing surface of adequate strength and a suitable area be left clear of obstruction at the inl...

Страница 9: ...ine and piped to a suitable oil water separator prior to drain Installation Recommendations The compressed air pipework should incorporate sufficient shut off valves to enable the dryer to be by passe...

Страница 10: ...g controls charging the system evacuating the system or opening the system in any way must be carried out by a FULLY QUALIFIED REFRIGERATION ENGINEER A City and Guilds 2078 or equivalent certificate i...

Страница 11: ...PS1061 C 021...

Страница 12: ...PS1061 C 001...

Страница 13: ...PS1061 C 002...

Страница 14: ...PS1061 C 003...

Страница 15: ...PS1061 C 004...

Страница 16: ...PS1061 C 005...

Страница 17: ...is achieved by a multi bladed propeller type fan directly driven by a single phase motor 4 Hot Gas By pass Valve This valve is installed such that discharge gas may be diverted to the suction line wh...

Страница 18: ...in Connections mm od 8 8 8 8 8 8 Electrical Supply 220 240 volt 1 phase 50 60 Hz Installed Power kW 0 45 0 57 0 66 0 96 0 96 0 85 Full Load Current Amps 2 2 6 3 4 35 4 35 3 9 Refrigerant R134a R407C R...

Страница 19: ...Connections mm od 8 8 8 8 8 Electrical Supply 220 240 volt 1 phase 50 60 Hz Installed Power kW 1 49 1 73 2 01 2 32 2 76 Full Load Current Amps 6 76 7 86 9 16 10 56 12 56 Refrigerant R407C Refrigerant...

Страница 20: ...ompressed air dryers 1 Valve Close Time the time the valve is closed between discharges Variable between 1 20 mins Hold the UP button for 15 seconds The display will start blinking displaying the valv...

Страница 21: ...of the electrical circuitry the following wiring diagrams are included Model Numbers Schematic Wiring Diagram Number C9 1 C14 1 C19 1 PS1061 C 011 C31 2 C39 2 C58 2 PS1061 C 012 C92 3 C120 3 C147 3 P...

Страница 22: ...PS1061 C 011...

Страница 23: ...PS1061 C 012...

Страница 24: ...PS1061 C 013...

Страница 25: ...PS1061 C 014...

Страница 26: ...ing system 5 Dispose refrigerant gas to waste 5 Send used refrigerant gas back for reprocessing Note Disposal of refrigerants must be closely controlled To dispose of refrigerant or a refrigerant syst...

Страница 27: ...tightness of electrical connections Check all wiring for damage to insulation Check running current Clean condensate line strainer Bi annually Check operation of refrigerant circuit including temperat...

Страница 28: ...indicates a value 4C permanently Return the air inlet temperature to within the limits Compressed air flow rate too high The digital display panel indicates a value 4C permanently Correct the air flow...

Страница 29: ...passage as the electronic controller has failed The compressor stops The compressor does not stop even if the digital display panel indicates 0 several minutes Change the electronic board Solenoid va...

Страница 30: ...and fan has invert spin In case 3 phases used The cooling air had pass on fan and refine unit Invert the electric phase E High pressure switch stop working and have to control by manual The refrigeran...

Страница 31: ...Notes...

Страница 32: ...co compressed air equipment can be found in all types and sizes of industry throughout the World from small operator spray booths to major industrial installations With an open flexible approach and a...