I-1024
Rev. G-43816
Page 10 of 16
3/23/18
RINSE LENGTH
(The length of the rinse cycle for one rack. In a conveyor machine this is used
12
5 – 75s
for the Rack Counter. Every time the rinse runs for this time a rack is counted.
In a door machine using only a detergent trigger, this is the length of the rinse
cycle following the loss of the trigger. The default is 12 seconds.)
SANITIZER SPEED
(The sanitizer speed may be set from 0 to100. The sanitizer pump is active
5
0 – 100%
during adjustment. Setting the speed to 0 will cause other sanitizer settings to be
skipped and the prime function will not be available.)
SANITIZER MODE
SANITIZER MODE
RUN WITH RINSE
RUN WITH DET.
ENTER NEW CODE
ENTER PROG CODE
LEFT ACCEPTS 0000 NEW CODE SAVED
0000 OTHER
TO
REJECT
COMMENTS AND CLARIFICATIONS
SYSTEM ACCESS
This option will only be displayed if the dispenser has already been programmed. Press ENTER. You will be
prompted for an access code. If no key is pressed for 30 minutes, SYSTEM ACCESS mode will be exited, the
company logo will be displayed and all entries will be saved.
Code Reset
This is not a menu option and cannot be done from the keypad. If, for any reason, the codes are forgotten, the access
codes can be cleared. Turn the power to the dispenser off. Open the front cover of the dispenser. Take the four
screws out to lift the board out. There are two solder points on the back of the board. Connect them together with an
insulated wire and turn on the power. Next, turn the power back off. Remove the connection from the two solder
points. When the power is turned back on, the prompts will ask for a NEW PROGRAM. All of the program
previously input will be retained. When the Programming code is requested, it will default to 0000 and may be
reentered.
NOTE: All previous programs will NOT be erased.
Press
at any of the submenu options to get to the System Access Menu.
External Alarm, (Aux. Alarm)
There are two .250” (6.4mm) spade terminals on the left side of the control board. There is a 24VDC 500mA output for
an external alarm (buzzer, relay, etc.). (+) is the top terminal, (-) is the bottom terminal.
These terminals are on anytime an alarm situation is activated.
When sitting idle, the control will display the company logo with the backlight off. When triggers are received, they
will be displayed with the backlight on for five seconds and then replaced with the company logo. The trigger
message(s) will be replaced with any alarm messages if alarms occur. The alarm messages will remain, with the
backlight on, until the alarms are cleared. An audible alarm will sound if there is an alarm condition and a trigger is
present. Pressing any key will mute the alarm until the next trigger. The alarm will automatically mute when
triggers are lost.