each separate sleeping area.

If more than one sleeping area or the bedroom doors are closed during the 

• 

night, you may need more than one CO alarm

For added protection, install at least one CO alarm in each level of the 

• 

home and at the top of the basement stairs.

Install an additional CO alarm at least 6 meter (20 feet) away from the 

• 

furnace or fuel burning heat source or appliance.

CO alarm is available for boats and recreational vehicles. 

• 

IMPORTANT: CO alarm should be placed where you will hear it while sleeping.

      

In normal environment, wall mounted at least 1.5 meter (6 feet) from the 

• 

floor is recommended.

If on wall position, at least 150mm (6 inch) below the ceiling.

• 

If ceiling position, at least 300mm (12 inch) from any wall.

• 

Higher than any door or window frame. 

• 

WARNING! The unit does not work without power. CO alarm is an early 

warning device, no more, no less. DO NOT PAINT the alarm.

WHERE NOT TO INSTALL CO ALARM

Within 1.5m (5 feet) of any gas appliance as furnace.

• 

In any high level of dusty, dirty or greasy area

• 

In damp or very humid areas, outdoor room or next to bathroom, at least 

• 

installed the alarm 3 meters (10 feet) away from the bathroom.

In very cold or very hot area where the temperature could not be less than 

• 

-10ºC or greater than 40ºC.

Humidity is less than 30% RH or more than 90% RH.

• 

In direct sunlight and direct above a sink or cooker.

• 

Behind drapes, curtains, furniture or other obstruction.

• 

In unheated basements or garages. 

• 

In location where they are exposed to chemical solvents or cleaners.

• 

Near vents, flues and chimneys.

• 

Near heating and cooking appliances. 

• 

In turbulent air, like near ceiling fans, heat vent, air conditioners, fresh air 

• 

return, or near the open window, because of the blowing air may delay 

CO from reaching the alarm.

15 cm

Te

s t  & H us

h

Alarm Fault Power

CARBON

MONOXIDE

ALARM

min 1,5 m

Содержание CN-1231

Страница 1: ...its Do not expose to rain or moisture The detector will not protect against risk of carbon monoxide poisoning when the battery is flat Do cover the alarm when decorating REMEMBER to uncover the unit when decoration is finished excessive fumes from paints solvents cleaning agents etc may damage or deteriorate sensor The CO alarm shall not be seen as a substitute for proper servicing of fuel burning...

Страница 2: ... as headaches tightness of chest dizziness fatigue confusion and breathing dif ficulties Because CO poisoning often causes a victim s blood pressure to rise the victim s skin may take on a pink or red cast Extreme exposure to CO can cause brain damage death WARNING EXPOSURE TO HIGH LEVELS OF CARBON MONOXIDE CAN BE FATAL OR CAUSE PERMANENT DAMAGE AND DISABILI TIES COMMON RISKS FOR CO POISONING Tech...

Страница 3: ...ting bracket 1 by pushing it upwards and then fasten it onto the ceiling wall with the enclosed screws Connect the battery with ve 2 and ve in the correct position and close the battery cover Connect snap contact to relay 3 base and all connecting wires through the cable entry Fix CO alarm to the relay base 4 with the screws provided Hook the relay base on bracket 5 until it locks in place Now tes...

Страница 4: ...ower CO alarm is an early warning device no more no less DO NOT PAINT the alarm WHERENOTTOINSTALLCOALARM Within 1 5m 5 feet of any gas appliance as furnace In any high level of dusty dirty or greasy area In damp or very humid areas outdoor room or next to bathroom at least installed the alarm 3 meters 10 feet away from the bathroom In very cold or very hot area where the temperature could not be l...

Страница 5: ...attempt to repair it yourself warranty will be void Note The test push button is independent function with hush button During the normal testing mode the silence feature will not active ADDITIONAL FEATURES The CO alarm comes with the following friendly additional features for use Silence feature This feature can be used to silence nuisance alarms Press test silence button during alarm condition wi...

Страница 6: ... function by pressing the test push button until an alarm sounds Self diagnostics Automatically check the sensor every 8s to ensure of correct operating of alarm Low battery warning When the battery power deteriorated the unit will emit one beep with Yellow LED flash every minute to remind user to replace battery Fault warning If a fault is detected the unit will emit 2 beeps with Yellow LED flash...

Страница 7: ... 50 ppm 60 min 90 min 100 ppm 10 min 40 min 300 ppm 3 min The battery lasts for over one year About a month before the battery is com pletely flat the alarm emits a short signal with Red LED flashes every minute This is the signal that the battery needs replacement The alarm works as nor mal during this time Always test the alarm after changing the battery Replace battery with GP1604A Duracell MN1...

Страница 8: ...detected Flash once every 8 seconds until alarm Memory function indicates the alarm has been activated before not from test button due to whatever reason 8s 8s 1 beep every 8 seconds last for 12 hours Press button once to reset to normal mode Low Battery Warning 1 beep flash every minute 1 min 1min Sensor Fault 2 beeps flash every 8 seconds 8s 8s 8s End of sensor lifetime warning 3 Beeps flash eve...

Страница 9: ... applies if the alarms is used in the normal way and is serviced regularly The obligations of this warranty at our discretion shall be limited to the repair or replacement of any part of the alarm and is also conditional on the CO Alarm s not having been tampered with modified or subject to attempted repairs Your statutory rights as a customer are in no way compro mised by this Warranty Limitation...