If the meter reads full scale at a voltage less than 10 volts, then Pr.03-16 should be set
by the following formula:
Pr.03-16 = ((meter full scale voltage)/10)
×
100%
For Example: When using the meter with full scale of 5 volts, adjust Pr.03-16 to 50%.
03-17
Analog Output Bias Voltage
a
Factory setting 0.00
Settings
-10.00~10.00V
This parameter determines the output voltage value corresponding to 0Hz.
03-18
Analog Output Value in REV Direction
a
Factory setting
0
Settings
0 absolute value in REV direction
1 output 0V in REV direction
2
output negative voltage in REV direction
10V
-10V
03-18=0
10V
-10V
03-18=1
10V
-10V
03-18=20
03-19
Reserved