VFD-V Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-24
Group 7: Special Parameter
Control Mode
Parameters Functions
Settings
Factory
Setting VF VG SV SG T TG
a
07-00 Software Braking Level
350.0~450.0VDC
700.0~900.0VDC
380.0
760.0
{
{
{ { { {
a
07-01 DC Braking Current Level
0~100%
0
{
{
{ { { {
a
07-02 DC Braking Time at Start-up 0.00~60.00
Sec
0.00
{
{
{ { { {
a
07-03
DC Braking Time during a
STOP
0.00~60.00 Sec
0.00
{
{
{ { { {
a
07-04
Frequency point for DC
Braking
0.00~400.00Hz 0.00
{
{
{ { { {
a
07-05
Increasing Rate of the DC
Voltage
1~500 30
{
{
{ { { {
a
07-06
Re-activate after Momentary
Power Loss
0: disable
1: begins from
command
frequency
2: begins from
minimum output
frequency
0
{
{
{ { { {
a
07-07
Maximum Allowable Power
Loss Time
0.1~5.0 Sec
2.0
{
{
{ { { {
a
07-08
Base Block Time for Speed
Search
0.1~5.0 Sec
0.5
{
{
{ { { {
a
07-09
Maximum Current Level for
Speed Search
20~200% 150
{
{
{ { { {
a
07-10
Deceleration Time for Speed
Search
0.50~600.00 Sec
3.00
{
{
{ { { {
a
07-11 Auto Restart after Fault
0~10
0
{
{
{ { { {
a
07-12 Speed
Search
Type
0: speed search
disabled
1: speed search
through the
frequency
command
2: FWD-speed search
only (motor only
runs in FWD
direction)
0
{
{
{ { { {
Содержание VFD-V Series
Страница 1: ......
Страница 2: ...V E 0 5 5011608405 2016 04...
Страница 3: ......
Страница 7: ......
Страница 27: ......
Страница 31: ......
Страница 115: ......
Страница 121: ......
Страница 153: ......
Страница 159: ...VFD V Series DELTA ELECTRONICS INC ALL RIGHTS RESERVED B 4 Braking Resistors Braking Units...
Страница 160: ...B VFD V Series DELTA ELECTRONICS INC ALL RIGHTS RESERVED B 5 Braking Resistors Braking Units...
Страница 167: ...VFD V Series DELTA ELECTRONICS INC ALL RIGHTS RESERVED B 12 EMI Filters 200TDDS84C Use on 100 HP 430V Three phase Models...
Страница 173: ......
Страница 183: ......