Chapter 5 Parameters
|
VFD-BW Series
Revision May 2009, BWE0, SW V1.05
5-33
01 - 04
Mid-Point Voltage (Vmid)
Unit: 0.1
Settings 230V series
0.1 to 255.0V
Factory Setting: 1.7V
460V series
0.1 to 510.0V
Factory Setting: 3.4V
This parameter sets the Mid-Point Voltage of any V/f curve. With this setting, the V/f ratio
between Minimum Frequency and Mid-Point Frequency can be determined. This parameter
must be equal to or greater than Minimum Output Voltage (Pr.01-06) and equal to or less than
Maximum Output Voltage (Pr.01-02).
This parameter is ineffective when Pr.11-00 is set to 1 to 4.
The settings of 01-03, 01-04, and 01-06 are invalid in vector control mode.
01 - 05
Minimum Output Frequency (Fmin)
Unit: 0.01
Settings 0.10 to 400.00Hz
Factory Setting: 0.50
This parameter sets the Minimum Output Frequency of the AC motor drive. This parameter
must be equal to or less than Mid-Point Frequency (Pr.01-03).
01 - 06
Minimum Output Voltage (Vmin)
Unit: 0.1
Settings 230V series
0.1 to 255.0V
Factory Setting: 1.7V
460V series
0.1 to 510.0V
Factory Setting: 3.4V
This parameter sets the Minimum Output Voltage of the AC motor drive. This parameter must
be equal to or less than Mid-Point Voltage (Pr.01-04).
The settings of Pr.01-01 to Pr.01-06 have to meet the condition of Pr.01-02
≥
Pr.01-04
≥
Pr.01-
06 and Pr.01-01
≥
Pr.01-03
≥
Pr.01-05.
In vector control mode, the settings of 01-03, 01-04, and 01-06 are invalid, whereas, Pr.01-05
is still the Minimum Output Frequency of the AC motor drive.
01 - 07
Output Frequency Upper Limit
Unit: 1
Settings
01 to 120%
Factory Setting: 100
This parameter must be equal to or greater than the Output Frequency Lower Limit (Pr.01-08).
The Maximum Output Frequency (Pr.01-00) is regarded as 100%.
Output Frequency Upper Limit value = (Pr.01-00 * Pr.01-07)/100.
Содержание VFD-BW Series
Страница 1: ...PLC1 ir ...
Страница 2: ......
Страница 3: ......
Страница 23: ...Chapter 1 Introduction VFD BW Series 1 14 Revision May 2009 BWE0 SW V1 05 This page intentionally left blank ...
Страница 61: ...Chapter 3 Start Up VFD BW Series 3 4 Revision May 2009 BWE0 SW V1 05 This page intentionally left blank ...
Страница 183: ...Chapter 5 Parameters VFD BW Series 5 118 Revision May 2009 BWE0 SW V1 05 This page intentionally left blank ...
Страница 189: ...Chapter 6 Fault Code Information VFD BW Series 6 6 Revision May 2009 BWE0 SW V1 05 This page intentionally left blank ...
Страница 214: ...Appendix B Accessories VFD BW Series Revision May 2009 BWE0 SW V1 05 B 7 Order P N VFDB4132 VFDB4132 CHARGE ACT OC OH ...
Страница 221: ...Appendix B Accessories VFD BW Series B 14 Revision May 2009 BWE0 SW V1 05 Order P N 50TDS4W4C Order P N 100TDS84C ...
Страница 222: ...Appendix B Accessories VFD BW Series Revision May 2009 BWE0 SW V1 05 B 15 Order P N 150TDS84C ...
Страница 243: ...Appendix B Accessories VFD BW Series B 40 Revision May 2009 BWE0 SW V1 05 This page intentionally left blank ...