Chapter 5 Parameters
|
VFD-BW Series
5-46
Revision May 2009, BWE0, SW V1.05
Settings Function
Description
15
Preliminary Count Value
Attained
Active when the counter reaches Preliminary Count Value.
16
Auxiliary Motor 1
17
Auxiliary Motor 2
18
Auxiliary Motor 3
For the fan & pump control applications, one can use the
Multi-function Output Terminals (1-3) to define the auxiliary
motor. When using with group 10 PID Controls and group 11
Fan and Pump Control, it can control flow of many motors.
19
Heat Sink Overheat
Warning (OH1)
When the heatsink overheats, it will signal to prevent OH
from turning off the drive. When it is higher than 85
o
C
(185
o
F), it will be ON. If not, it will be OFF.
20
AC Motor Drive Ready
Active when the drive is on and no abnormality detected.
21
Emergency Stop
Indication
Active once the drive’s emergency stop function is activated.
22
Desired Frequency
Attained 2
Active when the desired frequency (Pr.03-10) is attained.
23
Software Brake Signal
This function is used in conjunction with a VFDB Brake Unit.
The output will be activated when the drive needs help
braking the load. A smooth deceleration is achieved by using
this function.
24
Zero Speed Output
Signal
Active unless there is an output frequency present at
terminals U/T1, V/T2, and W/T3.
25 Low-current
Detection
Active once the drive’s current has fallen below its minimum
allowable value. (Refer to Pr.06-12, 06-13)
26
Operation Indication
(H>=Fmin)
Active when there is output voltage from U, V, W.
27
Feedback Signal Error
Active when the feedback signal is abnormal. (Refer to
Pr.10-08, Pr.10-16)
28
User-defined Low-
voltage Detection
Active once the DC Bus voltage is too low. (Refer to Pr.06-
16, Pr.06-17)
29
Mechanical Brake
Control (Desired
Frequency Attained 3)
Active when output frequency
≥
Pr.03-13. Deactivated when
output frequency
≤
Pr.03-14 after STOP command.
30
Motor’s Temperature
Warning
Active when the motor’s temperature reaches the set value.
31 Motor
Overheat
Active once the motor’s temperature has risen above its
maximum allowable value.
32
Full Reel Diameter
Attained
33
Empty Reel Diameter
Attained
Valid for tension control mode.
Содержание VFD-BW Series
Страница 1: ...PLC1 ir ...
Страница 2: ......
Страница 3: ......
Страница 23: ...Chapter 1 Introduction VFD BW Series 1 14 Revision May 2009 BWE0 SW V1 05 This page intentionally left blank ...
Страница 61: ...Chapter 3 Start Up VFD BW Series 3 4 Revision May 2009 BWE0 SW V1 05 This page intentionally left blank ...
Страница 183: ...Chapter 5 Parameters VFD BW Series 5 118 Revision May 2009 BWE0 SW V1 05 This page intentionally left blank ...
Страница 189: ...Chapter 6 Fault Code Information VFD BW Series 6 6 Revision May 2009 BWE0 SW V1 05 This page intentionally left blank ...
Страница 214: ...Appendix B Accessories VFD BW Series Revision May 2009 BWE0 SW V1 05 B 7 Order P N VFDB4132 VFDB4132 CHARGE ACT OC OH ...
Страница 221: ...Appendix B Accessories VFD BW Series B 14 Revision May 2009 BWE0 SW V1 05 Order P N 50TDS4W4C Order P N 100TDS84C ...
Страница 222: ...Appendix B Accessories VFD BW Series Revision May 2009 BWE0 SW V1 05 B 15 Order P N 150TDS84C ...
Страница 243: ...Appendix B Accessories VFD BW Series B 40 Revision May 2009 BWE0 SW V1 05 This page intentionally left blank ...