English-

 

4

Basic Wiring Diagram 

 

Users must connect wiring according to the following circuit diagram shown below. 

AVI

ACI

AUI

ACM

4~20mA

-10~+10V

+10V

5K

3

2

1

Power supply
+10V 20m A

Master Fr equency
0 to  10V 47k 

Analog S ignal Common

Main c irc ui t (power) terminals

Contr ol c ircuit ter minals

FWD
REV

JOG

EF
MI1
MI2
MI3
MI4

MI6
TRG

MI5

DCM

+24V

Sw1

Sink

Source

F act ory Settin g: 
SINK Mo de

F WD/ST OP

REV/STO P

JO G

E.F.

Multi-s tep 1

Multi-s tep 2

Multi-s tep 3

Multi-s tep 4

RESET

Acc el/Decel prohibit

Counter

Digital Si gnal Common

F ac tor y
setting

*  Don't apply voltage to 
  above ter minals 

.

directly

Please refer to F ig u re 4
fo r w irin g of S INK

m od e an d  SOURCE
m od e.

R(L1)

S(L2)
T(L3)

F us e/NF B(

None F use Br eaker)

SA

OF F

ON

MC

MC

RB

RC

+2/B1

B2

Jumper

Br ak e r es istor
(optional)

DC reac tor
(optional)

+1

Recommended Circ ui t 
 when power  suppl y 

is turned O FF by a 
fault output

R(L1)

S(L2)

T(L3)

E

Analog Multi- func tion Output
Ter minal

F ac tor y setting: Analog freq.
/ c ur rent meter 

0~1 0VDC/2 mA

U(T1)
V(T2)

W(T3)

IM

3~

MO1

MO2

MO3

AFM

ACM

RA

RB

RC

MCM

RS-485

Motor

F ac tor y setting:
indicates during operation

48V50mA

F ac tor y  setting:
F req. Setting Indication

F ac tor y setting:
Low-voltage Indication

Multi-function 
Photocoulper Output

Analog S ignal common

Seri al interface

1: EV 2: G ND 

5:Reserv ed 

6: 

3: SG- 

4: SG + 

Reserv ed

DFM

DCM

Digital F requency Output
Ter minal

F ac tor y default: 1:1 
Duty =50%
Digital Si gnal Common

48V50mA

48V50mA

E

Please refer  to control
Ter minal Ex planation.

T he wiring  for the models
may be differ ent.  Refer to

the following figures for detail.

* T hree phase input power may apply to single 
  phase drives .

*  For the single phas e driv es, the AC input 
  li ne can be connected to any two of the three 

  input termi nal s R, S , T.

Br ak e r es itor /uni t (optional)
Refer to us er manual for the use of

special brake resi stor/uni t.

E

E

E

Shield ed leads  & c able

 

Содержание VFD-007B

Страница 1: ...used only to control variable speed of 3 phase induction motors NOT for 1 phase motors or other purpose 7 VFD B series shall NOT be used for life support equipment or any life safety situation WARNING...

Страница 2: ...city kVA 2 3 3 2 4 2 6 5 9 9 13 7 18 3 24 4 28 9 34 3 45 7 55 6 69 3 84 114 Rated Output Current A 2 7 4 2 5 5 8 5 13 18 24 32 38 45 60 73 91 110 150 Maximum Output Voltage V 3 phase Proportional to I...

Страница 3: ...ut Indication AC drive operating frequency attained non zero Base Block fault indication local remote indication PLC operation indication auxiliary motor output driver is ready overheat alarm emergenc...

Страница 4: ...power supply is turned OFF by a fault output R L1 S L2 T L3 E Analog Multi function Output Terminal Factory setting Analog freq current meter 0 10VDC 2mA U T1 V T2 W T3 IM 3 MO1 MO2 MO3 AFM ACM RA RB...

Страница 5: ...43 A 53A VFD4 50B43A 53A VFD550B43A 43C 5 3A VFD750B43A 43 C 53A VFD055B23A 43A 5 3A VFD075B23A 43 A 53A VFD110B23A 43A 53A VFD185B23A 43 A 53A Figure 4 Wiring for SINK mode and SOURCE mode A SINK mo...

Страница 6: ...P STOP RESET UP and DOWN Key Sets the parameter number and changes the numerical data such as Master Frequency JOG Jog operation selector MODE Display mode selector Operation Steps of the Digital Keyp...

Страница 7: ...5 to 2 2kW VFD007B21A 23A 43A 53A VFD015B21A 21B 23A 23B 43A 53A VFD022B23B 43B 53A L1 T S U V W T3 T2 T1 2 B1 R L2 L3 1 B2 Control Terminal Torque 4Kgf cm 3 in lbf Wire 12 24 AWG 3 3 0 2 mm2 Power Te...

Страница 8: ...POWER IM MOTOR 3 Control Terminal Torque 4Kgf cm 3 in lbf Wire 12 24 AWG 3 3 0 2mm2 Power Terminal Torque 18 kgf cm 15 6 in lbf Wire Gauge 10 18 AWG 5 3 0 8mm2 Wire Type Stranded copper only 75 C Con...

Страница 9: ...ALARM W T3 S L2 R L1 T L3 2 1 U T1 V T2 173in lbf Screw Torque 200kgf cm POWER IM MOTOR 3 CHARGE Control Terminal Torque 4Kgf cm 3 in lbf Wire 12 24 AWG 3 3 0 2 mm2 Power Terminal Torque 30Kgf cm 26 i...

Страница 10: ...L1 POWER 1 V T2 U T1 2 200kgf cm 173in lbf Screw Torque IM 3 W T3 MOTOR Control Terminal Torque 4Kgf cm 3 in lbf Wire 12 24 AWG 3 3 0 2 mm2 Power Terminal Torque 58 7kgf cm 50 9 in lbf max Wire Gauge...

Страница 11: ...No fault TRG External counter input ON At every pulse counter is advanced by 1 MI1 6 Multi function Input 1 6 Refer to Pr 04 04 to Pr 04 09 for programming the Multi function Inputs DFM Digital Freque...

Страница 12: ...Pr 04 14 AUI Auxiliary analog voltage input ACM AUI 10 10V Internal Circuit AUI circuit Impedance 47k Resolution 10 bits Range 10 10VDC 0 Max Output Frequency Pr 01 00 Selection Pr 02 00 Pr 02 13 Pr...

Страница 13: ...wer factor angle n 06 Display output power P 07 Display actual motor speed HU 08 Display the estimated value of torque as it relates to current t 09 Display PG numbers 10ms G 10 Display analog feedbac...

Страница 14: ...3 Jog Acceleration Time 0 1 to 3600 0 sec 1 0 a01 14 Jog Frequency 0 10 Hz to 400 00 Hz 6 00 a01 15 Auto acceleration deceleration refer to Accel Decel time setting 00 Linear Accel Decel 01 Auto Accel...

Страница 15: ...coast to stop 02 STOP ramp to stop E F ramp to stop 03 STOP coast to stop E F ramp to stop 00 02 03 PWM Carrier Frequency Selections 230V 460V 1 5hp 0 75 3 7kW 1 15kHz 7 5 25hp 5 5 18 5kW 01 15kHz 30...

Страница 16: ...10V from AVI 02 4 to 20mA from ACI 03 10 to 10Vdc from AUI 04 RS 485 serial communication RJ 11 Last used frequency saved 00 a02 11 Source of the Auxiliary Frequency Command 00 Digital keypad PU01 UP...

Страница 17: ...3 00 No function 01 AC drive operational 02 Master frequency attained 03 Zero speed 04 Over torque detection 05 Base Block B B indication 06 Low voltage indication 07 Operation mode indication 08 Faul...

Страница 18: ...ive runs and fan ON AC motor drive stops and fan OFF 03 Fan ON to run when preliminary heatsink temperature attained 00 03 13 Brake Release Frequency 0 00 to 400 00Hz 0 00 03 14 Brake Engage Frequency...

Страница 19: ...ock enable N O 28 PID function disabled 29 Jog FWD REV command 30 External reset N C 31 Source of second frequency command enabled 32 Source of second operation command enabled 33 One shot PLC 34 Prox...

Страница 20: ...a05 03 4th Step Speed Frequency 0 00 to 400 00 Hz 0 00 a05 04 5th Step Speed Frequency 0 00 to 400 00 Hz 0 00 a05 05 6th Step Speed Frequency 0 00 to 400 00 Hz 0 00 a05 06 7th Step Speed Frequency 0 0...

Страница 21: ...00 to 6550 0 sec 00 05 26 Time Duration of 10th Step Speed 00 to 65500 sec or 00 to 6550 0 sec 00 05 27 Time Duration of 11th Step Speed 00 to 65500 sec or 00 to 6550 0 sec 00 05 28 Time Duration of...

Страница 22: ...Selection 00 Standard motor self cooled by fan 01 Special motor forced external cooling 02 Disabled 02 06 07 Electronic Thermal Characteristic 30 to 600 sec 60 06 08 Present Fault Record 06 09 Second...

Страница 23: ...User Defined Low Voltage Detection Time 0 1 3600 0 sec 0 5 06 18 Reserved Group 7 Motor Parameters a07 00 Motor Rated Current 30 to 120 100 a07 01 Motor No Load Current 01 to 90 40 a07 02 Torque Comp...

Страница 24: ...Speed Search 30 to 200 150 08 08 Skip Frequency 1 Upper Limit 0 00 to 400 00 Hz 0 00 08 09 Skip Frequency 1 Lower Limit 0 00 to 400 00 Hz 0 00 08 10 Skip Frequency 2 Upper Limit 0 00 to 400 00 Hz 0 0...

Страница 25: ...0 0 seconds 0 0 Disable 0 0 a09 04 Communication Protocol 00 7 N 2 Modbus ASCII 01 7 E 1 Modbus ASCII 02 7 O 1 Modbus ASCII 03 8 N 2 Modbus RTU 04 8 E 1 Modbus RTU 05 8 O 1 Modbus RTU 00 09 05 Reserve...

Страница 26: ...0 disable 1 00 10 14 Speed Control Output Frequency Limit 0 00 to 100 00 Hz 10 00 10 15 Sample time for refreshing the content of 210DH and 210EH 0 01 1 00 seconds 0 10 10 16 Deviation Range of PID Fe...

Страница 27: ...ther the required brake power is within the specified limits Overheating Heat sink temperature too high 1 Ensure that the ambient temperature falls within the specified temperature range 2 Make sure t...

Страница 28: ...place the AC motor drive with the next higher power model Over current during deceleration 1 Short circuit at motor output Check for possible poor insulation at the output line 2 Deceleration Time too...

Страница 29: ...Check whether the IGBT power module is damaged 2 Check for possible poor insulation at the output line External Base Block Refer to Pr 08 06 1 When the external input terminal B B is active the AC mo...

Страница 30: ...1A 23A 43A 53A 118 0 4 65 185 0 7 28 160 0 6 30 108 0 4 25 173 0 6 81 5 5 0 22 022B21A 037B23A 43A 53A 150 0 5 91 260 0 10 24 160 2 6 31 135 0 5 32 244 3 9 63 6 5 0 26 055B23A 43A 53A 075B23A 43A 53A...

Страница 31: ...53A 450B43A 53A 370 0 14 57 589 0 23 19 260 0 10 24 335 0 13 19 560 0 22 05 13 0 0 51 300B23A 370B23A 550B43C 53A 750B43C 53A 370 0 14 57 589 0 23 19 260 0 10 24 335 0 13 19 560 0 22 05 13 0 0 51 595...