English-
12
Terminal
Symbol
Terminal Function
Factory Settings (SINK)
ON: Connect to DCM
MCM
Multi-function output
common
Common for Multi-function Outputs
+10V
Potentiometer power
supply
+10VDC 20mA
AVI
Analog voltage Input
ACM
AVI
+10V
Internal Circuit
AVI circuit
Impedance: 47k
Ω
Resolution: 10
bits
Range: 0 ~10VDC = 0 ~ Max. Output Frequency (Pr.01-00)
Selection: Pr.02-00, Pr.02-13, Pr.10-00
Set-up:
Pr.04-00 ~ Pr.04-03
ACI
Analog current Input
ACM
ACI
Internal Circuit
ACI circuit
Impedance: 250
Ω
Resolution: 10
bits
Range: 4 ~ 20mA =0 ~ Max. Output Frequency (Pr.01-00)
Selection: Pr.02-00, Pr.02-13, Pr.10-00
Set-up:
Pr.04-11 ~ Pr.04-14
AUI
Auxiliary analog voltage
input
ACM
AUI
+10~-10V
Internal Circuit
AUI circuit
Impedance: 47k
Ω
Resolution: 10
bits
Range:-10 ~ +10VDC=0~Max. Output Frequency(Pr.01-00)
Selection: Pr.02-00, Pr.02-13, Pr.10-00
Set-up:
Pr.04-15 ~ Pr.04-18
AFM
Analog output meter
Internal Circuit
ACM circuit
AFM
ACM
0~10V
Max. 2mA
ondometer
0 to 10V, 2mA
Impedance: 470
Ω
Output current
2mA max
Resolution: 8
bits
Range:
0 ~ 10VDC
Function: Pr.03-05
ACM
Analog control signal
(common)
Common for AVI, ACI, AUI, AFM
**Control signal wiring size: 18 AWG (0.75 mm
2
) with shielded wire.
Summary of Parameter Settings
a
: The parameter can be set during operation.
Pr.
Explanation
Settings
Factory
Setting
NOTE
Group 0 User Parameters
00-00
Identity Code of the AC
motor drive
Read-only ##
00-01
Rated Current Display
of the AC motor drive
Read-only #.#