English-
16
Pr.
Explanation
Settings
Factory
Setting
NOTE
03: Enable. Operation status will change
if operation command source Pr.02-
01 and/or Pr.02-14 is changed.
02-07
Loss of ACI Signal (4-
20mA)
00: Decelerate to 0 Hz
01: Coast to stop and display “EF”
02: Continue operation by last frequency
command
00
a
02-08 Up/Down
Mode
00: Based on accel/decel time
01: Constant speed
02: Based on accel/decel time, but
frequency command will be 0 when
stopped.
00
a
02-09
Accel/Decel Rate of
Change of UP/DOWN
Operation with Constant
Speed
0.01~1.00 Hz/msec
0.01
a
02-10
Source of the Master
Frequency Command
00: Digital keypad (PU01) UP/DOWN
keys or Multi-function Inputs
UP/DOWN. Last used frequency
saved.
01: 0 to +10V from AVI
02: 4 to 20mA from ACI
03: -10 to +10Vdc from AUI
04: RS-485 serial communication (RJ-
11). Last used frequency saved.
00
a
02-11
Source of the Auxiliary
Frequency Command
00: Digital keypad (PU01) UP/DOWN
keys or Multi-function Inputs
UP/DOWN. Last used frequency
saved.
01: 0 to +10V from AVI
02: 4 to 20mA from ACI
03: -10 to +10Vdc from AUI
04: RS-485 serial communication (RJ-
11). Last used frequency saved.
00
a
02-12
Combination of the
Master and Auxiliary
Frequency Command
00: Master fre auxiliary
frequency
01: Master frequency - auxiliary
frequency
00
a
02-13
Source of Second
Frequency Command
00: Digital keypad (PU01) UP/DOWN
keys or Multi-function Inputs
UP/DOWN. Last used frequency
saved.
01: 0 to +10V from AVI
02: 4 to 20mA from ACI
03: -10 to +10Vdc from AUI
04: RS-485 serial communication (RJ-
11). Last used frequency saved
05: RS-485 serial communication (RJ-
11). Last used frequency not saved.
00