70
1.
In bypass mode, the touch panel shows the following screen and the tri-color LED
indicator illuminates yellow.
(Figure 6-32: Bypass Mode Screen)
2.
Single Input:
Switch
OFF
the bypass breaker, input breaker and output breaker.
Dual Input:
Switch
OFF
the bypass breaker, input breaker and output breaker.
3. The UPS will discharge DC bus voltage, and the tri-color LED indicator will illuminate yellow.
After discharging is completed, the UPS will shut down, and the touch panel and the tri-color
LED indicator will be off.
4.
Switch
OFF
every external battery cabinet’s breaker.
6.3.4 Manual Bypass Mode Turn-off Procedures
WARNING:
1.
For parallel units, ensure that every operation procedure mentioned below is
synchronized to all parallel UPSs.
2.
For parallel application, if you just want to operate a specific UPS but not all
parallel ones, please contact Delta service personnel
In manual bypass mode, the touch panel and the tri-color LED indicator are both
OFF
. In either
single input or dual input, please directly switch
OFF
the manual bypass breaker to completely
shut down the UPS.