background image

Page 4

210398   Rev. A

w w w . s p e c s e l e c t . c o m

If Hardwire Operated

• 102mm (4”) box is supplied, remove suitable knockouts and insert cable bushing as per Fig. 3.

• Rough-in box for sensor location as per Fig. 6.  Note: Solenoid extension cord supplied with trim is 915mm (36”) long.

• Securely attach box to wall structure.

• Install CSA and/or UL approved Class 2 transformer or equivalent in a convenient location or in a pipe chase.  

(Do NOT install the

  transformer inside the control box.)

• Run suitable wire from 24VAC power source into box.  Use wire which complies with local electrical codes for 1 amp load.  No.18 cable is

  usually sufficient.

• Attached supplied plasterguard as per Fig. 4 to ensure sensor mounting holes are positioned correctly.

• Rough-in 2X4 junction box as per Fig.6.

 

Solenoid Extension Cords

Fig. 5

• Install and attach flush valve to water supply as per Fig. 2.

If Hardwire Operated

• Attach hardwire converter supplied to the 24VAC power source using the

  wire nuts provided.

• Attach converter to the sensor module using the snap connector.

• Using the 915mm (36”) solenoid extension cord supplied, attach the male

  tabs to the sensor module and then run the wire down to the 2X4 rough-in

  box located behind the flush valve.

• Using the 25.4mm (12”) solenoid extension cord supplied, attach the female

  connectors to the solenoid valve on the flush valve cap.  

• Feed the free end of the wire through the tube assembly.

• Feed the tube assembly and wire through the bushing on the 2X4 plate and

  into the rough-in box located behind the flush valve.

• Attach the wires to the extension cord which was run down from the sensor.  Make sure to correctly match the wire colours on both

  extension cords.

• Secure 2X4 stainless steel plate with bushing to the junction box.

• Assemble cover onto flush valve cap and attach using 2 vandal proof screws provided.  Ensure the tube assembly is aligned with the slot

  in the back of the cover.

• If the factory default settings for the sensor are not suitable, refer to Step 6 for sensor adjustments.

• Attach sensor plate to the box using the 4 vandal proof screws provided.

STEP 1 - ROUGH-IN FLUSH VALVE

STEP 2 - ROUGH-IN SENSOR BOX

STEP 3 - ROUGH-IN JUNCTION BOX

STEP 4 - INSTALL SENSOR PLATE AND TUBE ASSEMBLY

Water closet sensing distance of 40”, 24 hour flush is off, and flush delay is 4 seconds.

Urinal sensing distance of 20”, 24 hour flush is off, and no flush delay.

 

 

Once in operation mode, if adjustments are preferred, installer must move into set up mode (see Step 6).

A sequence of red lights that strobe across the sensing lens window will signify that the valve is now in operation mode. 

Once in operation mode, if factory settings are preferred, no further action is required and the valve installation is complete.

Factory pre-set functions are:

STEP 5 - OPERATION MODE

FUNCTION AND TROUBLESHOOTING LIGHTS

HARDWIRE VERSION: NO LIGHTS-NO POWER

Check that the 24VAC transformer has power on the incoming 120VAC side.  (Transformer breaker is turned on.)

Check the connection of the flushometer wires to 24VAC transformer.

Check that the connection of the hardwire converter is made to the electronic board within the electronic flush valve housing.

For further technical assistance, call Delta Commercial Technical Service at 1-800-387-8277 (Canada) or 1-877-509-2680 (U.S.A.).

Electronic Override Button in Operating Mode:

 BLUE light flashes once when Electronic Override Button is activated.  Should the 

electronic override button stick, the program will continue to operate and will reset automatically if the electronic override button is repaired

or it returns to home position.

Содержание TECK 81T2 -WHSHWA Series

Страница 1: ... Brass Renewable Seat for previous Flush Valve models ordered separately 31 3 9a 8a 9b 10c PLEASE LEAVE this M I Sheet with the owner maintenance plumber etc as items relating to ongoing maintenance suggestions and procedures are included Nut Fibre Washer Rubber Washer Slip Joint Nut Installation Filter Screen 29 24VAC 6 4 VDC 12 36 3 5 6 4 30a 30b For valves manufactured after October 2014 0 5L 1...

Страница 2: ...s 4 1 2 x 4 1 2 114 mm x 114 mm shown Stainless Steel Cover with Studs Screws 4 pieces No 6 32 x 2 flat head Stainless Steel Screws Security Spanner Bit package for 4 1 2 114 mm Cover Sensor Module Urinal Flush Valve Sensor Module Water Closet Flush Valve Regulating Screw O Ring Cover Gasket 3 pkg Poppet Pin Pack 3 pkg also see 10b see Table 1 on page 1 Washer 3 pkg required for 6 0 4 8 4 2L Valve...

Страница 3: ...installation This assures SMOOTHER OPERATION of the valves and longer life for the working parts 114mm 4 1 2 114mm 4 1 2 B 121mm 13mm 4 75 44 71mm 2 81 76mm 3 0 VACUUM BREAKER TUBE 38mm 1 5 38mm 1 5 SLIP JOINT NUT WASHERS SUPPLIED 152 mm 6 0 70mm 2 75 114mm 4 5 114 mm 4 5 71mm 2 81 64mm 2 5 VACUUM BREAKER TUBE 19mm 0 75 19mm 0 75 SLIP JOINT NUT WASHERS SUPPLIED Fig 1 D 25mm 1 38mm 1 1 2 Cover Tube...

Страница 4: ...X4 stainless steel plate with bushing to the junction box Assemble cover onto flush valve cap and attach using 2 vandal proof screws provided Ensure the tube assembly is aligned with the slot in the back of the cover If the factory default settings for the sensor are not suitable refer to Step 6 for sensor adjustments Attach sensor plate to the box using the 4 vandal proof screws provided STEP 1 R...

Страница 5: ...r copper sweat with adaptor supplied Sensor Box 102 x 102 x 51mm 4 x 4 x 2 Junction Box C L Centerline Stainless Steel Coverplate Sensor Box 102 x 102 x 51mm 4 x 4 x 2 of sensor box 152mm 6 70mm 2 75 sensor 44mm 1 3 4 from centreline of stop 44mm 1 3 4 from centerline of stop Hardwire Junction Box and Sensor Rough In See Fig 1 for placement of inlet stop NOTE Hardwire juction box installed behind ...

Страница 6: ...e electronic override button until the lights loop back around to a setting that is one less the previous setting Once again verify that the sensor is not detecting the water closet door If not the sensor is now set at your desired position The sensing distance for water closets can be set between 24 and 56 and for urinals between 12 and 28 If all adjustments have been completed press and hold dow...

Страница 7: ...ove the water main etc We strongly recommend that pipe size calculations be done to insure proper water supply sizes Flushometers do NOT provide a water supply they are merely automatically timed self closing valves The inlet supply piping is the water reservoir that must supply sufficient water volume in a short period of time 4 to 10 seconds to properly flush and clear the fixture CONTINUOUS FLU...

Страница 8: ...is warranty gives you specific legal rights and you may also have other rights which vary from state to state This warranty is for commercial products only from Delta Faucet Company and Delta Faucet Canada a division of Masco Canada Limited and is void for any damage to this faucet due to misuse abuse neglect accident improper installation any use in violation of instructions furnished by Delta Fa...

Отзывы: