32
Infrasuite Power Management
Chapter 8 : Troubleshooting
Problem
Possible case
Solution
All LEDs on the
front panel are off.
The power
sources, S1 and
S2, are both
absent.
1. Check the output (overload/
short-circuit).
2. Check both power sources, S1
and S2.
3. Reset the upstream circuit
breakers.
S1 or S2 LED is
off.
The corresponding
power source is
absent or out of
range.
1. Check the corresponding power
source.
2. Reset the corresponding
upstream circuit breaker.
Fault LED flashes.
Output overload.
Reduce the connected load.
Over temperature.
Check the environment temperature.
Fault LED lights
up.
Internal component
damage.
Please contact service personnel.
Can not
communicate with
the rSTS.
Wrong setting or
malfunction.
Refer to the user manual of
InsightPower SNMP IPv6 for rSTS.