Infrasuite Power Management
No.
Item
Description
7
Test
LED
Green. If you press the test button, the rSTS will be under
test and the Test LED will flash (on: 0.5s; off: 0.5s). In normal
operation, the LED will be off.
8
Fault
LED
Red. If the rSTS has any internal fault, the LED will light up
as red. If the rSTS has any environmental fault, the LED
will flash (on: 0.5s; off: 0.5s). Via the
NETWORK
port, fault
messages will be sent to a connected PC. From the PC, you
can see error codes as follows.
Environmental Fault
Error Code
Meaning
E01
Output overload
E02
Over temperature (due to detection of
ambient temperature)
E03
Over temperature warning (due to
detection of S1 heat-sink temperature)
E04
Over temperature warning (due to
detection of S2 heat-sink temperature)
Internal Fault
Error Code
Meaning
E11
Over temperature (due to detection of S1
heat-sink temperature)
E12
Over temperature (due to detection of S2
heat-sink temperature)
E13
Auxiliary power 1 circuit failure
E14
Auxiliary power 2 circuit failure
E21
Input relay of S1 is open
E22
Input relay of S1 is short
E23
Input relay of S2 is open
E24
Input relay of S2 is short
E25
Input SCR of S1 is open
E27
Input SCR of S2 is open