15
Quick installation guide for RPI M50A inverters
Setting the inverter ID
If your PV plant contains multiple inverters, for each of the inverters a different inverter ID has to be set
The inverter ID is needed to identify each inverter For a description of the RS485 connection, see
“Con-
necting to a datalogger via RS485 (optional)”, p 11
E - V a n d a a g : 0 k W h
V e r m o g e n : 0 W
S t a t u s : A m N e t z
1 0 . S e p 2 0 1 4 1 5 : 3 2
1.
When the default information is displayed, press any button to open the main menu
Otherwise, repeatedly press the button
ESC
until the main menu is displayed
I n v e r t e r I n f o .
G e n e r a l S e t t i n g s
I n s t a l l S e t t i n g s
A c t i v e / R e a c t i v e P w r
F R T
2.
Use the buttons
and
to select
Install Settings
To confi rm your selection, press the button
ENT
0 * * *
P a s s w o r d
3.
The menu is protected by password 5555 Use the buttons
and
to set each
digit
To confi rm a digit, press the button
ENT
G r i d S e t t i n g s
C o u n t r y
I n s u l a t i o n
I n v e r t e r I D : 0 0 1
4.
Use the buttons
and
to select
Inverter ID
To confi rm your selection, press the button
ENT
I D = 0 0 1
S e t t i n g I D :
5.
Use the buttons
and
to change the value
To confi rm your setting, press the button
ENT
Setting AC connection type
Per default, the AC connection type is set to 3P4W (3 N + PE) Only if you use an AC connection
with 3 PE (3P3W), you need to change this setting For a description of the AC connection, see
“Connecting to the grid (AC)”, p 8
E - V a n d a a g : 0 k W h
V e r m o g e n : 0 W
S t a t u s : A m N e t z
1 0 . S e p 2 0 1 4 1 5 : 3 2
1.
When the default information is displayed, press any button to open the main menu
Otherwise, repeatedly press the button
ESC
until the main menu is displayed
I n v e r t e r I n f o .
G e n e r a l S e t t i n g s
I n s t a l l S e t t i n g s
A c t i v e / R e a c t i v e P w r
F R T
2.
Use the buttons
and
to select
Install Settings
To confi rm your selection, press the button
ENT
0 * * *
P a s s w o r d
3.
The menu is protected by password 5555 Use the buttons
and
to set each
digit
To confi rm a digit, press the button
ENT
A C C o n n e c t i o n : 3 P 4 W
E P O : N o r m a l C l o s e
A n t i - i s l a n d i n g : O N
M a x . P o w e r : 1 0 0 %
R e t u r n t o F a c t o r y
4.
Use the buttons
and
to select
AC Connection
and press the button
ENT
Use the buttons
and
to select
3P3W
, and press the button
ENT
to confi rm.