2
.Installation
2.1.Installation on wall
1. DC1
(1)
Use the supplied DIN Rail and mount in distribution cabinet (A).
(2)
Fix the Data Collector on top of the DIN Rail.(B)
(3)
Buckle the Data Collector on the DIN Rail.(C)
(4)
Install two stoppers on the DIN Rail on both side of the Data Collector, then lock in the screws on stoppers to fix these stoppers
on the DIN Rail.(D)
•
Specification of RSSI and SNR
•
Solar Panel and Mounting Rack
- Distance of the antenna from solar panel > 10 cm
- Distance of the antenna from mounting rack > 15 cm
•
Metal Enclosure
- Distance of the antenna from metal enclosure > 120 cm
•
Concrete Block
- Antenna should be placed in front of the concrete block in the transmission path.
- Distance of the antenna from concrete block > 15 cm
- Height difference between antenna and concrete block > 10 cm (antenna placed higher)
•
Substation
- Distance of the antenna from the substation > 1.5 m
•
High Voltage Transmission Tower
- Distance of the antenna from HV transmission tower > 10 m
RSSI
SNR
> -105 dBm
> 2 dB
D
C
B
A
C
B
A
D
Guidance and Recommendation on the Installation Location of SUB
_
1G
2. DC1 + SUB_1G (N1)
(1)
Use the supplied DIN Rail and mount in distribution cabinet (A).
(2)
Fix the Data Collector on top of the DIN Rail.(B)
(3)
Buckle the Data Collector on the DIN Rail.(C)
(4)
Install two stoppers on the DIN Rail on both side of the Data Collector, then lock in the screws on stoppers to fix these stoppers
on the DIN Rail.(D)
10