3.4.1 AC Grid Types and Connections
The default AC Grid connection is 3Ø-3W. It can also connect 3Ø-4W with Neutral (N).
The inverter will operate from the following grid connections without need of an
external transformer:
ATTENTION
3.4.2 Required Protective Devices
It is recommended to install an upstream circuit breaker between AC side and
inverter side for over current protection.
3.4.3 AC Wiring Preparation
Model
Upstream circuit breaker
M70A_260
150A max.
M50A_260
125A max.
• The cross-sectional area for each AC conductor is shown below.
• The information and notice of cable using is shown on next page.
TNC system
230/400V
inverter
inverter
inverter
inverter
inverter
L1
L2
L3
PE/N
TNC-S system
230/400V
L1
L2
L3
N
PE
TT system
230/400V
L1
L2
L3
N
IT system
230/400V
L1
L2
L3
TNS system
230/400V
L1
L2
L3
N
PE
Figure 3-13: Size of AC conductors
N
L2
L1
outer
jacket
Conductor cross-section:
M70A_260 -
Cu: 35 mm
2
(1 AWG) ~ 120 mm
2
(250 kcmil)
Al: 60 mm
2
(2/0 AWG) ~ 120 mm
2
(250 kcmil)
M50A_260 -
Cu: 25 mm
2
(2 AWG) ~ 60 mm
2
(2/0 AWG)
Al: 35 mm
2
(1 AWG) ~ 60 mm
2
(2/0 AWG)
PE
Stripping length: 20mm
L3
29
Installation