DANGER : ELECTRICAL HAZARD!!
- PV array converts sunlight into electric power with high DC voltage and high
DC current which can cause dangerous electrical shock hazard!
- Use an opaque material to cover the PV array before wiring or cabling.
- Ensure the correct polarities are connected when DC cabling is applied.
- Before plug in the DC connectors, pay attention to the polar is correct.
Reverse positive and negitive voltage, inverter will probably damage.
WARNING !
- The risk of electric shock and fire exists because of high DC and AC voltages.
- Only PV modules that are listed with system voltage under 1100V are permitted
for use.
- Ensure the two DC switches are placed in the "OFF" position, and the PV array
is disconnected when DC conductors are connected.
- The PV Array current carrying conductors (positive or negative) must not be
referenced to ground.
ATTENTION
- Do not remove the waterproof plug for unused DC strings.
- Do not remove the protective cover for unused MPPT 3 DC strings.
ATTENTION
3.5 Electrical Installation for DC Wiring
DANGER : ELECTRICAL HAZARD!!
- In order not to damage the components in the inverter, don’t repeat to change
the status of DC Switch quickly, the correct operation is waiting for the LED
display show "green off and yellow flash" (No DC) or turn on the switch after
5 minute later.
CAUTION: DC SWICH ON/OFF !
33
Installation