Quick Installation Guide for Solar Power Inverter M125HV EU V1 EN 2019-04-01

Basic safety instructions

DANGER 

Electric shock

Potentially fatal voltages are present at the 

inverter during operation. When the inverter 

is disconnected from all power sources, this 

voltage remains in the inverter for up to 135 

seconds. 

Therefore, always carry out the following steps 

before working on the inverter
1.  Turn both DC isolating switches to the 

OFF  

position.

2.  Disconnect the inverter from all AC and DC 

voltage sources and make sure that none 

of the connections can be accidentally 

restored.

3.  Wait at least 135 seconds until the internal 

capacitors have discharged.

DANGER

Electric shock

Potentially fatal voltages are present at the 

inverter DC connections. When light falls on the 

solar modules, they immediately start to gener-

ate electricity. This also happens when light 

does not fall directly on the solar modules.

 

► Never disconnect the inverter from the solar 

modules when it is under load. 

 

► Turn both DC isolating switches to the 

OFF 

position.

 

► Disconnect the connection to the mains so 

that the inverter cannot supply energy to the 

mains. 

 

► Disconnect the inverter from all AC and DC 

voltage sources. Ensure that none of the 

connections can be restored accidentally.

 

► Ensure that the DC cables cannot be 

touched accidentally.

WARNING

Electric shock

If the doors of the inverter are open, the IP65 

degree of protection is no longer guaranteed.

 

► Only open the doors when absolutely 

necessary.

 

► Do not open the doors if water or dirt might 

enter the inverter. 

 

► After work is completed, ensure that the 

doors are properly shut and screwed in 

again. Check that the doors are properly 

sealed.

WARNING

Heavy weight

The inverter is very heavy.

 

► The inverter must be lifted and carried by 

at least 3 people or using appropriate lifting 

gear.

 

● To comply with the IEC 62109-5.3.3 safety requirements 

and avoid injury or material damage, the inverter must be 

installed and operated in accordance with the safety and 

operating instructions set out in this manual. Delta Electron-

ics is not responsible for damage resulting from failure to 

follow the safety and operating instructions set out in this 

manual.

 

● The inverter may be installed and commissioned only by 

installers who have been trained and certified for the instal-

lation and operation of mains-based solar inverters.

 

● All repair work on the inverter must be carried out by Delta 

Electronics. Otherwise, the warranty will be void.

 

● Warning instructions and warning symbols attached to the 

inverter by Delta Electronics must not be removed.

 

● The inverter has a high leakage current value. The ground-

ing cable 

must

 be connected before commencing opera-

tion.

 

● Do not disconnect any cables while the inverter is under 

load due to risk of a fault arc.

 

● To prevent damage due to lightning strikes, follow the provi-

sions that apply in your country.

 

● The surface of the inverter can get very hot during op-

eration. Always wear safety gloves when you touch the 

inverter.

 

● The inverter is very heavy. For hoisting and moving, use a 

mechanical lifting device (e.g. crane or block and tackle). 

At least three persons are required for manual hoisting and 

moving. 

 

● Only equipment in accordance with SELV (EN 60950) may 

be connected to the RS485 interfaces.

 

● All external connections must be sufficiently insulated in 

order to ensure the IP65 degree of protection. Seal any un-

used connection openings with the closure caps supplied.

 

● The covers in the interior of the inverter do 

not

 have to be 

removed for the installation. All connections required for the 

installation are also accessible with the covers installed.

Содержание M125HV

Страница 1: ...Solar power inverter M125HV Quick Installation Guide United Kingdom European Union...

Страница 2: ...all mounting 16 Grounding the inverter housing 18 Earthing via the external grounding screws 18 Grounding via the PE screw of the AC connection 19 Connecting the mains AC general notes 20 Connecting t...

Страница 3: ...r is very heavy The inverter must be lifted and carried by at least 3 people or using appropriate lifting gear To comply with the IEC 62109 5 3 3 safety requirements and avoid injury or material damag...

Страница 4: ...pring washers and washers Mounting tool for DC plug 2 To disconnect the Amphenol UTX plugs from the DC connections of the inverter DC plug for DC 20 Amphenol UTX Female for DC UTXCFA4A for 4 6 mm2 DC...

Страница 5: ...M6 mounting screw 1 M4 mounting screw 2 Installation material for DC surge protection devices type 1 PE cable 1 DIN rail 1 M4 mounting screw 3 All mounting material for the use of type 1 surge protec...

Страница 6: ...2 7 8 9 3 1 1 2 4 5 10 11 12 1 Air outlets 7 Status LED 2 Additional mounting plate for wall mounting 8 Communication card 3 Type plate 9 Grounding connection 4 DC isolating switch 1 10 DC input conn...

Страница 7: ...urge protection devices type II 17 DC string fuses minus top and plus bottom 14 Internal fan 2 18 DIN rail for DC surge protection devices type I not included in delivery 15 Integrated DC surge protec...

Страница 8: ...ocal regula tions WEEE mark The inverter must not be disposed of as standard household waste but in accor dance with the applicable electronic waste disposal regulations of your country or region The...

Страница 9: ...EN 2019 04 01 Dimensions 663 538 6 19 2 102 306 510 612 980 950 1 0 5 1 1 940 52 75 2 344 226 5 266 5 306 5 40 980 950 1 0 5 40 92 Ansicht von vorne mit Montagewinkeln f r die Wandmontage Ansicht von...

Страница 10: ...be disturbing Therefore carefully choose the place of installation Mount the inverter on a fireproof wall Mounting alignment Outdoor installations The inverter has a protection degree of IP65 and can...

Страница 11: ...normal op erating behavior for the inverter and is necessary to protect the internal electronics In areas with many trees or meadows pollen and parts of plants can block air inlets and outlets and ob...

Страница 12: ...TE VDE 0100 712 This standard contains the requirements for minimum cable diameters and for avoiding overheating due to high currents Handling aluminum conductors during installation work The special...

Страница 13: ...erter DC plugs for DC cables DC DC a b Amphenol mm2 mm 4 6 5 3 7 65 UTXCFA4A 4 6 5 3 7 65 UTXCMA4A 1 Included in delivery Always use the mounting tools supplied to remove the DC plug from the DC conne...

Страница 14: ...e insulation AC cable When mounting the inverter always allow suf ficient space downwards so that the AC cable can be easily inserted into the inverter Fasten the cable with a strain relief element Re...

Страница 15: ...g the inverter Floor mounting 1 Fasten the 4 mounting brackets for floor mounting to the feet of the inverter with 2 M10 screws each torque 15 Nm spring washer and washer The screws are in cluded in t...

Страница 16: ...his are only allowed in exceptional cases approved by Delta Electronics Always check with Delta Customer Service first if you want to deviate from the work instructions given in this section 1 Screw t...

Страница 17: ...4 01 3 Mount the inverter on the mounting plate using a lifting device 4 Check that the inverter is correctly mounted on the mount ing plate 5 Attach the mounting plate on the inverter feet to wall th...

Страница 18: ...on the right foot inside on the PE screw of the AC connec tion Grounding via the external grounding screws 1 Bolt the grounding cable onto the right foot of the inverter Nuts spring washers and washer...

Страница 19: ...pper cables Use aluminum cables cable lugs covered with tin for alumi num cables Always follow the cable lug manufacturer s installation instructions 10 5 m a x 3 1 10 5 m a x 3 1 1 Screw the earthing...

Страница 20: ...nt circuit breaker Minimum tripping current of the type A residual current circuit breaker 300 mA The required tripping current of the residual cur rent circuit breaker depends first and foremost on t...

Страница 21: ...inverter enclosure must always be grounded via one of the external terminals In an IT type earth connection scheme the inverter housing can be connected to earth either through one of the external te...

Страница 22: ...r Power Inverter M125HV EU V1 EN 2019 04 01 72 5 76 8 mm 65 1 72 5 mm 58 2 65 1 mm 44 8 58 2 mm 33 0 44 8 mm D1 D2 D4 D5 D3 P1 P2 Use of the parts of the AC cable glands depends on the cable diameter...

Страница 23: ...ck Installation Guide for Solar Power Inverter M125HV EU V1 EN 2019 04 01 Tighten the nuts of the AC conductors torque 25Nm Tighten the cover of the AC conductors torque 0 8 Nm Connecting the mains AC...

Страница 24: ...nstallation NOTICE Ingress of moisture Moisture can enter via open DC connections To ensure protection degree IP65 close un used DC connections with the rubber plugs that are attached to the DC connec...

Страница 25: ...01 Closing the inverter ATTENTION Impairment of operating response caused by moisture and dirt In order to restore the IP65 degree of protection once the installation work is complete close the doors...

Страница 26: ...l block 4 RS485 terminal block 5 Protection against electromagnetic interference EMI Connecting a PC via RS485 To commission an inverter you need a PC with either the M125HV commissioning software or...

Страница 27: ...pplicable Connecting a single inverter to a data logger ON 1 Termination resistor ON Data logger Connecting multiple inverters to a data logger If the data logger does not have an integrated RS485 ter...

Страница 28: ...the active power an external ripple control receiver can be connected to the digital inputs Pin Short circuit Assigned action V1 K0 V1 K0 External power off EPO K1 V1 K1 Max active power 0 K2 V1 K2 Ma...

Страница 29: ...ot yet done so download the commissioning software from www solar inverter com 2 Open the commissioning software 1 2 3 Select a COM port 1 and click on the Open Port button 2 1 2 4 Enter the number of...

Страница 30: ...inverter ID 6 To save the new inverter IDs click on the Set ID button 2 The message ID Setting Successful appears if the setting was successful 1 2 7 Enter the number of your country in the Country I...

Страница 31: ...allation Guide for Solar Power Inverter M125HV EU V1 EN 2019 04 01 Commissioning via the commissioning software The message Sync Time successful appears if the setting was successful Commissioning is...

Страница 32: ...rters button 2 Error event Only xx inverters found Please check your 485 connection German Nur xx Wechselrichter gefunden Bitte die RS485 Verbindung pr fen Cause of error Fewer inverters were found wh...

Страница 33: ...leshooting for the commissioning software Error message and cause of error Fault correction Error event Time Sync failed German Synchronisierung der Uhrzeit fehlgeschlagen Cause of error Time synchron...

Страница 34: ...ISC 320 A Maximum breaking current 350 A DC1 200 A DC1 150 A Open circuit voltage VOC 1500 V Number of MPP trackers 1 Number of DC connectors 20 pairs 12 8 Electrical isolation No Overvoltage category...

Страница 35: ...out derating 25 50 C Storage temperature range 25 60 C Relative humidity 0 100 non condensing Max operating height 3000 m above sea level Noise level at a distance of 1 m 78 dB A Standards and guideli...

Страница 36: ...nverter com 0800 800 9323 toll free Greece support greece solar inverter com 49 7641 455 549 Great Britain support uk solar inverter com 0800 051 4281 toll free Israel supporto israel solar inverter c...

Отзывы: