- 4 - 

04P 06P Attrib. 

Register content 

Description 

#2 

#2 

O  R/W 

CH1 Input mode setting 

Input mode: Default = H’0000. Take CH1 for example: 

Mode 0 (H’0000): Pt100: -180°C ~ 800°C   

Mode 1 (H’0001): Ni100: -80°C ~ 170°C 

Mode 2 (H’0002): Pt1000: -180°C ~ 800°C 

Mode 3 (H’0003): Ni1000: -80°C ~ 170°C   

Mode 4 (H’0004): 0~300

Ω

 

Mode 5 (H’0005): 0~3000

Ω

 

Mode 6 (H’0006): JPt100 (-180°C ~ 500°C) 

Mode 7 (H’0007): Cu50 (-50°C ~ 150°C) 

Mode 8 (H’0008): Cu100 (-50°C ~ 150°C) 

Mode 9 (H’0009): LG-Ni1000 (-50°C ~ 180°C) 

Mode -1 (H’FFFF): Channel 1 unavailable   

Note: 04PT-E2 do NOT support mode 6-9.   

#3 

#3 

O  R/W 

CH2 Input mode setting 

#4 

#4 

O  R/W 

CH3 Input mode setting 

#5 

#5 

O  R/W 

CH4 Input mode setting 

 

#6 

O  R/W 

CH5 Input mode setting 

 

#7 

O  R/W 

CH6 Input mode setting 

#7 

 

O R/W  Temperature 

unit 

setting 

Select the temperature unit (Celsius °C / Fahrenheit °F). 

Default = H’0(°C) 

#8 

#8 

O  R/W 

CH1 sampling range 

Set sampling range: 

Range = K1 ~ K100 

Default = K10 

#9 

#9 

O  R/W 

CH2 sampling range 

#10 

#10 

O  R/W 

CH3 sampling range 

#11 

#11 

O  R/W 

CH4 sampling range 

 

#12 

O  R/W 

CH5 sampling range 

 

#13 

O  R/W 

CH6 sampling range 

#12 #14 X  R Average 

temperature 

measured 

at 

CH1 

Average temperature measured. 

Setting Temperature Unit : 

 DVP04PT-E2

CR#7 

 DVP06PT-E2

CR#27   

 

#13 

#15 

Average temperature measured at CH2 

#14 

#16 

Average temperature measured at CH3 

#15 

#17 

Average temperature measured at CH4 

 

#18 

Average temperature measured at CH5 

 

#19 

Average temperature measured at CH6 

#20 

#20 

Present temperature measured at CH1 

Present temperature measured. 

Setting Temperature Unit : 

 DVP04PT-E2

CR#7 

 DVP06PT-E2

CR#27 

#21 

#21 

Present temperature measured at CH2 

#22 

#22 

Present temperature measured at CH3 

#23 

#23 

Present temperature measured at CH4 

 

#24 

Present temperature measured at CH5 

 

#25 

Present temperature measured at CH6 

 #26 

R/W 

Mode 4 (H’0004): 0~300

Ω

. Temperature 

display decimal digit changes 

In mode 4 (0~300

Ω

), temperature display decimal 

changes (0: 1 digit after the decimal place/ 1: 2 digits 

after the decimal place). Default= H0 

 #27 

R/W 

Temperature 

unit 

setting 

Select the temperature unit (Celsius °C / Fahrenheit °F). 

Default = H’0(°C) 

#28 

#28 

O  R/W 

Adjusted offset value of CH1 

Adjusted offset value measured, range K-1000 ~ K1000. 

Default = K0 

  Measured Value = Original Value – Adjusted offset value   

Unit Setup: 

 DVP04PT-E2

CR#7 

 DVP06PT-E2

CR#27 

#29 

#29 

O  R/W 

Adjusted offset value of CH2 

#30 

#30 

O  R/W 

Adjusted offset value of CH3 

#31 

#31 

O  R/W 

Adjusted offset value of CH4 

 

#32 

O  R/W 

Adjusted offset value of CH5 

 #33

 

O  R/W 

Adjusted offset value of CH6 

#40 

#40 

O  R/W 

Function: Set value changing prohibited 

Prohibit set value changing, b0~b5 corresponds to CH1 ~ 

CH6. Default =H’0000 

#41 

#41 

X  R/W 

Function: Save all the set values 

Save all the set values. Default =H’0000 

#43 #43 X  R  Error 

status 

Register for storing all error status. See the table of error 

status for more information. 

Содержание DVP04PT-E2

Страница 1: ...DVP 0280530 02 20220112...

Страница 2: ...k all wiring again before DVP04 06PT E2 is powered up After DVP04 06PT E2 is disconnected Do NOT touch any terminals in a minute Make sure that the ground terminal on DVP04 06PT E2 is correctly ground...

Страница 3: ...E2 If using Ni100 Pt100 and 300 resistance sensor the internal excitation current is 1 53mA if using Ni1000 Pt1000 and 3000 resistance sensor the internal excitation current is 200 A 4 Connect FE wit...

Страница 4: ...Pt1000 180 C 800 C Ni1000 80 C 170 C JPt100 180 C 500 C Cu50 50 C 150 C Cu100 50 C 150 C LG Ni1000 50 C 180 C Pt100 180 C 800 C Ni100 80 C 170 C Pt1000 180 C 800 C Ni1000 80 C 170 C JPt100 180 C 500...

Страница 5: ...Average temperature measured at CH5 19 X R Average temperature measured at CH6 20 20 X R Present temperature measured at CH1 Present temperature measured Setting Temperature Unit DVP04PT E2 CR 7 DVP0...

Страница 6: ...R able to read data by using FROM instruction W able to write data by using TO instruction Module Reset Write H 4352 into CR 0 the action can re initialize all parameter settings to ensure normal fun...

Страница 7: ...6 X R W Auto tuning 0 Disabled 1 Auto tuning Default K0 Explanation on Special Registers D9900 D9999 When DVP ES2 MPU is connected with modules registers D9900 D9999 will be reserved for storing value...

Страница 8: ...de9 0 1 Mode4 Mode5 0 1 Mode 0 Mode 3 8 000 4 000 1 800 800 180 400 0 C C Digital output Measured temperature input 3 380 1 120 338 112 0 F F Digital output Measured temperature input Mode 1 Mode 4 1...

Страница 9: ...mm Ni100Pt100 J Pt100 Cu50 C u100 Ni1000 P t1000 LG Ni1000 3 A G 1 ADC A G INA 1 CH1 2 Wire CH4 3 Wire O1 I1 I1 0 300 Ni100 Ni1000 Pt100 Pt1000 Cu50 Cu100 JPt100 LG Ni1000 0 3000 0 300 Ni100 Ni1000 P...

Страница 10: ...C 32 131 F 04PT 3 Pt100 DIN 43760 1980 JIS C1604 1989 100 3850 PPM C Pt1000 DIN EN60751 1 k 3850 PPM C Ni100 Ni1000 DIN 43760 0 300 0 3000 06PT 3 Pt100 DIN 43760 1980 JIS C1604 1989 100 3850 PPM C Pt1...

Страница 11: ...F CR 04PT 06PT 0 0 O R DVP04PT E2 H 0082 DVP06PT E2 H 00C2 1 1 O R 16 2 2 O R W CH1 H 0000 CH1 0 H 0000 Pt100 180 C 800 C 1 H 0001 Ni100 80 C 170 C 2 H 0002 Pt1000 180 C 800 C 3 H 0003 Ni1000 80 C 170...

Страница 12: ...CH3 Offset 31 31 O R W CH4 Offset 32 O R W CH5 Offset 33 O R W CH6 Offset 40 40 O R W b0 b5 CH1 CH6 H 0000 41 41 X R W H 0000 43 43 X R 100 100 O R W b0 b5 CH1 CH6 0 Disable 1 Enable H 0000 101 101 X...

Страница 13: ...144 164 184 O R W KD K 29 125 145 165 185 O R W K0 126 146 166 186 O R W K0 127 147 167 187 X R 128 148 168 188 O R W H 0 H 1 H 0000 129 149 169 189 O R W K 32 760 K32 760 K32 000 130 150 170 190 O R...

Страница 14: ...3 D9973 CH4 D9904 D9914 D9924 D9934 D9944 D9954 D9964 D9974 CH5 D9905 D9915 D9925 D9935 D9945 D9955 D9965 D9975 CH6 D9900 D9999 WPLSoft FROM TO CR 8 CR 13 1 PT Offset Offset Offset 0 3 6 9 0 1 4 5 0 1...

Страница 15: ...t100 J Pt100 Cu50 C u100 Ni1000 P t1000 LG Ni1000 3 A G 1 ADC A G INA 1 CH1 2 Wire CH4 3 Wire O1 I1 I1 0 300 Ni100 Ni1000 Pt100 Pt1000 Cu50 Cu100 JPt100 LG Ni1000 0 3000 0 300 Ni100 Ni1000 Pt100 Pt100...

Страница 16: ...04PT 3 Pt100 DIN 43760 1980 JIS C1604 1989 100 3850 PPM C Pt1000 DIN EN60751 1 k 3850 PPM C Ni100 Ni1000 DIN 43760 0 300 0 3000 06PT 3 Pt100 DIN 43760 1980 JIS C1604 1989 100 3850 PPM C Pt1000 DIN EN6...

Страница 17: ...CR 04PT 06PT 0 0 O R DVP04PT E2 H 0082 DVP06PT E2 H 00C2 1 1 O R 16 2 2 O R W CH1 H 0000 CH1 0 H 0000 Pt100 180 C 800 C 1 H 0001 Ni100 80 C 170 C 2 H 0002 Pt1000 180 C 800 C 3 H 0003 Ni1000 80 C 170...

Страница 18: ...CH3 Offset 31 31 O R W CH4 Offset 32 O R W CH5 Offset 33 O R W CH6 Offset 40 40 O R W b0 b5 CH1 CH6 H 0000 41 41 X R W H 0000 43 43 X R 100 100 O R W b0 b5 CH1 CH6 0 Disable 1 Enable H 0000 101 101 X...

Страница 19: ...144 164 184 O R W KD K 29 125 145 165 185 O R W K0 126 146 166 186 O R W K0 127 147 167 187 X R 128 148 168 188 O R W H 0 H 1 H 0000 129 149 169 189 O R W K 32 760 K32 760 K32 000 130 150 170 190 O R...

Страница 20: ...63 D9973 CH4 D9904 D9914 D9924 D9934 D9944 D9954 D9964 D9974 CH5 D9905 D9915 D9925 D9935 D9945 D9955 D9965 D9975 CH6 D9900 D9999 WPLSoft FROM TO CR 8 CR 13 1 PT Offset Offset Offset 0 3 6 9 0 1 4 5 0...

Отзывы: