- 4 -
04P 06P Attrib.
Register content
Description
#2
#2
O R/W
CH1 Input mode setting
Input mode: Default = H’0000. Take CH1 for example:
Mode 0 (H’0000): Pt100: -180°C ~ 800°C
Mode 1 (H’0001): Ni100: -80°C ~ 170°C
Mode 2 (H’0002): Pt1000: -180°C ~ 800°C
Mode 3 (H’0003): Ni1000: -80°C ~ 170°C
Mode 4 (H’0004): 0~300
Ω
Mode 5 (H’0005): 0~3000
Ω
Mode 6 (H’0006): JPt100 (-180°C ~ 500°C)
Mode 7 (H’0007): Cu50 (-50°C ~ 150°C)
Mode 8 (H’0008): Cu100 (-50°C ~ 150°C)
Mode 9 (H’0009): LG-Ni1000 (-50°C ~ 180°C)
Mode -1 (H’FFFF): Channel 1 unavailable
Note: 04PT-E2 do NOT support mode 6-9.
#3
#3
O R/W
CH2 Input mode setting
#4
#4
O R/W
CH3 Input mode setting
#5
#5
O R/W
CH4 Input mode setting
#6
O R/W
CH5 Input mode setting
#7
O R/W
CH6 Input mode setting
#7
O R/W Temperature
unit
setting
Select the temperature unit (Celsius °C / Fahrenheit °F).
Default = H’0(°C)
#8
#8
O R/W
CH1 sampling range
Set sampling range:
Range = K1 ~ K100
Default = K10
#9
#9
O R/W
CH2 sampling range
#10
#10
O R/W
CH3 sampling range
#11
#11
O R/W
CH4 sampling range
#12
O R/W
CH5 sampling range
#13
O R/W
CH6 sampling range
#12 #14 X R Average
temperature
measured
at
CH1
Average temperature measured.
Setting Temperature Unit :
●
DVP04PT-E2
:
CR#7
●
DVP06PT-E2
:
CR#27
#13
#15
X
R
Average temperature measured at CH2
#14
#16
X
R
Average temperature measured at CH3
#15
#17
X
R
Average temperature measured at CH4
#18
X
R
Average temperature measured at CH5
#19
X
R
Average temperature measured at CH6
#20
#20
X
R
Present temperature measured at CH1
Present temperature measured.
Setting Temperature Unit :
●
DVP04PT-E2
:
CR#7
●
DVP06PT-E2
:
CR#27
#21
#21
X
R
Present temperature measured at CH2
#22
#22
X
R
Present temperature measured at CH3
#23
#23
X
R
Present temperature measured at CH4
#24
X
R
Present temperature measured at CH5
#25
X
R
Present temperature measured at CH6
#26
O
R/W
Mode 4 (H’0004): 0~300
Ω
. Temperature
display decimal digit changes
In mode 4 (0~300
Ω
), temperature display decimal
changes (0: 1 digit after the decimal place/ 1: 2 digits
after the decimal place). Default= H0
#27
O
R/W
Temperature
unit
setting
Select the temperature unit (Celsius °C / Fahrenheit °F).
Default = H’0(°C)
#28
#28
O R/W
Adjusted offset value of CH1
Adjusted offset value measured, range K-1000 ~ K1000.
Default = K0
Measured Value = Original Value – Adjusted offset value
Unit Setup:
●
DVP04PT-E2
:
CR#7
●
DVP06PT-E2
:
CR#27
#29
#29
O R/W
Adjusted offset value of CH2
#30
#30
O R/W
Adjusted offset value of CH3
#31
#31
O R/W
Adjusted offset value of CH4
#32
O R/W
Adjusted offset value of CH5
#33
O R/W
Adjusted offset value of CH6
#40
#40
O R/W
Function: Set value changing prohibited
Prohibit set value changing, b0~b5 corresponds to CH1 ~
CH6. Default =H’0000
#41
#41
X R/W
Function: Save all the set values
Save all the set values. Default =H’0000
#43 #43 X R Error
status
Register for storing all error status. See the table of error
status for more information.