CR#
Attrib.
Register content
Description
#121 #141 #161 #181 O R/W Sampling time (s)
Range: K1 ~ K30 (s). Default = K2
#122 #142 #162 #182 O R/W K
P
Proportional control constant.
Default = K121
#123 #143 #163 #183 O R/W K
I
Integral constant. Default = K2,098
#124 #144 #164 #184 O R/W K
D
Derivative constant. Default = K-29
#125 #145 #165 #185 O R/W Upper limit of I value Upper limit of I value. Default = K0
#126 #146 #166 #186 O R/W Lower limit of I value Lower limit of I value. Default = K0
#127 #147 #167 #187 X R I value
Current accumulated offset value
#128 #148 #168 #188 O R/W Heating/cooling
0: Heater, 1: Cooler. Default = K0
#129 #149 #169 #189 O R/W Upper limit of output
Upper limit of output. Default =
K32,000
#130 #150 #170 #190 O R/W Lower limit of output Lower limit of output. Default = K0
#131 #151 #171 #191 X R Output percentage Output percentage (Unit: 0.1%)
#132 #152 #172 #192 X R Output width (ms)
Width of control output. Unit: ms
#133 #153 #173 #193 X
R
Output cycle (ms)
Cycle of control output. Unit: ms
#134 #154 #174 #194 X R Output volume
Output volume
#135 #155 #175 #195 X R/W PID_RUN/STOP
0: STOP, 1: RUN. Default = K0
#136 #156 #176 #196 X R/W Auto-tuning
0: Disabled, 1: Auto-tuning. Default
= K0
Explanation on Special Registers D9900~D9999
When DVP-ES2 MPU is connected with modules, registers D9900~D9999 will be
reserved for storing values from modules. You can apply MOV instruction to operate
values in D9900~D9999.
When DVP-ES2 MPU is connected with DVP04/06PT-E2, the configuration of special
registers is as below:
Note 1: D9900 ~ D9999 are average input values of CH1 ~ CH4 and the sampling range is K1 ~ K100.
When the sampling range is set to K1, the values displayed in D9900~D9999 are current values.
You can use: 1. ES_AIO Configuration Function of WPLSoft or 2. FROM/TO instructions (CR#8
~ CR#11) to set the sampling range as K1.
Module
#0
Module
#1
Module
#2
Module
#3
Module
#4
Module
#5
Module
#6
Module
#7
Description
D1320 D1321 D1322 D1323 D1324 D1325 D1326 D1327 Model
Code
D9900 D9910 D9920 D9930 D9940 D9950 D9960 D9970
CH1 average
temperature
D9901 D9911 D9921 D9931 D9941 D9951 D9961 D9971
CH2 average
temperature
D9902 D9912 D9922 D9932 D9942 D9952 D9962 D9972
CH3 average
temperature
D9903 D9913 D9923 D9933 D9943 D9953 D9963 D9973
CH4 average
temperature
D9904 D9914 D9924 D9934 D9944 D9954 D9964 D9974
CH5 average
temperature
D9905 D9915 D9925 D9935 D9945 D9955 D9965 D9975
CH6 average
temperature