Delta DVP04PT-E2 Скачать руководство пользователя страница 7

- 6 - 

CR# 

Attrib. 

Register content 

Description 

#121  #141  #161  #181  O  R/W  Sampling time (s)   

Range: K1 ~ K30 (s). Default = K2 

#122 #142 #162 #182 O R/W  K

P

 

Proportional control constant. 
Default = K121 

#123 #143 #163 #183 O R/W  K

I

 

Integral constant. Default = K2,098 

#124 #144 #164 #184 O R/W  K

D

 

Derivative constant. Default = K-29 

#125  #145  #165  #185  O  R/W  Upper limit of I value  Upper limit of I value. Default = K0 

#126  #146  #166  #186  O  R/W  Lower limit of I value  Lower limit of I value. Default = K0 

#127  #147  #167  #187  X  R  I value   

Current accumulated offset value 

#128  #148  #168  #188  O  R/W  Heating/cooling 

0: Heater, 1: Cooler. Default = K0 

#129 #149 #169 #189 O R/W  Upper limit of output 

Upper limit of output. Default = 
K32,000 

#130  #150  #170  #190  O  R/W  Lower limit of output    Lower limit of output. Default = K0 

#131  #151  #171  #191  X  R  Output percentage    Output percentage (Unit: 0.1%) 

#132  #152  #172  #192  X  R  Output width (ms)   

Width of control output. Unit: ms 

#133  #153  #173  #193  X 

Output cycle (ms) 

Cycle of control output. Unit: ms 

#134 #154 #174 #194  X  R  Output volume 

Output volume 

#135  #155  #175  #195  X  R/W  PID_RUN/STOP   

0: STOP, 1: RUN. Default = K0 

#136 #156 #176 #196 X R/W Auto-tuning  

0: Disabled, 1: Auto-tuning. Default 
= K0 

 

Explanation on Special Registers D9900~D9999

 

When DVP-ES2 MPU is connected with modules, registers D9900~D9999 will be 
reserved for storing values from modules. You can apply MOV instruction to operate 
values in D9900~D9999. 

When DVP-ES2 MPU is connected with DVP04/06PT-E2, the configuration of special 
registers is as below: 

Note 1: D9900 ~ D9999 are average input values of CH1 ~ CH4 and the sampling range is K1 ~ K100. 

When the sampling range is set to K1, the values displayed in D9900~D9999 are current values. 
You can use: 1. ES_AIO Configuration Function of WPLSoft or 2. FROM/TO instructions (CR#8 
~ CR#11) to set the sampling range as K1. 

 
 

Module

#0 

Module 

#1 

Module 

#2 

Module 

#3 

Module 

#4 

Module 

#5 

Module 

#6 

Module 

#7 

Description 

D1320 D1321 D1322 D1323 D1324 D1325 D1326 D1327 Model 

Code 

D9900 D9910 D9920 D9930 D9940 D9950 D9960 D9970 

CH1 average 
temperature 

D9901 D9911 D9921 D9931 D9941 D9951 D9961 D9971 

CH2 average 
temperature 

D9902 D9912 D9922 D9932 D9942 D9952 D9962 D9972 

CH3 average 
temperature 

D9903 D9913 D9923 D9933 D9943 D9953 D9963 D9973 

CH4 average 
temperature 

D9904 D9914 D9924 D9934 D9944 D9954 D9964 D9974 

CH5 average 
temperature 

D9905 D9915 D9925 D9935 D9945 D9955 D9965 D9975 

CH6 average 
temperature 

Содержание DVP04PT-E2

Страница 1: ...DVP 0280530 02 20220112...

Страница 2: ...k all wiring again before DVP04 06PT E2 is powered up After DVP04 06PT E2 is disconnected Do NOT touch any terminals in a minute Make sure that the ground terminal on DVP04 06PT E2 is correctly ground...

Страница 3: ...E2 If using Ni100 Pt100 and 300 resistance sensor the internal excitation current is 1 53mA if using Ni1000 Pt1000 and 3000 resistance sensor the internal excitation current is 200 A 4 Connect FE wit...

Страница 4: ...Pt1000 180 C 800 C Ni1000 80 C 170 C JPt100 180 C 500 C Cu50 50 C 150 C Cu100 50 C 150 C LG Ni1000 50 C 180 C Pt100 180 C 800 C Ni100 80 C 170 C Pt1000 180 C 800 C Ni1000 80 C 170 C JPt100 180 C 500...

Страница 5: ...Average temperature measured at CH5 19 X R Average temperature measured at CH6 20 20 X R Present temperature measured at CH1 Present temperature measured Setting Temperature Unit DVP04PT E2 CR 7 DVP0...

Страница 6: ...R able to read data by using FROM instruction W able to write data by using TO instruction Module Reset Write H 4352 into CR 0 the action can re initialize all parameter settings to ensure normal fun...

Страница 7: ...6 X R W Auto tuning 0 Disabled 1 Auto tuning Default K0 Explanation on Special Registers D9900 D9999 When DVP ES2 MPU is connected with modules registers D9900 D9999 will be reserved for storing value...

Страница 8: ...de9 0 1 Mode4 Mode5 0 1 Mode 0 Mode 3 8 000 4 000 1 800 800 180 400 0 C C Digital output Measured temperature input 3 380 1 120 338 112 0 F F Digital output Measured temperature input Mode 1 Mode 4 1...

Страница 9: ...mm Ni100Pt100 J Pt100 Cu50 C u100 Ni1000 P t1000 LG Ni1000 3 A G 1 ADC A G INA 1 CH1 2 Wire CH4 3 Wire O1 I1 I1 0 300 Ni100 Ni1000 Pt100 Pt1000 Cu50 Cu100 JPt100 LG Ni1000 0 3000 0 300 Ni100 Ni1000 P...

Страница 10: ...C 32 131 F 04PT 3 Pt100 DIN 43760 1980 JIS C1604 1989 100 3850 PPM C Pt1000 DIN EN60751 1 k 3850 PPM C Ni100 Ni1000 DIN 43760 0 300 0 3000 06PT 3 Pt100 DIN 43760 1980 JIS C1604 1989 100 3850 PPM C Pt1...

Страница 11: ...F CR 04PT 06PT 0 0 O R DVP04PT E2 H 0082 DVP06PT E2 H 00C2 1 1 O R 16 2 2 O R W CH1 H 0000 CH1 0 H 0000 Pt100 180 C 800 C 1 H 0001 Ni100 80 C 170 C 2 H 0002 Pt1000 180 C 800 C 3 H 0003 Ni1000 80 C 170...

Страница 12: ...CH3 Offset 31 31 O R W CH4 Offset 32 O R W CH5 Offset 33 O R W CH6 Offset 40 40 O R W b0 b5 CH1 CH6 H 0000 41 41 X R W H 0000 43 43 X R 100 100 O R W b0 b5 CH1 CH6 0 Disable 1 Enable H 0000 101 101 X...

Страница 13: ...144 164 184 O R W KD K 29 125 145 165 185 O R W K0 126 146 166 186 O R W K0 127 147 167 187 X R 128 148 168 188 O R W H 0 H 1 H 0000 129 149 169 189 O R W K 32 760 K32 760 K32 000 130 150 170 190 O R...

Страница 14: ...3 D9973 CH4 D9904 D9914 D9924 D9934 D9944 D9954 D9964 D9974 CH5 D9905 D9915 D9925 D9935 D9945 D9955 D9965 D9975 CH6 D9900 D9999 WPLSoft FROM TO CR 8 CR 13 1 PT Offset Offset Offset 0 3 6 9 0 1 4 5 0 1...

Страница 15: ...t100 J Pt100 Cu50 C u100 Ni1000 P t1000 LG Ni1000 3 A G 1 ADC A G INA 1 CH1 2 Wire CH4 3 Wire O1 I1 I1 0 300 Ni100 Ni1000 Pt100 Pt1000 Cu50 Cu100 JPt100 LG Ni1000 0 3000 0 300 Ni100 Ni1000 Pt100 Pt100...

Страница 16: ...04PT 3 Pt100 DIN 43760 1980 JIS C1604 1989 100 3850 PPM C Pt1000 DIN EN60751 1 k 3850 PPM C Ni100 Ni1000 DIN 43760 0 300 0 3000 06PT 3 Pt100 DIN 43760 1980 JIS C1604 1989 100 3850 PPM C Pt1000 DIN EN6...

Страница 17: ...CR 04PT 06PT 0 0 O R DVP04PT E2 H 0082 DVP06PT E2 H 00C2 1 1 O R 16 2 2 O R W CH1 H 0000 CH1 0 H 0000 Pt100 180 C 800 C 1 H 0001 Ni100 80 C 170 C 2 H 0002 Pt1000 180 C 800 C 3 H 0003 Ni1000 80 C 170...

Страница 18: ...CH3 Offset 31 31 O R W CH4 Offset 32 O R W CH5 Offset 33 O R W CH6 Offset 40 40 O R W b0 b5 CH1 CH6 H 0000 41 41 X R W H 0000 43 43 X R 100 100 O R W b0 b5 CH1 CH6 0 Disable 1 Enable H 0000 101 101 X...

Страница 19: ...144 164 184 O R W KD K 29 125 145 165 185 O R W K0 126 146 166 186 O R W K0 127 147 167 187 X R 128 148 168 188 O R W H 0 H 1 H 0000 129 149 169 189 O R W K 32 760 K32 760 K32 000 130 150 170 190 O R...

Страница 20: ...63 D9973 CH4 D9904 D9914 D9924 D9934 D9944 D9954 D9964 D9974 CH5 D9905 D9915 D9925 D9935 D9945 D9955 D9965 D9975 CH6 D9900 D9999 WPLSoft FROM TO CR 8 CR 13 1 PT Offset Offset Offset 0 3 6 9 0 1 4 5 0...

Отзывы: