http://www.delta.com.tw/products/plc.asp
DVP04AD-S
DVP04AD-S
Analog Input Module
Instruction Sheet
1
WARNING
Always read this instruction thoroughly before using the DVP04AD-S.
The DC input power must be disconnected before any maintenance.
This is an OPEN-TYPE built-in DVP04AD-S, and the DVP04AD-S is certified to meet the safety
requirements of IEC 61131-2 (UL 508) when installed in the enclosure to avoid high temperature,
high humidity, exceessive vibration, corrosive gases, liquids, airbome dust or metallic particles.
Also, it is equipped with protective methods such as some special tool or key to open the
enclosure, so as to avoid the hazard to users and the damage to the DVP04AD-S.
Do not connect the AC power to any of the input/output terminals, as it might cause damage to
the DVP04AD-S. Make sure that all the wiring is well conducted prior to power on.
Do not touch the internal circuit for at least 1 minute after the power supply is disconnected.
Make sure that the DVP04AD-S is properly grounded
, to avoid any electromagnetic noise.
2
INTRODUCTION
2.1 Model Explanation and Peripherals
Thank you for choosing DELTA’s PLC DVP Series. The analog input module receives external
4-point analog signal input (voltage or current) and transforms it into 14 bits digital signal. The
analog input module of DVP04AD-S series can read/write the data of analog input module by
using commands FROM / TO via DVP-PLC SS/SA/SX Series MPU program. There are 49
CR(Control Register) in each module and there are 16 bits in each register.
DVP04AD-S analog input module can update software version by RS-485 communication. Power
unit and module are separate. Small volume and easy to install.
Users can select input from voltage or current via wiring. Voltage input range is
±
10V DC
(resolution is 1.25 mV). Current input range is
±
20 mA (resolution is 5 µA).
Nameplate Explanation
P L C m o d e l
Input power Supply Spec.
Analog Input /Output Module Spec.
Barcode, series and version
04AD-S0T3250003
VX.XX
20.4VDC ~ 28.8VDC
MADE IN XXXXX X
1.25 mV or 5 A
-10V ~ + 10V or -20mA ~ +20mA
Model Explanation
Serial Number
Model
S: for SS series MPU
P: for EP series MPU
H: for EH series MPU
XA: Analog input/output mixed module
Product Series
Input + Output points
Model type
AD: Analog input module
DA: Analog output module
PT: Platinum temperature sensors (PT-100)
TC: Thermocouple sensors (Type J/K)
Production series
Production week
Production year (2004)
Production place (Taoyuan)
Serial number of version
Production Model
RT: Resistor Thermocouple
HC: Input module of high-speed counter
PU: single axis positioning unit
2.2 Product Profile and Outline
90.00
4.00
3.00
25.20
1
2
3
4
60.00
5
6
7
8
9
3
10
●
FG
V+
I+
COM
C
H
1
FG
V+
I+
COM
C
H
2
FG
V+
I+
COM
C
H
3
FG
V+
I+
COM
C
H
4
11
12
13
3.4
90.00
60.00
3.00
14
●
UNIT: mm
1. Status indicator (Power, RUN and ERROR)
8. Expansion port
2. Model name
9. Expansion unit clip
3. DIN rail clip
10. DIN rail (35mm)
4. I/O terminals
11. RS-485 Communication port
5. I/O point indicator
12. Mounting rail of the Expansion unit
6. Mounting hole of the Expansion unit
13. DC Power input
7. Nameplate
14. Expansion port
2.3 External
wiring
Voltage Input
-10V ~ +10V
Current Input
-20mA ~ +20mA
V+
COM
Isolation Wire 1
*
*
5
FG
I+
250
Ω
~
~
V+
FG
I+
*
2
CH1
CH4
250
Ω
24+
24-
*
3
AG
+15V
-15V
DC/DC
Converter
*
4
System
Grounding
Class 3 Grounding
(100 or less)
Ω
COM
CH1
CH4
104.7K
104.7K
AG
104.7K
104.7K
AG
Isolation Wire 1
*
terminal of
power module
Note 1: Please isolate analog input and other
power wiring.
Note 2: If connect to current signal, please
short circuit between V+ and I+
terminals.
Note 3: If noise is too loud, please connect
FG to grounding.
Note 4: Please connect
terminal of
power module and
terminal of
analog input module to system
earth point and make system earth
point be grounding or connects to
machine cover.
Note 5: If wave of input terminal of loaded is
too big that noise interferes wiring,
please connect capacitance with
0.1~0.47µF 25V.
Warning: DO NOT wire to the No function
terminal .
2.4 Terminal of analog module layout
DVP04AD-S
DVP02DA-S
DVP04DA-S
DVP04PT-S
DVP04TC-S
DVP06XA-S
DVP08RT-S
V+
I+
COM
FG
V+
I+
COM
FG
I+
COM
FG
V+
I+
COM
FG
V+
V+
I+
COM
FG
V+
I+
COM
FG
V+
I+
COM
FG
V+
I+
COM
FG
V+
I+
COM
FG
V+
I+
COM
FG
L+
L-
FG
FG
I-
L+
L-
I-
L+
L-
FG
FG
I-
L+
L-
I-
L+
L-
SLD
L+
L-
L+
L-
L+
L-
SLD
SLD
SLD
V+
I+
COM
V+
I+
COM
I+
COM
V+
I+
COM
V+
V+
I+
COM
V+
I+
COM
L1+
L1-
FG
L3+
L3-
L2-
L2+
L4-
L4+
L51
L5-
FG
L7+
L7-
L6-
L6+
L8-
L8+
3
STANDARD SPECIFICATIONS
3.1 Function
Specifications
Analog/ Digital (4A/D) module
Voltage input
Current input
Power supply voltage
24 VDC(20.4VDC~28.8VDC) ( –15% ~ +20%)
Analog input channel
4 channel / each module
Analog input range
±
10V
±
20 mA
Digital conversion range
±
8000
±
4000
Resolution
14 bits(1
LSB
=1.25 mV)
13 bits (1
LSB
=5 µA)
Input impedance
200 K
Ω以上
250
Ω
Overall accuracy
±
0.5% of full scale of 25
℃
(77
℉
)
±
1% of full scale during 0~55
℃
(32~131
℉
)
Response time
3 ms
×
channels
Isolation Method
It has isolation between digital area and analog area. There is no isolation among
channels.
Absolute input range
±
15 V
±
32 mA
Digital data format
2’s complementary of 16-bit, 13 Significant Bits
Average function
Yes (CR#2~CR#5 can be set and setting range is K1~K4096)
Self diagnose function
Upper and lower bound detection / channels
Communication mode (RS-485)
MODBUS ASCII/RTU Mode. Communication baud rate of 4800 / 9600 / 19200 / 38400 /
57600 / 115200. For ASCII mode, date format is 7Bits, even, 1 stop bit (7 E 1). For RTU
mode, date format is 8Bits, even, 1 stop bit (8 E 1). The RS-485 is disabled when the
DVP04AD-S is connected in series to an MPU.
Connect to DVP-PLC MPU in series
The input point of the first analog expansion unit it connects from the near to the distant
is from 0 to 7. The Max. is 8 modules and it won’t waste digital I/O point.
3.2 Other
Specification
Power Specification
Max. Rated Consuming Power
24 VDC(20.4VDC~28.8VDC) ( –15%
〜
+20%), 2W, supply from external power
Environment Condition
Environment Condition
It is the same with DVP-PLC MPU.
Spec. of Prevent Static Electricity
All places between terminal and grounding
4
CR (Control Register)
DVP04AD-S analog signal input module
Explanation
CR
No.
RS-485
Parameter
address
Latched Register
name b15
b14
b13
b12
b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
#0
H 4000
○
R
Model type
System used, data length is 8bits (b7~b0). DVP04AD-S model code =H 88
reserved CH4 CH3 CH2 CH1
#1
H 4001
○
R/W Input
mode
setting
Input mode setting: factory setting is H0000.
Mode 0: input voltage mode (-10V~+10V).
Mode 1: input voltage mode (-6V~+10V).
Mode 2: input current mode (-12mA~+20mA)
Mode 3: input current mode(-20mA~+20mA)
Mode 4: none use.
#2
H 4002
○
R/W CH1 average times
#3
H 4003
○
R/W CH2 average times
#4
H 4004
○
R/W CH3 average times
#5
H 4005
○
R/W CH4 average times
Average times setting of channel CH1~CH4. Setting range is K1~K4096 and factory
setting is K10.
#6
H 4006
╳
R
average value of
CH1 input signal
#7
H 4007
╳
R
average value of
CH2 input signal
#8
H 4008
╳
R
average value of
CH3 input signal
#9
H 4009
╳
R
average value of
CH4 input signal
Display average value of CH1~CH4 input signal
#10 ~ #11
Reserved
#12
H 400C
╳
R
present value of CH1
input signal
#13
H 400D
╳
R
present value of CH2
input signal
#14
H 400E
╳
R
present value of CH3
input signal
#15
H 400F
╳
R
present value of CH4
input signal
Display present value of CH1~CH4 input signal
#16 ~ #17
Reserved
#18
H 4012
○
R/W To adjust OFFSET
value of CH1
#19
H 4013
○
R/W To adjust OFFSET
value of CH2
#20
H 4014
○
R/W To adjust OFFSET
value of CH3
#21
H 4015
○
R/W To adjust OFFSET
value of CH4
Offset setting of CH1~CH4. Factory setting is K0 and unit is LSB.
Voltage input: setting range is K-4000 ~K4000
Current input: setting range is K-4000 ~K4000
#22 ~ #23
Reserved
#24
H 4018
○
R/W To adjust GAIN value
of CH1
#25
H 4019
○
R/W To adjust GAIN value
of CH2
#26
H 401A
○
R/W To adjust GAIN value
of CH3
#27
H 401B
○
R/W To adjust GAIN value
of CH4
GAIN setting of CH1~CH4. Factory setting is K4000 and unit is LSB.
Voltage input: setting range is K-3200 ~K16000.
Current input: setting range is K-3200 ~K10400.
#28 ~ #29
Reserved
#30
H 401E
╳
R
Error status
It is the data register to save all error status. Please refer to fault code chart for detail.
#31
H 401F
○
R/W Communication
address setting
Setting RS-485 communication address. Setting range is 01~255 and factory setting
is K1
#32
H 4020
○
R/W Communication
baud
rate setting
It is used to set communication baud rate (4800, 9600, 19200, 38400, 57600,
115200bps). Communication format: ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1).
Communication format of RTU mode is 8Bit, even bit, 1 stop bit (8 E 1).
b0: 4800 bps (bit/sec). b1: 9600 bps (bit/sec). (factory setting)
b2: 19200 bps (bit/sec). b3: 38400 bps (bit/sec).
b4: 57600 bps (bit/sec). b5: 115200 bps (bit/sec).
b6-b13: reserved.
b14: exchange low and high byte of CRC check code (only for RTU mode)
b15: ASCII / RTU mode selection
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
Reserved CH4 CH3 CH2 CH1
#33
H 4021
○
R/W Reset
to
factory
setting and set
characteristics
adjustable priority
Factory setting is H0000.
Give CH1 setting for example:
1. When b0=0, user can set OFFSET and GAIN value of CH1 (CR#18, CR#24).
When b0=1, inhibit user to adjust OFFSET and GAIN value of CH1 (CR#18,
CR#24).
2. b1 means if characteristic register is latched. b1=0 (factory setting, latched), b1=1
(not latched).
3. When b2 is set to 1, all settings will reset to factory setting.
#34
H 4022
○
R
Software version
It is hexadecimal to display software version. For example: H 010A means 1.0A.
#35~#48 System
used
○
means latched.
╳
means not latched.
R means can read data by using FROM command or RS-485.
W means can write data by using TO command or RS-485.
LSB (Least Significant Bit): 1. Voltage input: 1
LSB
=10V/8000=2.5mV. 2. Current input: 1
LSB
=20mA/4000=5µA.
Explanation:
1.
CR#0: The content of CR#0 is model type, user can read the data from program to know if there
is expansion module.
2.
CR#1: CR#1 is used to set 4 inner channels working mode of analog input module. Every
channel has four modes to set and can be set individually. For example: if setting CH1 to mode 0
(b2~b0=000), CH2 to mode 1(b5~b3=001), CH3: mode2 (b8~b6=010), CH4: mode
3(b11~b9=011). It needs to set CR#1 to H0688 and the upper bit (b12~b15) will reserved. The
factory setting of CR#1 is H0000.
3.
CR#2 ~ CR#5: it is used to set average times of CH1~CH4. Setting range is K1~K4096 and
factory setting is K10.
4.
CR#6 to CR#9 are the average value that calculates according to the value that is set in
CR#2~CR#5 (average time of CH1~CH4 input signal). For example, if CR#2 (the average times
of CH1) is 10, it will calculate the average of CH1 input signal every 10 times.
5.
CR#10, CR#11, CR#16, CR#17, CR#22, CR#23, CR#28, CR#29 reserved.
6.
CR#12 ~ CR#15: display present value of CH1~CH4 input signal.
7.
CR #18~ CR #21: the content is the value of adjusting OFFSET value of CH1~CH4 if analog
input voltage or current is 0 after it transfers from analog to digital. Voltage setting range:
-5V~+5V(-4000
LSB
~+4000
LSB
). Current setting range: -20mA~+20mA (-4000
LSB
~+4000
LSB
).