- 8 - 

 BAT.LOW LED Indicator 

After the 24 V DC power is switched off, the data in the latched area will be stored in the 
SRAM memory, and the rechargeable battery will supply power to the SRAM memory. 
Therefore, if the battery is damaged or cannot be charged, the data in the program and 
latched area will be lost. If you need to permanently store the data in the program and 
latched data register, please refer to the mechanism of storing the data in the Flash 
ROM permanently and the mechanism of restoring the data in Flash ROM stated below. 

Mechanism of storing the data in the Flash ROM permanently: 

You can use WPLSoft (Options -> PLC<=>Flash) to indicate whether to permanently 
store the data in the latched area in Flash ROM memory (the new indicated data will 
replace all data previously saved in the memory). 

Mechanism of restoring the data in Flash ROM: 

If the rechargeable battery is in low voltage, resulting in possible loss of data in the 
program, the PLC will automatically restore the data in the latched area in the program 
and device D of Flash ROM into SRAM memory (M1176 = On) next time when DC24V is 
re-powered. The ERROR LED flashing will remind you that if the recorded program is 
able to resume its execution. You only need to shut down and re-power the PLC once to 
restart its operation (RUN). 
1.  The rechargeable lithium-ion battery in DVP-SV/SV2 is mainly used on the latched 

procedure and data storage. 

2.  The lithium-ion battery has been fully charged in the factory and is able to retain the 

latched procedure and data storage for 6 months. If DVP-SV/SV2 has not been 
powered for less than 3 months, the life of the battery does not decrease. To prevent 
the electricity emitted by the battery from resulting in short life of the battery, before 
disconnecting DVP-SV/SV2 for a long time, you need to power DVP-SV/SV2 for 24 
hours to charge the battery. 

3.  If the lithium-ion battery is put in an environment in which temperature is above 40

o

C, 

or if it is charged for more than 1000 times, its effect becomes bad, and the time for 
which the data can be stored is less than 6 moths. 

4.  The lithium-ion battery is rechargeable, and has a longer life span than an ordinary 

battery. However, it still has its own life cycle. When the power in the battery is not 
sufficient to retain the data in the latched area, please send it to the distributor for 
repair. 

5.  Please be aware of the date of manufacturing. The charged battery can sustain for 6 

months from its date of manufacture. If you find that the BAT.LOW indicator stays on 
after PLC is powered, it means the battery voltage is low and the battery is being 
charged. DVP-SV/SV2 has to remain on for more than 24 hours to fully charge the 
battery. If the indicator turns from on to “flash” (every 1 second), it means that the 
battery cannot be charged anymore. Please correctly process your data in time and 
send the PLC back to the distributor for repair. 

 Accuracy (second /month) of RTC 

Temperature (ºC/ºF) 

0/32 

25/77 

55/131 

Max. inaccuracy (second) 

-117 

52 

-132 

Содержание DVP-SV

Страница 1: ...2018 07 20 5011669009 SV12...

Страница 2: ...ute Make sure that the ground terminal on DVP SV SV2 is correctly grounded in order to prevent electromagnetic interference FR DVP SV SV2 est un module OUVERT Il doit tre install que dans une enceinte...

Страница 3: ...C Vibration shock immunity International standards IEC61131 2 IEC 68 2 6 TEST Fc IEC61131 2 IEC 68 2 27 TEST Ea Weight g 260 260 240 240 230 Input Point Spec Items 24VDC single common port input 200kH...

Страница 4: ...No isolation between digital circuits and analog circuits 1 If the scan cycle is longer than 2 milliseconds or greater than the setting value the scan cycle is given preference 2 If the value in D106...

Страница 5: ...0 75 C copper conductor 22 16AWG 1 5mm 2 DO NOT wire empty terminal DO NOT place the I O signal cable in the same wiring circuit 3 DO NOT drop tiny metallic conductor into the PLC while screwing and w...

Страница 6: ...C power supply output 24VDC 500mA 9 DVP PLC main processing unit 10 Digital I O module Input Point Wiring There are 2 types of DC inputs SINK and SOURCE See the example below For detailed point config...

Страница 7: ...are connected to the common terminals UP0 and ZP0 Y10 Y13 are connected to the common terminals UP1 and ZP1 See Figure 11b 4 Isolation circuit The optical coupler is used to isolate signals between t...

Страница 8: ...ff 1 DC power supply 2 Emergency stop 3 Circuit protection fuse 4 The output of the transistor model is open collector If Y0 Y1 is set to pulse output the output current has to be bigger than 0 1A to...

Страница 9: ...data storage 2 The lithium ion battery has been fully charged in the factory and is able to retain the latched procedure and data storage for 6 months If DVP SV SV2 has not been powered for less than...

Страница 10: ...O 8 VR1 M1179 D1179 19 I O 9 20 DIN 35mm 10 21 I O 11 DVP28SV11R DVP28SV11R2 DVP28SV11T DVP24SV11T2 DVP28SV11T2 DVP28SV11S2 24VDC 15 20 Max 2 2A 24VDC 2 5A 30VDC Polyswitch 6W 5M 500VDC ESD IEC 61131...

Страница 11: ...24VDC 5mA Off On 150ns 8 s On Off 3 s 60 s D1020 D1021 10 60 ms 10ms 1 A2 X10 X11 X14 X15 200kHz V2 00A2 2 24SV2 X12 X17 No Y0 Y7 Y10 Y13 Y0 Y4 Y6 Y5 Y7 Y10 Y13 1Hz 200kHz 10kHz 250VAC 30VDC 5 30VDC 1...

Страница 12: ...M4 DIN 35mm DIN I O 3 Figure 6 I O 1 22 16AWG 1 5mm 4 PLC 1 90 kg cm 1 65 in lbs 60 75 C 2 3 PLC PLC DVP SV SV2 1 24VDC 0V 20 4 28 8VDC 20 4VDC PLC Off ERROR LED 2 10ms PLC PLC Off PLC PLC DVP SV SV2...

Страница 13: ...5 Figure 11b 4 PLC 5 Figure 12 1 2 3 5 10A 4 1 DC 6 Figure 13 2 DC Zener On Off 6 Figure 14 5 6 7 Y3 Y4 PLC 8 9 6 Figure 15 6 Figure 17 Figure 18 1 2 3 4 Open Collector Y0 Y1 0 1A 1 6 Figure 19 Figur...

Страница 14: ...13 D Flash ROM WPLSoft PLC Flash D Flash ROM Flash ROM PLC Flash ROM D SRAM PLC RUN 1 DVP SV SV2 2 6 24 3 40o C 1000 6 4 5 6 BAT LOW DVP SV SV2 24 1 PLC C F 0 32 25 77 55 131 117 52 132...

Страница 15: ...O 8 VR1 M1179 D1179 19 I O 9 20 DIN 35mm 10 21 I O 11 DVP28SV11R DVP28SV11R2 DVP28SV11T DVP24SV11T2 DVP28SV11T2 DVP28SV11S2 24VDC 15 20 Max 2 2A 24VDC 2 5A 30VDC Polyswitch 6W 5M 500VDC ESD IEC 61131...

Страница 16: ...1 5mA 8V Off On 150ns 8 s On Off 3 s 60 s D1020 D1021 10 60 ms 10ms 1 A2 X10 X11 X14 X15 200kHz V2 00A2 2 24SV2 X12 X17 No Y0 Y7 Y10 Y13 Y0 Y4 Y6 Y5 Y7 Y10 Y13 1Hz 200kHz 10kHz 250VAC 30VDC 5 30VDC 1...

Страница 17: ...N 35mm DIN I O 3 Figure 6 I O 1 22 16AWG 1 5mm 4 PLC 1 90 kg cm 1 65 in lbs 60 75 C 2 3 PLC PLC DVP SV SV2 1 24VDC 0V 20 4VDC 28 8VDC 20 4VDC PLC Off ERROR LED 2 10ms PLC PLC Off PLC PLC DVP SV SV2 DC...

Страница 18: ...11b 4 PLC 5 Figure 12 1 2 3 5 10A 4 1 DC 6 Figure 13 2 DC Zener On Off 6 Figure 14 5 6 7 Y3 Y4 PLC 8 9 6 Figure 15 6 Figure17 Figure18 1 2 3 4 Open Collector Y0 Y1 0 1A 1 6 Figure 19 Figure20 2 Zener...

Страница 19: ...18 WPLSoft PLC Flash D Flash ROM Flash ROM 1 PLC Flash ROM D SRAM PLC RUN 1 DVP SV SV2 2 6 24 3 40o C 1000 6 4 5 6 BAT LOW DVP SV SV2 24 1 PLC C F 0 32 25 77 55 131 117 52 132...

Отзывы: