- 6 -
INA + INB input:
INA+INB
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
OUT1 control mode
10A8H
10A9H
10AAH
10ABH
10ACH
10ADH
10AEH
10AFH
Alarm
1
output
mode
10C0H 10C1H 10C2H 10C3H 10C4H 10C5H 10C6H 10C7H
Upper bound of Alarm 1 output
1080H
1081H
1082H
1083H
1084H
1085H
1086H
1087H
Lower bound of Alarm 1 output
1088H
1089H
108AH
108BH
108CH
108DH
108EH
108FH
CT value (latch)
19A0H
19A1H
19A2H
19A3H
--
--
--
--
CT value (dynamic)
19A4H
19A5H
19A6H
19A7H
--
--
--
--
3. OUT1 control mode has to be set to “0” (heating) or “1” (cooling). It cannot be set to “2” (proportional output).
4. You can select Alarm 1 or Alarm 2 to be the output contact. The output mode has to be set to “13” (000DH).
5. Adjust the upper/lower bound of the alarm output.
6. The CT value will only be measured when there is OUT1 executing. If OUT1 does not exist, the previous CT value measured will be
displayed.
EVENT Input
Function
DTE10T offers 8 channels of EVENT input (EV1 ~ EV8), and each EVENT can be
set up independently. Slot number 1 ~ 8 in AUX on DTE10T correspond to EV1 ~ EV8.
EV1 to EV8 can be short-circuited individually with slot number 9 to switch functions.
Hardware requirement: Accessory DTE20D inserted in the slot AUX.
How to Operate
1. Enable the EVENT function: Write 1234H into the address 47F1H and then 0002H into address 4824H.
bits in 4824H
Bit7
Bit6
Bit5
Bit4 Bit3 Bit2 Bit1 Bit0
Flag --
Hot runner
control
Slope control
--
Latch
CT
EVENT
--
Notes:
The flag to enable EVENT is at bit1 of 4824H. Write 0002H to bit1 to set it on.
If the “multistate” function is enabled, for example, writing in 0022H means enabling bit5 and bit1 at the same time.
You can only choose to use either the CT or EVENT function.
If there is already a set value in 4824H and you would like to modify it, reset it to 0 before you set up a new value.
2. Each channel can be set up individually for specific functions.
Addresses:
CH
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8
Address for the
EVENT function
1998H 1999H 199AH 199BH 199CH 199DH 199EH 199FH
Functions:
Set value
0
1
2
3
4
Function N/A
RUN (open circuit)
STOP (short circuit)
SV1 (open circuit)
SV2 (short circuit)
Auto (open circuit)
Manual (short circuit)
Execute (open circuit)
Pause (short circuit)
Definitions:
RUN/STOP: To enable or disable the output.
SV1/SV2: To switch between set values.
Auto/manual: To switch between the PID and manual controls.
Execute/pause: To execute or pause the counting time when in programmable PID control.
Example: If you would like the function of EVENT1 at CH1 to be “SV1/SV2”, write 0002H into address 1998H.
Slope
Function
The temperature rises according to the slope set. Unit: 0.1
°
C/min.
Example: Suppose the slope is set to “50” and SV “200.0°C”, then the temperature will rise at 5°C per minute until it reaches 200.0°C.