Http://www.delta.com.tw/industrialautomation

 

 

 

Series Temperature Controller Instruction Sheet

 

Thank you very much for choosing Delta DTD series temperature controller. Please read this instruction sheet before using your DTD to ensure proper 
operation. Keep this instruction sheet handy for quick reference.

 

 

Warning

 

 

DANGER! CAUTION! ELECTRIC SHOCK!

 When the power is on, DO NOT touch the AC terminals in case an electric shock may occur. Make sure 

the power is disconnected when you check the input power

.

   

 

DTD is an OPEN-TYPE device. If it will cause serious injury to workers or damage on other equipments when used in a dangerous environment, 
please make sure it is installed in an automatic safety protection device.

   

1.  Always use recommended solder-less terminals: Fork terminal with isolation (M3 screw, Max. width 7.2mm). Please be sure to tighten 

them properly and make sure the wire is connected to the correct terminal.   

2.  Prevent dust or metallic debris from falling into the device and cause malfunctions. DO NOT modify or uninstall DTD series without 

being permitted. DO NOT use empty terminals.   

3.  Keep away from high-voltage and high-frequency environment during installation in case of interference. Prevent using the device in 

premises which contain:     

(a) dust or corrosive gas; (b) high humidity and high radiation; (c) shock and vibration 

4.  The power has to be switched off when wiring or changing temperature sensor. 
5.  Make sure to use compensation wire which matches the thermocouple when extending or connecting the thermocouple wire.   
6.  Use wires with resistance when extending or connecting the platinum resistance sensor. 
7.  Keep the wire as short as possible when wiring a sensor to the temperature controller. Separate the power cable and load wire in 

order to prevent interference and induced noise. 

8.  DTD is an open-type device. Make sure to install it in an enclosure which prevents dust and humidity in case of an electric shock.  
9.  Make sure the power cables and signal device are installed correctly before switching on the power; otherwise serious damage may 

occur. 

10. DO NOT touch the terminals or repair the device when the power is on; otherwise an electric shock may occur 
11. Please wait for one minute after the power is switched off to allow the capacitor to discharge and DO NOT touch the internal wiring 

within this period. Use dry cloth to clean the device. DO NOT use acid or alkaline liquid to clean the device. 

 

 

Display, LED & Pushbuttons 

PV 

Present value/function display
(red 7-segment LED) 

SV 

Set value 
(green 7-segment LED) 

AT 

Flashes when PID auto-tuning
(green LED) 

OUT 

On when output (green LED) 

ALM 

On when alarm (red LED) 

 

Selecting modes 
completing setup 

 

Displaying functions 
Left-shifting the digit 

 

Ordering Information

 

DTD

0

1 2 3 4 5

 

 

Series name 

DTD: Delta D series temperature controller 

1

!

 

Up key 

 

2 3 4

 

Panel size   
(W × H) 

4848: 1/16 DIN W48 × H48 mm 
4896: 1/8 DIN W48 × H96 mm 
7272: W72 × H72 mm 

5

 

R: Relay output SPST (250VAC, 5A) 
V: Voltage pulse output 14V +10% ~ -20%   

(Max. 40mA) 

Optional 0: 

None 

 

 

Specifications

 

Power input 

AC100 ~ 240V 50/60Hz 

Input power range 

85% ~ 110%, rated voltage 

Power consumption 

6VA Max. 

Display 

7-segment LED; PV in red, SV in green 

Input temperature 
sensor 

Thermocouple: K, J, T, E, N, R, S, B, U, L, Txk 

Platinum resistance: Pt100, JPt100 
Copper resistance: Cu50 

Analog input 

Current: 0 ~ 20mA, 4 ~ 20mA 

Voltage: 0 ~ 5V, 0 ~ 10V, 0 ~ 70mV 

Display scale 

For temperature input: K2, J2, T2, Pt100-2, JPt100 and Cu50 can display to 0.1 degree; others display in 
1degree as a unit. 

Control method 

PID, PID programmable control, On/Off, manual output 

Relay output: AC 250V, 5A, SPST 

Control output type 

Voltage pulse output: DC 14V, Max. output current 40mA 

Sampling cycle 

0.4 second (including analog input signal and sensor input signal) 

Vibration resistance 

10 ~ 55Hz 10m/s

2  

3 axes 10mins 

Shock resistance 

Max. 300m/ s

2

    3 axes 6 directions, 3 times each 

Ambient temperature 

0°C ~ 50°C 

 

1

Содержание DTD Series

Страница 1: ...ce Make sure to install it in an enclosure which prevents dust and humidity in case of an electric shock 9 Make sure the power cables and signal device are installed correctly before switching on the power otherwise serious damage may occur 10 DO NOT touch the terminals or repair the device when the power is on otherwise an electric shock may occur 11 Please wait for one minute after the power is ...

Страница 2: ...rn to the screen of operation mode If the setting is current input a 249Ω resistor has to be connected to the current input terminals Setting up Input Unit In the operation mode press for more than 3 seconds and PV will display the parameter Press once to select the unit If the input type is thermocouple or platinum resistance the PV will display In this case press to select the temperature unit C...

Страница 3: ...ou can select heading default or cooling Press to return to the operation mode Setting up RUN and STOP In the operation mode press and display parameter The default is RUN Use to select STOP Press to complete the setting and the output will be disabled Setting up On Off Control Parameters Press in the operation mode If DTD is in On Off heating mode the PV will display if in On Off cooling mode the...

Страница 4: ... steps and times of execution and directly monitor the current executing step remaining time and the current SV There is only 1 group of PID parameter settings and by the first step you can directly control the temperature to the SV You can also set up the control status that after the program ends DTD will either stop the output or stay at the last SV Setting up the parameters in the program To s...

Страница 5: ...ter is flashing you can press to move to other digits Press to complete and save the setting The initial setting of the alarm option is 0000 i e all alarm options are not enabled If you need to enable all the alarm options set the parameter to 1111 Standby alarm output Set the first digit in right hand side as 1 to enable the standby mode The alarm output will be enabled when the PV is SV 2 and th...

Страница 6: ... get temperature value ADC input error The displayed value exceeds 10 999 The displayed value is smaller than 1 999 The input exceeds TP H Max temp TP L Min temp or the range of the input sensor selected How to Mount 1 Insert DTD into the panel cutout 2 Insert the mounting bracket into the mounting groove at the top and bottom of DTD 3 Push the mounting bracket forward until the bracket stops at t...

Страница 7: ...t Up Current Input Please connect a 249Ω resistor between the terminals TC and TC in parallel The content of this instruction sheet may be revised without prior notice Please consult our distributors or download the most updated version at http www delta com tw industrialautomation ...