background image

 

 

7

 

Terminals

!

DTD4848R0 

 

DTD4848V0 

 

DTD4896R0 

 

DTD4896V0 

 

DTD7272R0 

 

DTD7272V0 

 

 

How to Set Up Current Input

!

Please connect a 249

 resistor between the terminals TC+ and TC- in parallel. 

 

   

 

 
 
 

The content of this instruction sheet may be revised without prior notice. Please consult our distributors or download 

the most updated version at 

http://www.delta.com.tw/industrialautomation

Содержание DTD Series

Страница 1: ...ce Make sure to install it in an enclosure which prevents dust and humidity in case of an electric shock 9 Make sure the power cables and signal device are installed correctly before switching on the power otherwise serious damage may occur 10 DO NOT touch the terminals or repair the device when the power is on otherwise an electric shock may occur 11 Please wait for one minute after the power is ...

Страница 2: ...rn to the screen of operation mode If the setting is current input a 249Ω resistor has to be connected to the current input terminals Setting up Input Unit In the operation mode press for more than 3 seconds and PV will display the parameter Press once to select the unit If the input type is thermocouple or platinum resistance the PV will display In this case press to select the temperature unit C...

Страница 3: ...ou can select heading default or cooling Press to return to the operation mode Setting up RUN and STOP In the operation mode press and display parameter The default is RUN Use to select STOP Press to complete the setting and the output will be disabled Setting up On Off Control Parameters Press in the operation mode If DTD is in On Off heating mode the PV will display if in On Off cooling mode the...

Страница 4: ... steps and times of execution and directly monitor the current executing step remaining time and the current SV There is only 1 group of PID parameter settings and by the first step you can directly control the temperature to the SV You can also set up the control status that after the program ends DTD will either stop the output or stay at the last SV Setting up the parameters in the program To s...

Страница 5: ...ter is flashing you can press to move to other digits Press to complete and save the setting The initial setting of the alarm option is 0000 i e all alarm options are not enabled If you need to enable all the alarm options set the parameter to 1111 Standby alarm output Set the first digit in right hand side as 1 to enable the standby mode The alarm output will be enabled when the PV is SV 2 and th...

Страница 6: ... get temperature value ADC input error The displayed value exceeds 10 999 The displayed value is smaller than 1 999 The input exceeds TP H Max temp TP L Min temp or the range of the input sensor selected How to Mount 1 Insert DTD into the panel cutout 2 Insert the mounting bracket into the mounting groove at the top and bottom of DTD 3 Push the mounting bracket forward until the bracket stops at t...

Страница 7: ...t Up Current Input Please connect a 249Ω resistor between the terminals TC and TC in parallel The content of this instruction sheet may be revised without prior notice Please consult our distributors or download the most updated version at http www delta com tw industrialautomation ...

Отзывы: