TECHNICAL DATASHEET

 

Sync DIN Rail Power Supply 

12V 50W 1 Phase (NEC Class 2) / DRS-12V50W1N

□ 

 
 

  

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.

 

  www.DeltaPSU.com (March 2016, Rev. 00)  

 

3

 

Mechanical 

 

Case Cover / Chassis 

 

Plastic  

Dimensions (L x W x D) 

 

75 x 30 x 89.5 mm (2.95 x 1.18 x 3.52 inch) 

Unit Weight 

 

0.18 kg (0.40 lb) 

Indicator 

 

Green LED (DC OK) 

Cooling System 

 

Convection 

Terminal 

Input  3 Pins (Rated 300V/16A) 

 

Output  4 Pins (Rated 300V/16A) 

Wire 

Input / Output 

AWG 22-12 / AWG 20-12 

Mounting Rail 

 

Standard TS35 DIN Rail in accordance with EN 60715 

Noise (1 Meter from power supply) 

 

Sound Pressure Level (SPL) < 25dBA 

 
 

Environment 

 

Surrounding Air Temperature 

Operating  -20°C to +70°C (Cold start at -40°C @ 40% load) 

 

Storage  -40°C to +85°C 

Power De-rating 

  -10°C to -20°C de-rate power by 2% / °C 

> 55°C de-rate power by 3.33% / °C 

Operating Humidity 

  5 to 95% RH (Non-Condensing) 

Operating Altitude 

  0 to 2,000 Meters (6,560 ft.) 

Shock Test 

Non-Operating 

IEC60068-2-27, Half Sine Wave: 50G for a duration of 11ms; 
3 times per direction, 9 times in total 

 

Operating 

IEC 60068-2-27, Half Sine Wave: 10G for a duration of 11ms; 
1 time in X axis 

Vibration 

Non-Operating 

IEC 60068-2-6, Random: 5-500Hz; 2.09G

rms

, 20 min per axis 

for all X, Y, Z directions 

 

Operating 

IEC 60068-2-6, Sine Wave: 10-500Hz; 2G peak; displacement 
of 0.35mm; 1 octave per min; 60 min per axis for all X, Y, Z 
directions 

Pollution Degree 

  2 

 
 

Protections 

 

Overvoltage 

< 18.7V, SELV Output, Latch Mode 

Overload / Overcurrent 

105~120% of rated load current,  
Foldback Mode (continuous current, voltage drops), 
Auto-recovery when the fault is removed 

Over Temperature 

< 75°C Surrounding Air Temperature @ 100% load,  
Latch Mode 

Short Circuit 

Hiccup Mode, Non-Latching 
(Auto-recovery when the fault is removed) 

Internal Fuse 

T3.15A 

Degree of Protection 

IP20 

Protection Against Shock 

Class I with PE* connection 

*PE: Primary Earth 

 
 
 

 

Содержание DRS-24V30W-1AZ

Страница 1: ...wer supply is designed for industrial applications requiring highly reliable power supply that must fit in a small space The Sync series operates with universal AC input range and offers full power up...

Страница 2: ...Voltage 12Vdc Factory Set Point Tolerance 12Vdc 2 Output Voltage Adjustment Range 12 15Vdc Output Current 4A 48W max Output Power 48W Line Regulation 0 5 85 264Vac 100 load Load Regulation 1 0 85 264V...

Страница 3: ...3 C Operating Humidity 5 to 95 RH Non Condensing Operating Altitude 0 to 2 000 Meters 6 560 ft Shock Test Non Operating IEC60068 2 27 Half Sine Wave 50G for a duration of 11ms 3 times per direction 9...

Страница 4: ...ty Standards Directives Safety Entry Low Voltage SELV EN 60950 Electrical Safety TUV Bauart UL cUL recognized CB Scheme EN 60950 1 UL 60950 1 CSA C22 2 No 60950 1 File No E191395 IEC 60950 1 Limited P...

Страница 5: ...2kV Surge IEC 61000 4 5 Level 3 Criteria A 1 Common Mode 3 2kV Differential Mode 4 1kV Conducted IEC 61000 4 6 Level 3 Criteria A1 150kHz 80MHz 10Vrms Power Frequency Magnetic Fields IEC 61000 4 8 Cri...

Страница 6: ...IN Rail Power Supply 12V 50W 1 Phase NEC Class 2 DRS 12V50W1N All parameters are specified at 25 C ambient and AC input unless otherwise indicated www DeltaPSU com March 2016 Rev 00 6 Block Diagram DR...

Страница 7: ...March 2016 Rev 00 7 Device Description DRS 12V50W1NZ 1 Input terminal block connector 2 Output terminal block connector 3 DC voltage adjustment potentiometer 4 DC OK LED Green 5 Universal mounting sys...

Страница 8: ...RS 12V50W1N All parameters are specified at 25 C ambient and AC input unless otherwise indicated www DeltaPSU com March 2016 Rev 00 8 Dimensions L x W x D 75 x 30 x 89 5 mm 2 95 x 1 18 x 3 52 inch DRS...

Страница 9: ...til the surrounding air temperature is lowered or the load is reduced as far as necessary to keep the device in working condition and require removal re application of input AC voltage in order to res...

Страница 10: ...sk of explosion severe damage To guarantee sufficient convection cooling keep a distance of 80mm 3 14 inch above and below the device as well as a lateral distance of 25mm 0 98 inch to other units Not...

Страница 11: ...to 90 of its final steady state set value Hold up Time Time between the collapse of the AC input voltage and the output falling to 95 of its steady state set value Inrush Current Inrush current is the...

Страница 12: ...output current will operate in Hiccup mode The power supply will return to normal operation after the short circuit is removed Overvoltage Protection Latch Mode The power supply s overvoltage circuit...

Страница 13: ...n of the use of certain hazardous substances in electrical and electronic equipment This product conforms to this standard Fig 3 Parallel Operation Connection Diagram The power supply units PSUs can a...

Отзывы: