TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
48 V 60 W 1 Phase / DRP048V060W1B
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (September 2021, Rev. 06)
10
Safety Instructions
Vertical Mounting
•
ALWAYS switch mains of input power OFF before connecting and disconnecting the input voltage to the unit. If mains are not turned
OFF, there is risk of explosion / severe damage.
•
To guarantee sufficient convection cooling, please refer to the following instructions to ensure sufficient clearance around
the device.
Vertical Mounting: 50 mm (1.97 inch) above and below the device as well as a lateral distance of 20 mm (0.79 inch) to other
units.
Horizontal Mounting: 20 mm (0.79 inch) above and below the device as well as a lateral distance of 50 mm (1.97 inch) to
other units.
•
Note that the enclosure of the device can become very hot depending on the surrounding air temperature and load of the power
supply. Risk of burns!
•
Only plug in and unplug connectors when power is turned off!
•
DO NOT insert any objects into the unit.
•
Hazardous voltages may be present for up to 5 minutes after the input mains voltage is disconnected. Do not touch the unit during
this time.
•
The power supplies are built in units and must be installed in a cabinet or room (condensation free environment and indoor location)
that is relatively free of conductive contaminants.
•
CAUTION: “For use in a controlled environment”.
For DRP048V060W1BA:
•
The power supplies unit must be installed in an IP54 enclosure or cabinet in the final installation. The enclosure or cabinet must
comply with EN 60079-0 or EN 60079-15.
•
Warning: Explosion Hazard - Substitution of components may impair suitability for Class I, Division 2.
•
Warning: Explosion Hazard - Do not disconnect equipment or adjust potentiometer unless the power has been switched off or the
area is known to be non-hazardous.
Horizontal Mounting