background image

TECHNICAL DATASHEET

 

CliQ II DIN Rail Power Supply 

48 V 60 W 1 Phase / DRP048V060W1B

 

 

 

  

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.

 

  www.DeltaPSU.com (September 2021, Rev. 06) 

 

1

 

 

Highlights & Features 

  Universal AC input voltage range 

  Power will not de-rate for the entire input voltage range 

  Power Boost of 150% for 5 seconds 

  Full corrosion resistant aluminium casing 

  Conforms to harmonic current IEC/EN 61000-3-2, Class A 

  Extreme low temperature cold start at -40°C 

  Conformal coating on PCBAs to protect against common 

dust and chemical pollutants 

  Hazardous Locations approval to ATEX and Class I, Div 2 

(DRP048V060W1BA) 

  Certified according to IEC/EN/UL 62368-1 

 

 

Safety Standards 

 

CB Certified for worldwide use 

 

 

Model Number:

   

DRP048V060W1B

 

Unit Weight:

 

 

0.38 kg (0.84 lb) 

Dimensions (L x W x D):

  121 x 32 x 125

 

mm 

(4.76 x 1.26 x 4.92 inch)

 

 

 

General Description 

The CliQ II DIN rail power supply series from one of the world’s leading power supply companies, Delta Electronics Group, offers output 

voltage of 48  V. These products are encased in rugged yet lightweight full aluminium body that can withstand shock and vibration 

according to IEC 60068-2 standard. The series of single phase products can operate over a wide temperature range of -25°C to +80°C. 

These products also feature universal AC input voltage range from 85 Vac to 264 Vac and the power will not de-rate throughout the entire 

range. Another great feature is the conformal coating on the PCBA which allows selected models to be certified to ATEX and Class I, Div 

2 for use in hazardous locations. The design conforms to harmonic current emission IEC/EN 61000-3-2, Class A.   

 

 

Model Information 

CliQ II DIN Rail Power Supply 

 

Model  Number

 

Input Voltage Range

 

Rated Output  Voltage

 

Rated Output  Current

 

DRP048V060W1B

 

85-264 Vac (120-375 Vdc) 

48 Vdc 

1.25 A 

 

 

Model Numbering 

DR

 

P

 

048V

 

060W

 

1

 

B

 

 

DIN Rail 

Power Supply 

Output Voltage  Output Power 

Single Phase 

CliQ II Series 

A - Metal Case, 

      with Class I, Div 2 
N - Metal Case, 

      without Class I, Div 2 

 

 

Содержание DRP048V060W1B Series

Страница 1: ...supply series from one of the world s leading power supply companies Delta Electronics Group offers output voltage of 48 V These products are encased in rugged yet lightweight full aluminium body tha...

Страница 2: ...Voltage 48 Vdc Factory Set Point Tolerance 48 Vdc 1 Output Voltage Adjustment Range 48 56 Vdc Output Current 1 25 A continuously operating at 48 V 1 875 A Power Boost for 5 seconds at 48 V refer to th...

Страница 3: ...ng Humidity 5 to 95 RH Non Condensing Operating Altitude 0 to 2 500 Meters 8 200 ft Shock Test Non Operating IEC 60068 2 27 30 G 300 m S for a duration of 18 ms 1 time per direction 2 times in total V...

Страница 4: ...2 No 62368 1 File No E191395 CB scheme IEC 60950 1 IEC 62368 1 UKCA BS EN 62368 1 Industrial Control Equipment UL cUL listed UL 508 and CSA C22 2 No 107 1 01 File No E315355 CSA CSA C22 2 No 107 1 01...

Страница 5: ...teria A1 80 MHz 1 GHz 10 V M 80 modulation 1 kHz Electrical Fast Transient Burst IEC 61000 4 4 Level 3 Criteria A1 2 kV Surge IEC 61000 4 5 Level 3 Criteria A1 Common Mode2 2 kV Differential Mode3 1 k...

Страница 6: ...ATASHEET CliQ II DIN Rail Power Supply 48 V 60 W 1 Phase DRP048V060W1B All parameters are specified at 25 C ambient and AC input unless otherwise indicated www DeltaPSU com September 2021 Rev 06 6 Blo...

Страница 7: ...and AC input unless otherwise indicated www DeltaPSU com September 2021 Rev 06 7 Device Description 1 Input terminal block connector 2 Output terminal block connector 3 DC Voltage adjustment potentiom...

Страница 8: ...evice may run into Over Temperature Protection When activated the output voltage will go into bouncing mode and will recover when the surrounding air temperature is lowered or the load is reduced as f...

Страница 9: ...insert it onto the DIN rail 2 Push downwards until stopped 3 Press against the bottom front side for locking 4 Shake the unit slightly to ensure that it is secured Fig 2 2 Dismounting To uninstall pul...

Страница 10: ...evice can become very hot depending on the surrounding air temperature and load of the power supply Risk of burns Only plug in and unplug connectors when power is turned off DO NOT insert any objects...

Страница 11: ...10 to 90 of its final steady state set value Hold up Time Time between the collapse of the AC input voltage and the output falling to 95 of its steady state set value Inrush Current Inrush current is...

Страница 12: ...approved on 20 A UL and 16 A IEC branch circuits without additional protection device An external protection device is only required if the supplying branch has an ampacity greater than above Thus if...

Страница 13: ...use damage to the PSU Short Circuit Protection Auto Recovery The power supply s output OLP OCP function also provides protection against short circuits When a short circuit is applied the output curre...

Страница 14: ...d from Vout Please note that output voltage Vout from DRR module will be VO output voltage of power supply Vdrop in DRR module Vdrop will vary from 0 60 V to 0 90 V Typical 0 65 V depending on the loa...

Страница 15: ...ort circuit V1 V1 will come across V2 V2 which means connecting 2 power supplies in opposite polarity and may cause damage to the power supply With reverse bias diodes in place the voltage across each...

Страница 16: ...arth wire or to the machine ground Fig 9 2 of 3 Phase System Input Operation Connection Diagram 2 of 3 Phase System Input Operation Delta s CliQ II can use on 2 of 3 phase system Please refer to the f...

Страница 17: ...user does not profit from fulfilling this standard therefore it is important to know whether it is mandatory to meet this standard for a specific application Attention Delta provides all information...

Отзывы: