background image

TECHNICAL DATASHEET

 

CliQ DIN Rail Power Supply 

24 V 60 W 1 Phase / DRP024V060W1AZ

 

 

 

  

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.

 

  www.DeltaPSU.com (September 2021, Rev. 10) 

 

1

 

 

Highlights & Features 

  Universal AC input voltage range 

  Power will not de-rate for the entire input voltage range 

  Power Boost of 150% for 3 seconds 

  Rugged and compact design (Vibration 5 G, Shock 30 G) 

  Conforms to harmonics current IEC/EN 61000-3-2, Class A 

  Wide operating temperature range -20°C to 80°C 

  Overvoltage / Overcurrent / Over Temperature / Short Circuit 

Protections 

  Certified according to IEC/EN/UL 62368-1 

 

 

Safety Standards 

 

CB Certified for worldwide use 

 

 

Model Number:

   

DRP024V060W1AZ 

Unit Weight:

 

 

0.33 kg (0.73 lb) 

Dimensions (L x W x D):

  120.6 x 32 x 113

 

mm 

   

 

 

(4.75 x 1.26 x 4.45 inch)

 

 

 

General Description 

The DRP024V060W1AZ is part of the CliQ DIN rail power supply series from one of the world’s leading power supply companies, Delta 

Electronics Group,  offers state-of-the-art designs made to withstand harsh industrial environments. Its rugged plastic casing has a 

compact body at only 32 mm, which is both shock and vibration resistant according to IEC 60068-2 standard. The DRP024V060W1AZ 

operates within a wide temperature range from -20°C to +80°C and universal AC input voltage range from 85 Vac to 264 Vac, the power 

will not de-rate for the entire input voltage range value. The single phase power supply unit includes overvoltage, overcurrent, over 

temperature and short circuit protections. The feature built-in Power Boost of 150% for 3 seconds enables reserve power to be always 

available for reliable startup of loads with high inrush current, thus eliminating the need of a more expensive power supply unit at higher 

power rating.  

 

 

Model Information 

CliQ DIN Rail Power Supply 

 

Model  Number

 

Input Voltage Range

 

Rated Output  Voltage

 

Rated Output  Current

 

DRP024V060W1AZ

 

85-264 Vac (120-375 Vdc) 

24 Vdc 

2.50 A 

 

 

Model Numbering 

DR

 

P

 

024V

 

060W

 

1

 

A

 

Z

 

DIN Rail 

Power Supply 

Output Voltage  Output Power 

Single Phase 

CliQ Series 

Plastic Case 
 

 

 

 

Содержание DRP024V060W1AZ

Страница 1: ...companies Delta Electronics Group offers state of the art designs made to withstand harsh industrial environments Its rugged plastic casing has a compact body at only 32 mm which is both shock and vi...

Страница 2: ...Nominal Output Voltage 24 Vdc Factory Set Point Tolerance 24 Vdc 2 Output Voltage Adjustment Range 22 28 Vdc Output Current 2 50 A continuously operating at 24 V 3 75 A Power Boost for 3 seconds at 2...

Страница 3: ...l Mounting 10 C to 20 C output power is 80 of rated power 0 C de rate power by 2 C 50 C de rate power by 2 5 C 70 C de rate power by 4 C Operating Humidity 5 to 95 RH Non Condensing Operating Altitude...

Страница 4: ...ltage SELV IEC 60950 1 Electrical Safety SIQ Bauart EN 62368 1 UL cUL recognized UL 60950 1 and CSA C22 2 No 60950 1 File No E191395 UL 62368 1 and CSA C22 2 No 62368 1 File No E191395 cCSAus CSA C22...

Страница 5: ...ria A1 80 MHz 1GHz 3 V M 80 modulation 1kHz Electrical Fast Transient Burst IEC 61000 4 4 Level 3 Criteria A1 2 kV Surge IEC 61000 4 5 Level 3 Criteria A1 Common Mode2 2 kV Differential Mode3 2 kV Con...

Страница 6: ...ecified at 25 C ambient and AC input unless otherwise indicated www DeltaPSU com September 2021 Rev 10 6 Block Diagram Device Description 1 Input terminal block connector 2 Output terminal block conne...

Страница 7: ...t voltage will go into bouncing mode and will recover when the surrounding air temperature is lowered or the load is reduced as far as necessary to keep the device in working condition 3 In order for...

Страница 8: ...UL 62368 flexible cables require ferrules Use appropriate copper cables designed to sustain operating temperature of at least 75 C or more to fulfill UL requirements Dismounting Fig 2 1 Mounting Snap...

Страница 9: ...o ensure sufficient clearance around the device Vertical Mounting 50 mm 1 97 inch above and below the device as well as a lateral distance of 20 mm 0 79 inch to other units Horizontal Mounting 50 mm 1...

Страница 10: ...90 of its final steady state set value Hold up Time Time between the collapse of the AC input voltage and the output falling to 95 of its steady state set value Inrush Current Inrush current is the pe...

Страница 11: ...ted and approved on 20 A UL and 16 A IEC branch circuits without additional protection device An external protection device is only required if the supplying branch has an ampacity greater than above...

Страница 12: ...rrent will operate in Hiccup mode as shown in the illustration in the OLP OCP section on this page The power supply will return to normal operation after the short circuit is removed Overvoltage Prote...

Страница 13: ...stem load from Vout Please note that output voltage Vout from DRR module will be VO output voltage of power supply Vdrop in DRR module Vdrop will vary from 0 60V to 0 90V Typical 0 65V depending on th...

Страница 14: ...earth wire or to the machine ground Fig 7 2 of 3 Phase System Input Operation Connection Diagram 2 of 3 Phase System Input Operation Delta s CliQ can use on 2 of 3 phase system Please refer to the fol...

Страница 15: ...for any claim or action arising from any error for the provided information in the datasheets Customer shall take its responsibility for evaluation of using the product before placing an order with De...

Отзывы: