TECHNICAL DATASHEET
CliQ DIN Rail Power Supply
24 V 60 W 1 Phase / DRP024V060W1AZ
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (September 2021, Rev. 10)
14
Fig. 6 DC Input Operation Connection Diagram
DC Input Operation
Step 1.
Use a battery or similar DC source.
Step 2.
Cpole to L and -pole to N.
Step 3.
Connect the PE terminal to an earth wire or to the machine ground.
Fig. 7 2 of 3 Phase System Input Operation Connection Diagram
2 of 3 Phase System Input Operation
Delta's CliQ can use on 2 of 3 phase system. Please refer to the following step.
Step 1.
The input voltage applied from Line to Neutral is below the maximum rated input. The input voltage shall be below 10%.
Step 2.
The external protector is needed on N (Neutral) input line to secure a safety. N line does not have internal fuse protection. An appropriate
fuse or circuit breaker should be connected in series with N input line connection like the following.