background image

 

 

 

Installation & Application Guide 

 

 

Delta Field Module (4 Pulse Inputs) 

 

 

DFM-400P (Rev 1.2) 

Document Edition 1.6

 

Product Description 

The Delta Field Modules are small expansion I/O boards 

that provide remotely expandable I/O to Delta’s BACnet 
Controllers.  The DFM-400P Pulse Input Field Module 

provides four pulsed inputs and communicates directly on 
a BACnet RS-485 MS/TP network where it functions as an 

independent BACnet device and the pulse counter values 
and PI objects are accessible over the MS/TP network. 
Ideal for electrical, water, gas, and various flow meters, 
the DFM-400P has four pulse inputs.  Two inputs support 

pulses from 0 to 200 Hz and the other two inputs support 
pulses from 0 to 2000 Hz. 
Any additional strategies associated with the pulse 
counter values are typically programmed in GCL in other 

controllers on the network. 

 

 
 

 
 

 

Contents 

Model Numbers.......................................................................................................................... 2

 

Package Contents ...................................................................................................................... 2

 

Other Relevant Documents ........................................................................................................ 2

 

Important Information ............................................................................................................... 2

 

Product Specifications ............................................................................................................... 3

 

Board Layout (DFM-400P) .......................................................................................................... 4

 

Device Address DIP Switches .................................................................................................... 5

 

Indicators ................................................................................................................................... 5

 

Jumpers ..................................................................................................................................... 5

 

Mounting .................................................................................................................................... 7

 

Input Wiring ................................................................................................................................ 7

 

Power ......................................................................................................................................... 7

 

Network & Cabling Requirements ............................................................................................. 7

 

Network Topology ...................................................................................................................... 8

 

Network Communications Setup ............................................................................................... 8

 

Application Notes ....................................................................................................................... 9

 

Cautions and Warnings ............................................................................................................ 13

 

Compliance Declarations ......................................................................................................... 13

 

Содержание DFM-400P

Страница 1: ...al for electrical water gas and various flow meters the DFM 400P has four pulse inputs Two inputs support pulses from 0 to 200 Hz and the other two inputs support pulses from 0 to 2000 Hz Any addition...

Страница 2: ...Guide ORCAview Technical Reference Manual particularly Appendix G in the V3 22 Manual Important Information The Pulse Input Field Module is designed to work with Application Controller products starti...

Страница 3: ...Inputs 2 Pulse Inputs PP1 and PP2 0 2000 Hz each or actual maximum of about 1950 2 Pulse Inputs PP3 and PP4 0 200 Hz each Monitors either Dry Contact or Open Collector signals Jumper selectable DEBOUN...

Страница 4: ...DFM 400P Rev 2 1 Installation and Appplication Guide Edition 1 6 Page 4 of 14 Board Layout...

Страница 5: ...device is transmitting out the associated port and a red LED flashes to indicate when the device is receiving data through the port Jumpers DEBOUNCE DEBOUNCE Debounce circuitry which may be necessary...

Страница 6: ...ess from higher up devices may be enabled or disabled via jumper setting Enabled With the jumper in place the device automatically obtains portions of its overall BACnet device address as related to A...

Страница 7: ...ust be powered separately Network Cabling Requirements To ensure network stability and reliable communications particularly at high speeds on a BACnet RS 485 MS TP network it is imperative that you ad...

Страница 8: ...s that there is one other device configured as a System level device on the network 2 Pulse Input Field Modules Configured as LINKnet Devices Not applicable for the DFM 400P Field Module as it can onl...

Страница 9: ...Setup tab 60 AV4 PI1 Number of Sample Intervals Number of Intervals from PI Adv 5 AV5 PI1 Total Pulses Total Pulses from PI Data tab N A AV6 PI2 Converted Pulse Rate Pulse Value PI2 Present Value N A...

Страница 10: ...Input Field Module does not support this property There is no need when the hardware supports a jumper configurable debounce COV The PI objects each have a COV setting that is used globally for all of...

Страница 11: ...y the sample interval time and verify that the result remains within the Maximum Pulses per Sample Time as listed above Notice that only PP1 and PP2 are designed to handle the higher pulse rates In an...

Страница 12: ...ulse values MS TP Connection Objects All of the existing predefined DFM 400P objects are readily accessible over the MS TP network GCL Programming Write GCL programs in other controllers on the networ...

Страница 13: ...adian Interference Causing Equipment Regulations Cet appareil num rique de la Classe A Respecte toutes les exigences du R glement sur le mat rial brouiller du Canada UL Compliance Information This pro...

Страница 14: ...ns Class A EN 61000 3 2 1999 Power Line Harmonics Class D EN 61000 3 3 1998 Power Line Fluctuations Pst 1 Plt 0 65 EN50082 1 1997 Generic Immunity Standard Part 1 Residential EN 61000 4 2 1995 ESD Imm...

Отзывы: