background image

DFM-400P Rev 2.1 Installation and Appplication Guide  Edition 1.6 

Page 7 of 14

 

 

 

 

Mounting 

The DFM-400P includes a plastic enclosure that can be mounted quickly and easily with two screws in an 
appropriate location, or within another enclosure (to meet code requirements). 
The Rev 1.2 DFM-400P enclosure can be snapped into a 35mm DIN rail. 

Input Wiring 

Pulse Inputs on the Pulse Input Field Module follow the same general wiring diagrams for dry contact 

and open collector connections as other Delta products.  Refer to separate documentation for additional 
details. 

Power 

The Pulse Input Field Module requires a 24 VAC @ 2 VA power supply, typically an isolated Class II 

transformer.  More than one device – not including DCUs or V2 products – may be connected to the same 
transformer, providing the transformer is properly sized, including line losses, and polarity is observed 

between controllers (in regards to 24~ and GND).  The transformer must ONLY be used to provide power 
to other MS/TP devices.  Auxiliary field devices (i.e., 4-20 mA devices) that don’t use ½ wave rectification 

must be powered separately. 

Network & Cabling Requirements 

To ensure network stability and reliable communications, particularly at high speeds on a BACnet RS-

485 MS/TP network, it is imperative that you adhere to the following network and cabling requirements: 

Item 

Description 

Cabling 

For BACnet MS/TP networks it is recommended that you use network cabling that 
matches the following specifications: 

 

Balanced 100 to 120 ohm nominal impedance Twisted Shielded Pair (TSP) Cable 

 

Nominal capacitance of 16 PF/FT or lower  

 

Nominal velocity of propagation of 66% or higher 

Topology 

For BACnet MS/TP networks, ensure the cable is installed as a 

daisy-chain

 from one 

device to the next. 

Max. Nodes 

The maximum number of devices per BACnet MS/TP network without any repeaters 
is 

50

Termination 
Boards 

A termination board 

must

 be installed at each end of each BACnet MS/TP network 

segment – or two per BACnet MS/TP network.  Ensure you do not overlook this in 

laying out your network architecture and ordering product. 

Repeater 

A repeater (RPT-768) is not necessary unless more than 50 nodes will be installed on 
a network 

or

 you need to extend the network beyond 4000 ft (1220 m). 

For more detailed information, including wiring, refer to the Delta Controls Wiring and Installation Guide 

Содержание DFM-400P

Страница 1: ...al for electrical water gas and various flow meters the DFM 400P has four pulse inputs Two inputs support pulses from 0 to 200 Hz and the other two inputs support pulses from 0 to 2000 Hz Any addition...

Страница 2: ...Guide ORCAview Technical Reference Manual particularly Appendix G in the V3 22 Manual Important Information The Pulse Input Field Module is designed to work with Application Controller products starti...

Страница 3: ...Inputs 2 Pulse Inputs PP1 and PP2 0 2000 Hz each or actual maximum of about 1950 2 Pulse Inputs PP3 and PP4 0 200 Hz each Monitors either Dry Contact or Open Collector signals Jumper selectable DEBOUN...

Страница 4: ...DFM 400P Rev 2 1 Installation and Appplication Guide Edition 1 6 Page 4 of 14 Board Layout...

Страница 5: ...device is transmitting out the associated port and a red LED flashes to indicate when the device is receiving data through the port Jumpers DEBOUNCE DEBOUNCE Debounce circuitry which may be necessary...

Страница 6: ...ess from higher up devices may be enabled or disabled via jumper setting Enabled With the jumper in place the device automatically obtains portions of its overall BACnet device address as related to A...

Страница 7: ...ust be powered separately Network Cabling Requirements To ensure network stability and reliable communications particularly at high speeds on a BACnet RS 485 MS TP network it is imperative that you ad...

Страница 8: ...s that there is one other device configured as a System level device on the network 2 Pulse Input Field Modules Configured as LINKnet Devices Not applicable for the DFM 400P Field Module as it can onl...

Страница 9: ...Setup tab 60 AV4 PI1 Number of Sample Intervals Number of Intervals from PI Adv 5 AV5 PI1 Total Pulses Total Pulses from PI Data tab N A AV6 PI2 Converted Pulse Rate Pulse Value PI2 Present Value N A...

Страница 10: ...Input Field Module does not support this property There is no need when the hardware supports a jumper configurable debounce COV The PI objects each have a COV setting that is used globally for all of...

Страница 11: ...y the sample interval time and verify that the result remains within the Maximum Pulses per Sample Time as listed above Notice that only PP1 and PP2 are designed to handle the higher pulse rates In an...

Страница 12: ...ulse values MS TP Connection Objects All of the existing predefined DFM 400P objects are readily accessible over the MS TP network GCL Programming Write GCL programs in other controllers on the networ...

Страница 13: ...adian Interference Causing Equipment Regulations Cet appareil num rique de la Classe A Respecte toutes les exigences du R glement sur le mat rial brouiller du Canada UL Compliance Information This pro...

Страница 14: ...ns Class A EN 61000 3 2 1999 Power Line Harmonics Class D EN 61000 3 3 1998 Power Line Fluctuations Pst 1 Plt 0 65 EN50082 1 1997 Generic Immunity Standard Part 1 Residential EN 61000 4 2 1995 ESD Imm...

Отзывы: