4.1.7 System calibration procedure
The system is pre-calibrated by Delta Power Solutions. Calibration is not needed unless some changes
have been made to the System hardware or the interfacing sensors is different from measurements made
with calibrated test equipment during maintenance. Thus system calibration is
4.1.8 Conforming the Configuration
All the parameter values come pre-set from the factory and should not be changed without valid reason.
Only configuration that is recommended on site is setting no. of inverters and APN.
Check the configuration logging in Pushpak II locally. The web user interface is protected against
unauthorized access by username and password.
Step 1. Login to the PUSHPAK II using Google Chrome browser using
IP Address 192.168.100.30
.
Step 2. Go to
Configure>Site
to set NOC Configuration and inverters numbers.
Step 3. Go to
Configure>NOC
to set server configurations.
Step 4. Go to
Configure>PORTS
for Ethernet Port settings.
Step 5. Go to
Configure>Clock
to set Date & Clock.
1
Check
all LED’s are functioning
accordingly.
2
No tools should be left inside the
system.
3
Check equipments top cover is properly
closed before leaving the site.
4
Check system is communicating with
remote server & verify site data.
NOTE
PARAMETERS ARE NOT ALLOWED TO CALIBRATE ONSITE, IF
REQUIRED PLEASE CONTACT CUSTOMER CARE.
NOTE
SITE ID, SITE NAME, SITE ADDRESS ARE NOT IMPORTANT THAT CAN
BE LEFT DEFAULT.
NOTE
DO NOT CHANGE RS485 PORT SETTINGS DEFAULT BAUDE RATE IS
9600.