Chapter 14 Fault Codes and Descriptions
CP2000
14-3
ID*
Display on LCD Keypad
Fault Name
Fault Descriptions
2
Over-current during
deceleration
(ocd)
Output current exceeds 2.4 times of rated current during
deceleration.
When ocd occurs, the drive closes the gate of the
output immediately, the motor runs freely, and the
display shows an ocd error.
Action and Reset
Action level
240% of rated current
Action time
Immediately act
Fault treatment parameter
N/A
Reset method
Manual reset
Reset condition
Reset in 5 sec. after the fault is cleared
Record
Yes
Cause
Corrective Actions
Deceleration time too short
1. Increase the deceleration time
2. Increase the deceleration time of S-curve
3. Set auto-acceleration and auto-deceleration parameter (Pr.01-44)
4. Set over-current stall prevention function (Pr.06-03)
5. Replace the drive with a larger capacity model
Check if the mechanical brake of
the motor activates too early
Check the action timing of the mechanical brake
Short-circuit at motor output due to
poor insulation wiring
Check the motor cable and remove causes of the short circuits, or replace the
cable before turning on the power.
Check for possible burnout or
aging insulation of the motor
Check the motor insulation value with megger. Replace the motor if the
insulation is poor.
The load is too large
Check if the output current during the whole working process exceeds the AC
motor drive’s rated current. If yes, replace the AC motor drive with a larger
capacity model.
Impulsive change of the load
Reduce the load or increase the capacity of AC motor drive.
Use special motor or motor with
larger capacity than the drive
Check the motor capacity (the rated current on the motor’s nameplate should
≦
the rated current of the drive)
Use ON/OFF controller of an
electromagnetic contactor at the
output (U/V/W) of the drive
Check the action timing of the contactor and make sure it is not turned ON/OFF
when the drive outputs the voltage.
V/F curve setting error
Adjust V/F curve settings and frequency/voltage. When the fault occurs, and the
frequency voltage is too high, reduce the voltage.
Torque compensation is too large
Adjust the torque compensation (refer to Pr.07-26 torque compensation gain)
until the output current reduces and the motor does not stall.
Malfunction caused by interference
Verify the wiring of the control circuit and wiring/grounding of the main circuit to
prevent interference.
The length of motor cable is too
long
Increase AC motor drive’s capacity
Install AC reactor(s) on the output side (U/V/W)
Hardware error
The ocd occurs due to short circuit or ground fault at the output side of the drive.
Check for possible short circuits between terminals with the electric meter:
B1 corresponds to U, V and W; DC- corresponds to U, V and W;
corresponds to U, V and W.
If short circuits occur, return to the factory for repair.
Check if the setting of stall
prevention is correct
Set the stall prevention to the proper value.
Содержание CP2000 Series
Страница 3: ......
Страница 12: ...Chapter 1 Introduction CP2000 1 3 1 2 Model Name 1 3 Serial Number...
Страница 35: ...Chapter 1 Introduction CP2000 1 26 Digital Keypad KPC CC01 Figure 1 32...
Страница 36: ...Chapter 2 Installation CP2000 2 1 Chapter 2 Installation 2 1 Mounting Clearance 2 2 Flow and Power Dissipation...
Страница 42: ...Chapter 3 Unpacking CP2000 3 1 Chapter 3 Unpacking 3 1 Unpacking 3 2 The Lifting Hook...
Страница 72: ...Chapter 4 Wiring CP2000 4 1 Chapter 4 Wiring 4 1 System Wiring Diagram 4 2 Wiring...
Страница 77: ...Chapter 4 Wiring CP2000 4 6 Figure 4 5...
Страница 78: ...Chapter 4 Wiring CP2000 4 7 4 2 1 SINK NPN SOURCE PNP Mode Figure 4 6 Figure 4 7 Figure 4 8 Figure 4 9...
Страница 79: ...Chapter 4 Wiring CP2000 4 8 This page intentionally left bank...
Страница 109: ...Chapter 6 Control Terminals CP2000 6 12 This page intentionally left blank...
Страница 171: ...Chapter 7 Optional Accessories CP2000 7 62 EMC Filter Dimension EMC filter model name EMF021A23A EMF014A43A Figure 7 45...
Страница 172: ...Chapter 7 Optional Accessories CP2000 7 63 EMC filter model name EMF018A43A Figure 7 46...
Страница 173: ...Chapter 7 Optional Accessories CP2000 7 64 EMC filter model name EMF056A23A EMF039A43A Figure 7 47...
Страница 174: ...Chapter 7 Optional Accessories CP2000 7 65 EMC filter model name KMF370A KMF3100A Figure 7 48...
Страница 175: ...Chapter 7 Optional Accessories CP2000 7 66 EMC filter model name B84143D0150R127 Figure 7 49...
Страница 176: ...Chapter 7 Optional Accessories CP2000 7 67 EMC filter model name B84143D0200R127 Figure 7 50...
Страница 182: ...Chapter 7 Optional Accessories CP2000 7 73 Wall Mounting Embedded Mounting...
Страница 197: ...Chapter 7 Optional Accessories CP2000 7 88 6 Installation complete...
Страница 237: ...Chapter 7 Optional Accessories CP2000 7 128 This page intentionally left blank...
Страница 242: ...Chapter 8 Option Cards CP2000 8 5 Communication extension card Slot 1 CMC PD01 CMC DN01 CMC EIP01 EMC COP01 CMC PN01...
Страница 245: ...Chapter 8 Option Cards CP2000 8 8 I O Relay Card EMC D42A EMC D611A EMC R6AA EMC BPS01 EMC A22A...
Страница 247: ...Chapter 8 Option Cards CP2000 8 10 I O Relay Card EMC D42A EMC D611A EMC R6AA EMC BPS01 EMC A22A...
Страница 265: ...Chapter 8 Option Cards CP2000 8 28 This page intentionally left blank...
Страница 277: ...Chapter 09 Specifications CP2000 9 12 575V 690V Figure 9 3 Altitude Derating Curve Figure 9 4...
Страница 279: ...Chapter 09 Specifications CP2000 9 14 230V 460V Advanced Control Pr 00 11 2 PM SVC Pr 05 33 1 2 Figure 9 7 Figure 9 8...
Страница 281: ...Chapter 09 Specifications CP2000 9 16 9 8 Efficiency Curve Figure 9 11 Figure 9 12...
Страница 317: ...Chapter 10 Digital Keypad CP2000 10 36 This page intentionally left blank...
Страница 355: ...Chapter 11 Summary of Parameter Settings CP2000 11 38 11 Advanced Parameters Group 11 Advanced Parameters are reserved...
Страница 361: ...Chapter 11 Summary of Parameter Settings CP2000 11 44 This page intentionally left blank...
Страница 416: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 3 3 4 5...
Страница 417: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 4 6 7 8...
Страница 418: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 5 9 10 11...
Страница 419: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 6 12 13 14...
Страница 420: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 7 15 16 17...
Страница 421: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 8 18 19 20...
Страница 422: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 9 21 22 23...
Страница 423: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 10 24 25 26...
Страница 424: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 11 27 28 29...
Страница 425: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 12 30 31 32...
Страница 426: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 13 33 34 35...
Страница 427: ...Chapter 12 Description of Parameter Settings CP2000 12 1 03 14 36 37 38...
Страница 528: ...12 Description of Parameter Setting CP2000 12 1 11 1 11 Advanced Parameters Group 11 Advanced parameters are reserved...
Страница 560: ...Chapter 12 Description of Parameter Settings CP2000 12 2 00 6 III PM SVC Carrier Start up Adjustment...
Страница 835: ...Chapter 16 PLC Function Applications CP2000 16 152 Step 3 Physical configuration CP2000 Step 4 Write to PLC program...
Страница 836: ...Chapter 16 PLC Function Applications CP2000 16 153...
Страница 838: ...Chapter 16 PLC Function Applications CP2000 16 155...
Страница 841: ...Chapter 16 PLC Function Applications CP2000 16 158 This page intentionally left blank...
Страница 857: ...Chapter 17 Introduction to BACnet CP2000 17 16 This page intentionally left blank...