Delta Endüstriyel Makine Ürünleri ve Danışmanlık Ltd
İkitelli OSB Dersan Blok Sk. TRIOS B Blok No:92 Başakşehir-İstanbul
Tel: +90 212 674 72 03 E-mail:
A
IR
M
A
ST
ER
ELEMENT TYPE
UNIT
OF
SF
PF
CF
ELEMENT DEFINITION
Prefilter
Fine
Prefilter Fine Filter
A.Carbon
Filter
Partical Removal/
Partielle Entfernung
micron
3
0,1
0,01
-
Max Oil Carryover at 21
Cº
Maximaler
Ölmengen-Übertrag bei 21 Cº mg/m3
-
0,1
0,01
0,003
Initial Pressure Loss (New&Dry)
Anfangsdruckverlust (Neu&Trocken)
mbar
35
60
80
60
Pressure Loss for Element Change
Elementwechsel bei Druckverlust
mbar
700
700
700
700
AIRMASTER Filter Grade OF
ISO 8573.1-2010 Quality Class;
Solids: Class 3 Oil content: Class 4
Maximum inlet liquid load: 2.000 ppm w/w
Application Areas;
Upstream of ultra high efficiency oil
removal filters.
Downstream of aftercoolers
Downstream of heatless adsorption
dryers.
In case an aftercooler/separator
installed upstream… if needed
AIRMASTER-Filterklasse OF
ISO 8573.1-
2010 Qualitätsklasse:
Feststoffe: Klasse 3
Ölgehalt: Klasse 4
Maximale Einlass-
Flüssigkeitsbelastung:
2.000 ppm w/w
Anwendungsbereiche:
Als Vorfilter vor Ultra
Hochleistungsfiltern zur
Ölabscheidung.
Als Wasserabscheider nach
Druckluft Nachkühlern
Als Vorfilter für Kälte-
Drucklufttrockner
AIRMASTER Filter Grade SF
ISO 8573.1-2010 Quality Class;
Solids: Class 1 Oil content: Class 2
Maximum inlet liquid load: 1.000 ppm w/w
Application Areas;
Upstream of desiccant or
membrane dryers
Downstream of refrigerated dryers
Downstream of pressure-swing
desiccant
dryers for fine particulate removal
AIRMASTER Filterklasse SF
ISO 8573.1-
2010 Qualitätsklasse:
Feststoffe: Klasse 1
Ölgehalt: Klasse 2
Maximale Einlass-
Flüssigkeitsbelastung:
1.000 ppm w/w
Anwendungsbereiche:
Bei Bedarf als Vorfilter für Ultra
Hochleistungsfilter zur
Ölabscheidung, vor
Adsorptions- oder Membranetrocknern.
Als Staubfilter nach Adsoptionstrocknern
zum ausfiltern des Trockenmittelabriebes
Als Nachfilter von Druckluft-
Kältetrocknern
AIRMASTER Filter Grade PF
ISO 8573.1-2010 Quality Class;
Solids: Class 1 Oil content: Class 1
Maximum inlet liquid load: 100 ppm w/w
Application Areas;
Upstream of adsorption or
membrane dryers (use a Grade SF
filter as a prefilter if needed
Downstream of refrigerated dryers
Downstream of adsorption dryers
AIRMASTER Filterklasse PF
ISO 8573.1-
2010 Qualitätsklasse;
Feststoffe: Klasse 1
Ölgehalt: Klasse 1
Maximale Einlass-
Flüssigkeitsbelastung:
100 ppm w/w
Anwendungsbereiche:
als Vorfilter vor Adsorptions- oder
Membrantrocknern
(verwenden Sie bei Bedarf einen
Filter der Filterklasse SF als
Vorfilter)
dem Kälte-Drucklufttrockner