Accessory 24E2S
Hardware Setup
7
HARDWARE SETUP
Switch Configuration
UMAC Address DIP Switch S1
S1-1
S1-3
S1-4
Board No.
IC No.
I-Variable Range
Base Address
ON
ON
ON
1
2
I7200
$078200
OFF
ON
ON
2
3
I7300
$078300
ON
OFF
ON
3
4
I7400
$079200
OFF
OFF
ON
4
5
I7500
$079300
ON
ON
OFF
5
6
I7600
$07A200
OFF
ON
OFF
6
7
I7700
$07A300
ON
OFF
OFF
7
8
I7800
$07B200
OFF
OFF
OFF
8
9
I7900
$07B300
S1, S1-3, S1-4 are used to address the Acc-24E2S as shown in this table.
S1-2
S1-5
S1-6
Function
ON
ON
ON
3U Turbo PMAC Use
S1-2, S1-5, and S1-6 are used to determine whether the Acc-24E2S is communicating to a Turbo
3U PMAC or a MACRO Station CPU.
MACRO Station Address DIP Switch S1
S1-1, S1-2, S1-3, S1-4 are used to address the Acc-24E2 as shown in the table below.
S1-1
S1-2*
S1-3
S1-4
Board No.
IC No.
Base Address
ON
ON
OFF
OFF
1
2
$00C040
OFF
OFF
OFF
OFF
2
3
$00C060
* Always set to OFF for legacy MACRO Stations (part number 602804-100 thru 602804-104)
S1-5 and S1-6 are used to determine whether the Acc-24E2 is communicating to a Turbo 3U PMAC or a
MACRO Station CPU.
S1-5
S1-6
Function
OFF
OFF
3U MACRO Station use
Acc-24E2 Clock Settings
The Phase Clock and Servo Clock must be configured on each Acc-24E2S. Each system can have only
one source for the servo and phase clocks and jumpers must be set appropriately to avoid a timing conflict
or a watchdog condition.
Starting in UMAC-Turbo firmware version 1.937, the firmware will set the clock settings automatically
for the Acc-24E2 cards in the UBUS. To enable this feature, set jumper E16 from 2 to 3 for all of the
Acc-24E2Ss plugged into the UMAC. At re-initialization (either
$$$***
command or power up with E3
jumpered on UMAC), the firmware will know that all of the cards are in the auto configuration setup and
will assign the card with the lowest base address setting (usually $78200) the task of sourcing the clocks
by setting variable I19 to the appropriate register. The clocks will be set initially to the factory default
servo update cycle and phase clock cycle. For a better understanding of this feature, refer to the
description of I19 in the Turbo Software Reference Manual.
For UMAC Turbo systems with firmware older than version 1.937, set one of the Acc-24E2s to transmit
(E16 set 2-3) the phase and servo clock (usually the card at the lowest base address setting) and set the
rest of the Acc-24E2s to receive (E16 set 1-2) the phase and servo clocks.
For MACRO systems, the clock select jumper should be set to receive servo and phase clocks. For the
Acc-24E2S, E16 should be set 1-2.